Menu Overview
Press
Prg
Esc
to enter menus.
c. BMS Config
d. Service Settings
Service
Manufacturer
Service Password
Insert service
password (PW1):
0000
Service Password
Insert service
password (PW1):
0000
Manufacturer Password
Insert service
password (PW1):
0000
BACnet Read/Write
Function: Read
Update? Yes
*Cycle unit power to
confirm write command.
a. Working hour set
a. Configuration
c. Factory settings
c. Password/Defaults
b. Probe adjustment
Probe Adjust
pCOe number:
1
Offset Ch 1:
0.0
Offset Ch 2:
0.0
Offset Ch 3:
0.0
Offset Ch 4:
0.0
Digital Compressor
Minimum OFF:
1.0vdc
Minimum ON:
1.9vdc
Maximum: 5.0vdc
Delay OFF:
60s
Max Power Start:
120s
Hot Gas Controller
Integration: 300s
Band: 20°F
Unoccupied Mode Setup
Type: CycleSupplyFan
Source:
Input ID6
TCP/IP SETUP
Instance: 77000
IP set by:
DHCP
IP: 172.016.000.001
Subnet: 255.255.255.000
Gatewy: 192.168.001.001
Analog Input
Cold Coil Temperature
Input B03: ###.#°F
Offset: 0.0°F
Value: ###.#°F
Analog Output Config
Wheel
Channel: Y1
Action: DIRECT
Minimum: #.#vdc
Maximum: ##.#vdc
Cooling Controller
Integration: 300s
Band: 20°F
Reheat Setup
Will heater be used
for reheat during
dehumidification?
Reheat: Disable
Supply Reset Control
Integration: 1200s
Band: 10°F
Wheel Rotation Sensor
Alarm delay:
30s
(input ID3)
TCP/IP SETUP
DNS 1:
###.###.###
DNS 2:
###.###.###
Type: IP
Analog Input
Room Temperature
Input B04: ###.#°F
Offset: 0.0°F
Value: ###.#°F
Compressor Setup
# of stages:
#
Rotation: LIFO
Reheat Setup 2
Will heater be used
for reheat along
with hot gas?
Heater: Disable
Heat/Cool Delay
Time delay between
heating, cooling &/or
economizer modes.
Delay: 180s
Temperature Scale
Select: Fahrenheit
Display Buzzer
Select: Disable
User Default
Insert new service
password (PW1):
0000
Unit BMS Control
Unit Start/Stop:
Yes
Temp Setpoint:
Local
Occupancy:
Input ID6
BMS Configuration
Protocol: None
BACnet Plugin?
Yes
MAINTENANCE HOURS
SYSTEM
Run hours:
0000h
Set Point:
0000h
Reset to Zero?
No
Unit Code
Select DDC configur-
ation code here.
Code: GWXXXXXXX00
Analog Input
Outside Temperature
Channel:B1
Type: NTC
Offset: #.#°F
Value: ##.#°F
Factory Setup
Consult Factory
Before Altering
Compressor Timers
Minimum ON:
###s
Minimum OFF:
###s
Between Stages:
###s
Hot Gas Setup
Hot gas reheat coil
minimum on/off
time: 10minutes
Damper Setup
Allow the dampers to
open for: 10 seconds
before starting the
fans.
Factory Settings
Save? No
Restore? No
User Default settings
Save?
No
Restore?
No
BMS Write Points
TempSetpoint: aaa.a°F
Start/Stop: Stop
Reset Alarms:
No
Occupancy: Occ
MODBUS SETUP
Address: 1
Baudrate 9600
Analog Input
Outside Temperature
Input B01: ###.#°F
Offset: 0.0°F
Value: ###.#°F
Unit Expansion Comm
Field Card Settings
Baudrate:
19200
Stop bit:
2
Parity mode:
NONE
Timeout:
300ms
Digital Input
Supply Fan
Channel: ID1
Action: OPEN
Delay: 0s
Open
Economizer Controller
Integration 300s
Band: 20°F
Econo ON/OFF times:
Minimum ON:
300s
Minimum OFF:
300s
Compressor Staging
Stage1: ON @ 50% OFF 0%
Stage2: ON @ 100% OFF 50%
Fan/Airflow Proving
Alarm delay:
30s
(inputs ID1 & ID5)
Hot Gas Flush Setup
Cycle: 30minutes
Duration: 1minutes
New Password
Insert new manufacturer
password (PW2):
####
MSTP SETUP
Instance: 77000
Baudrate 38400
MAC Addr:
0
MaxMasters: 127
MaxInfoFrames: 10
Analog Input
Discharge Temperature
Input B02: ###.#°F
Offset: 0.0°F
Value: ###.#°F
Unit Expansion I/O
Enable Expansion:
No
Relay Output
Defrost
Channel: 1
Status: OFF
Supply Fan Cycling
Defrost setup
Fan off time:
5min
Fan on time:
30min
Heater Controller
Integration: 300s
Band: 20°F
Mod Hot Gas Setup
Minimum On:
4.0vdc
Maximum On:
10.0vdc
Fan Delay
Time delay between
starting of supply
& exhaust fans.
Fan delay:
15s
Initialization
DEFAULT INSTALLATION
Erase user settings
and install global
default values:
No
b. I/O Configuration
All I/O points are included An example of each is shown.
d. Initialization
11
DDC Controller for Tempered Air Products
®