background image

Relay Wiring

Note:

  Neutrals terminate within the adjoining lighting panel.

The standard relay is a simple contact closure, breaking the

line and load wires of a normal circuit.

To wire the relay into the control unit:
1.  Verify that all wire cuttings are removed from the enclosure.

2.  Test branch circuits for short circuits prior to landing wiring 

on relays.

3.  Connect  a  120  or  277  volt,  20  amp  max,  de-energized 

branch circuit breaker to the relay terminal block.

4.  Connect the load wiring to the output terminal block.  

Note:

 

terminal  blocks  are  not  polarity  sensitive  although  it  is 

recommended that line and load be brought into terminal 

blocks in the same manner for consistency. 

5.  Tighten down relay terminal screws.  Manufacturer’s recom

-

mended torque rating is 7lbs-in. (0.59 lbs-foot) (0.8Nm).

6.  Document relay to circuit information for future reference.     

 

                     

ControlKeeper-2

®

 Relay Wiring

Connecting Low Voltage Inputs

The ControlKeeper-2

®

 logic board can support both dry contact 

closure and Digita

®

 Switch inputs.  If a combination of contact 

input switches and Digita

®

 Switches are being used, the com

-

bined total cannot exceed 64 inputs.
Regardless of input type used, it is recommended that all input 

wiring be done prior to applying power to the logic board or at 

the very least with the terminal blocks removed from the logic 

board.  Please verify that there are no shorts to AC Ground 

prior to connection of input devices.

Regardless of input type, the following notes apply.
1.  All low voltage wiring is Class 2 wiring.

2.  All low voltage wiring must enter the cabinet into the Low 

  Voltage section of the enclosure.  Low Voltage wiring can be 

 

  brought into the enclosure from the left side of the enclosure.   

 

  Failure to separate high voltage from low voltage wiring 

 

  may cause interference with logic board function.

3.  All low voltage wiring must be run in separate conduit from 

 

  line-voltage wiring.

4.  Test all low voltage wiring for shorts to AC ground before 

 

  connection to the relay panel.

5.  When powering peripheral devices such as motion sensors 

 

  and photosensors from the ControlKeeper-2

®

 panel, there may 

 

  be a limitation on the number of sensors that can be sup- 

  ported.  This is also true if Digita

®

 Switches are used with the 

 

  system.  See the recommendations below or contact Cooper 

 

  Controls for further information.

6.  It is recommended that the terminal blocks be removed from 

 

  the board or power removed from the logic board when 

 

  doing initial switch input wiring.

Contact Input Switch Wiring

This  section  describes  the  wiring  for  dry  contact  closure 

devices.  There are two switch input wiring terminals on the 

left side of the ControlKeeper-2

®

 to allow for wiring of the dry 

contact closure devices. 
1.  Use 18 AWG twisted, unshielded wire for all low voltage 

 

  dry contact closure device wiring.

2.  Maximum length for dry contact closure device wiring is 

 

  1000 feet.

3.  Please see wiring detail below for details on connections 

 

  of different devices to the ControlKeeper-2

®

 system.

                ControlKeeper-2

®

 Low Voltage Switch Wiring

Contact Input Photosensor and Greengate Sensor Notes

It is possible to use a contact input photosensor and Greengate 

Motion Sensors in conjunction with the lighting control system.  

The  ControlKeeper-2

®

  is  capable  of  powering  a  number  of 

these devices.  Please refer to the chart below for details on 

how many devices the transformer can support.

40

16

20

20

Greengate

PIR Sensor

Greengate 

Dual-Technology

Sensor

Greengate

Ultrasonic

Sensor

PPS-4

Indoor

Photosensor

4

PPS-5

Outdoor

Photosensor

Page 2

Содержание ControlKeeper 2 CK2-120-NC

Страница 1: ...ring enters the enclosure separately High Voltage wir ing should be brought into the right section of the enclo sure Low Voltage wire should enter in the low voltage wiring compartment on the left side of the enclosure Failure to separate high voltage from low voltage wiring may cause interference with logic board function Wiring the Transformer The ControlKeeper 2 is factory configured with a 120...

Страница 2: ...e enclosure from the left side of the enclosure Failure to separate high voltage from low voltage wiring may cause interference with logic board function 3 All low voltage wiring must be run in separate conduit from line voltage wiring 4 Test all low voltage wiring for shorts to AC ground before connection to the relay panel 5 When powering peripheral devices such as motion sensors andphotosensors...

Страница 3: ... Switch Installation Instructions included with your Digita Switch Gateway for information on wiring the Digita Switch network to the Digita Switch Gateway 1 Mount the Digita Switch Gateway next to the ControlKeep er 2 panel A six foot phone style cable has been provided for connection to the ControlKeeper 2 panel 2 Run a length of the Digita Switch LC or Belden cabling from the Digita Switch Gate...

Страница 4: ...the next panel s network and terminals Continue this process through the network making certain to observe polarity When finished the two end panels will have a single pair of wires coming into the network terminal block while all middle panels in the network will have two sets of wires 4 Set the network termination jumpers On the end panels on the network set to the terminated position For all pa...

Страница 5: ...utton The unit is now cleared to factory default programming LED Operation The ControlKeeper 2 has LEDs mounted on the left side of the panel Refer to the diagram at the beginning of these instructions for the location of these LEDs System LEDs There are three 3 system status LEDs that are located in the upper section of the ControlKeeper 2 These status LEDs will indicate proper operation or poten...

Страница 6: ...tor 5 Network Terminal 6 Network Termination Jumper 7 Panel ID Selection Switch 8 System Status LEDs 9 Relay 1 Override Switch 10 Relay 1 Status LED 11 High Low Voltage Barrier 12 Relay Output 1 13 120V Black or 277V Orange 14 Neutral White 15 Transformer 16 Relay Output 2 17 Relay 2 Override Switch 18 Relay 2 Status LED 19 Reset Switch Page 6 ...

Страница 7: ...tion or misapplication by damage during shipment or by improper service There are no warranties which extend beyond the hereinabove limited warranty INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS No employee agent dealer or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller any other liabil...

Отзывы: