Greenfire Pellet Stove and Insert Technical Manual
9
GF55 FREESTANDING PELLET STOVE
These dimensions are minimum clearances to combustibles, however it
is highly recommended that you leave sufficient room on each side (20"
where possible) for servicing, routine cleaning and maintenance.
This pellet stove requires floor protection. The floor protection must be
non-combustible, extending 6" (150mm) beyond the full width and depth
of the unit including 6" (150 mm) in front for ember protection.
Floor Protection:
Width 36-7/16” (934mm)
Depth 36” (914mm)
Figure 3: Floor Protection
Back wall
S
id
e
w
al
l
Adjacent
wall
2"
(51mm)*
3" (76mm)
6"
(152mm)
Figure 4: Minimum Clearances to Combustibles
ALCOVE CLEARANCES
Minimum Width
36" (914mm)
Minimum Height
48" (1219mm)
Maximum Depth
30" (762mm)
Figure 5: Alcove Clearances
CLEARANCES TO COMBUSTIBLES
MOBILE HOME INSTALLATION
● Secure the heater to the floor using the holes in the pedestal of the
appliance.
● Ensure the unit is electrically grounded to the chassis of your home
(permanently).
WARNING: Do not install in a room people sleep in.
CAUTION: The structural integrity of the manufactured home
floor, wall and ceiling/roof must be maintained
• Outside fresh air is mandatory. Secure outside air connections directly
to fresh air intake pipe and secure with three (3) screws evenly spaced.
Figure 6: Mobile Home Install Mounting
INSTALLATION
*NOTE:
If the unit is installed as a corner installation,
clearances change from 2" to 3", see "Corner thru Wall
Installation" section.