background image

 

Page 

17

 of 

28

 

Version 4.37 • CE • ALIS Tube Lamp

 

21 May 2019

 

 

5.

 

Fault finding 

If the ALIS-Lamps flash ON and OFF, this means you have too much load on the system. Start unclipping the 

ALIS-Tube Couplers one at a time until the flashing stops. 

 

5.1 Led Status Indicator & Reset Button. 

 

To facilitate fault diagnosis, the PH500/200 has a bi-colour (red & green) status indicator. 

When the Power Hub is performing normally the status indicator is solid GREEN. If another indication is observed, 

please see the chart below for an indication. To remove the fault, press the reset button as shown below by the 

red arrow. 

 

 

 

 

LED Status Indicator 

 

Operating Mode 

 

Description 

 

Action 

 

Steady Amber 

Input voltage too low. 

Automatic lockout 

when input supply 

drops below 160 Vac 

The ALIS-Hub resets when supply 

returns to normal. 

Flashing amber, 1 

Flash per second, 50% 

Duty cycle 

Input voltage too high. 

Automatic lockout 

when input supply 

exceeds 270 Vac 

The ALIS-Hub resets when supply 

returns to normal. 

Flashing alternate red 

and green, 2 flashes 

per second 50% duty 

cycle. 

Power required exceeds power 

available. 

Too much load fitted 

to the ALIS-Bus 

Remove excess load. The system 

automatically resumes normal mode of 

operation 

Solid red 

(with system OFF) 

Output voltage too high. 

ALIS-Bus is 

open circuit. 

Repair fault in the ALIS-Bus. Reset the 

system by pressing the reset button. 

Solid red 

(with system OFF) 

ALIS-Hub only. Ground fault 

protection. 

ALIS-Hub has detected 

a power imbalance in 

the output current 

(residual current) 

>80mA rms 

Disconnect from AC supply until LED is 

extinguished. Examine the ALIS-Bus for 

possible earth leakage. Reset button will 

not allow re-start. 

Flashes red, 1 flash 

per second, 50% 

duty cycle 

Temperature too high. 

ALIS-Hub case 

temperature exceeds 

90˚C (+/

-

5˚C), 

shutting itself down. 

The ALIS-Hub resets when temperature 

returns to normal. This may take 

several minutes. 

 

 

The reset button on the power hub can only be pressed 3 times. Thereafter the power 

hub must be reset by disconnecting it from the AC mains supply, waiting until the status 

indicator has extinguished and then reconnecting it. 

 

 

Содержание ALIS CE

Страница 1: ...4 37...

Страница 2: ...Lift the upper coupler back on its hinge and check the position of the seal Due to the compression the seal may have stuck to the upper coupler If this has occurred then peel the seal off and positio...

Страница 3: ...installers should contact Greengage Lighting Ltd technical support with any queries they may have at support greengage global Please follow these instructions carefully as deviation from them may inva...

Страница 4: ...0 General guidance 11 3 1 ALIS bus termination 12 3 2 End termination 13 3 3 End termination rules 14 3 4 Hub supply cable termination CE 15 3 5 Hub supply cable termination UL 15 3 6 System connecti...

Страница 5: ...ay be required depending on the exact suspension mounting method used and the composition of the surface mounting material Tape Measure Screwdrivers including terminal driver Cable cutters crimpers an...

Страница 6: ...serves as guidance for an ALIS installation within an intensive livestock rearing building Installers must also follow all applicable local electrical installation standards and wiring regulations whe...

Страница 7: ...90 C min and 300V minimum 4 ALIS Tube Lamps 0 6m 0 9m 1 2m ALS0013 ALS0012 ALS0011 Suitable for wet location use Do not submerse IP66 5 ALIS Tube Coupler ALS00015 ALS00015 Suitable for wet location us...

Страница 8: ...et local regulations 11 ALIS Bus End termination module and enclosure ETM ETM Must be housed within a suitably sealed enclosure IP66 see section 3 2 12 P2M Supply Connector P2M N A Not applicable CE O...

Страница 9: ...tting at an early stage with either the house builder or architect to ensure that correct placement of the ALIS lamps within the house is possible If not a redesign of the lighting plan may be require...

Страница 10: ...in a dry and dust free location acceptable to local wiring regulations If this is not possible then they must be housed within a suitably sealed enclosure as per local wiring regulations Due to the he...

Страница 11: ...ch as a system partition ensure the ALIS Tube Coupler is moved to at least 15cm from this point to allow movement during washout Once positioned within the Coupler Housing bring the two lid sections t...

Страница 12: ...g care not to damage the inner insulation Strip the ends of the ALIS Bus inner insulation to 8mm 0 3 inch of exposed conductor ensuring there is not any conductor loss Slide the orange connector cover...

Страница 13: ...to damage the cable conductors Strip the ends of the ALIS Bus to 5mm 0 2 inch of exposed conductor ensuring there is not any conductor loss as shown below Twist the exposed copper cable strands Inser...

Страница 14: ...tions should be observed If the length of the ALIS bus is less than 100m then the ALIS Bus must be terminated by means of a shorting connection to keep the ALIS Bus in resonance with the Hub When the...

Страница 15: ...connection a Connect the ALIS Bus to the ALIS Dimmer as shown in the ALIS system components diagram page 5 b Connect the ALIS Dimmer to the ALIS Power Hub as shown in the ALIS system components diagr...

Страница 16: ...IS Tube End Connector 4 Check the ALIS ETM termination Ensure the ALIS Bus cable is properly terminated 5 Ensure the ALIS Dimmer is properly connected to the ALIS Bus 6 Ensure the ALIS Dimmer is prope...

Страница 17: ...s when supply returns to normal Flashing alternate red and green 2 flashes per second 50 duty cycle Power required exceeds power available Too much load fitted to the ALIS Bus Remove excess load The s...

Страница 18: ...ge level is ascertained attempt a power up reset If this does not resolve the fault replace the power hub firstly carrying out the check list on page 8 5 ALIS Tube s flashing or flickering If this is...

Страница 19: ...ise please ensure that all ends are sealed and lids correctly fitted to stop fauna rodent ingress 8 Installations should never use no more than the required length of ALIS Bus for each ALIS Power Hub...

Страница 20: ...CE Max Power 500W Load Regulation 0 500W Output 0 95 1 45 1 95 O P Frequency ALIS Bus 49 kHz 50 kHz 51 kHz O P Current ALIS Bus 1 805A 1 9A 1 995A Start Time Turn On Time 460mS 480mS 500mS 475W outpu...

Страница 21: ...shock are not safe to touch Circuit connected to any FELV control terminal shall be insulated for the LV voltage of the control gear and any terminals connected to the FELV circuit shall be protected...

Страница 22: ...requirements 2009 EN 61000 3 2 Electromagnetic compatibility EMC Limits Limits for harmonic current emissions equipment input current 16 A per phase 2014 EN 61000 3 3 Electromagnetic compatibility EMC...

Страница 23: ...rposes EMC immunity requirements 2009 EN 62493 Assessment of lighting equipment related to human exposure to electromagnetic fields 2015 EN 60598 1 Luminaires Part 1 General requirements and tests 201...

Страница 24: ...Limited Roslin Innovation Centre The University of Edinburgh Easter Bush Campus Midlothian EH25 9RG United Kingdom Date of Installation Site Information Client Telephone inc country code Address Mobi...

Страница 25: ...er Hub Serial Number ALIS Dimmer Serial Number Length of Cable Number of ALIS Tube Couplers Length of ALIS Tube per Coupler Dimming Facility ALIS Pot 0 10VDc Pictures Please send pictures of the follo...

Страница 26: ...Page 26 of 28 Version 4 37 CE ALIS Tube Lamp 21 May 2019 Appendix Connection diagram...

Страница 27: ...ST 18i3 96052 Bamberg 49 951 9324 0 ENG 49 951 9324 198 Mounting Instruction Screw Connection Internet www wieland gesis GST 18i3 July 2004 Low Profile electric com 2004 Wieland Electric GmbH Email in...

Страница 28: ...Page 28 of 28 Version 4 37 CE ALIS Tube Lamp 21 May 2019...

Отзывы: