Greenfire Pellet Stove and Insert Technical Manual

13

VERTICAL RISE WITH HORIZONTAL

TERMINATION INSTALLATION

Figure 13: Through Wall with Horizontal 

Termination 

A 45° elbow may be used in place of the termination cap (or stainless 

steel termination hood).

THROUGH CONCRETE WALL

WITH VERTICAL RISE INSTALLATION

A 45° elbow may be used in place of the termination cap (or stainless 

steel termination hood).

This is the recommended installation to use if there is a concrete or retain-

ing wall in line with exhaust vent on pellet stove. 

The termination must be 12 inches (30cm) from the outside wall and 12 

inches (30cm) above the ground. 

Figure 14: Vertical rise with Horizontal Termination

INSIDE VERTICAL INSTALLATIONS

1.

  Choose a stove location that is ideal.  Refer to "Locating Your Pellet 

Appliance" section.

 

2.

  Place the unit on the hearth pad (if installed on a carpeted surface) 

and space the unit in a manner so when the pellet vent is installed 

vertically, it will be 3” (76 mm) away from a combustible wall.

3.

  Locate the center of the fresh air intake pipe on the unit. Match that 

center with the same point on the wall and cut a hole about 2” (51 

mm) in diameter.

4.

  Install the fresh air intake pipe.

5.

  Install the tee with clean out.

6.

 

I

nstall the pellet vent upward from there.  When you reach the ceiling, 

make sure that the vent goes through the ceiling fire stop.  Maintain 

a 3” (76 mm) distance to combustibles and keep attic insulation away 

from the vent pipe. Maintain an effective vapor barrier.

7.

  Finally, extend the pellet vent to go through the roof flashing.

8.

  Ensure that the rain cap is at least 24” (610 mm) above the roof at 

the shortest side of the vent.

 

Rain cap - ensure cap is at 

least 2 feet (610mm) above 

the roof at the lowest point

Storm collar

Roof flashing

Roof rafter

Fire stop with 

Support Collar

Ceiling joist

Vertical vent pipe

Clean out tee with 

Pipe adapter

NOTE:

All vent sections must maintain 3" 

(76 mm) clearances to combustibles.

Figure 15: Inside Vertical Installation

INSTALLATION

Содержание Greenfire GF55

Страница 1: ...r additional information consult an authorized installer or service agency FOR YOUR SAFETY Donotstoreorusegasolineorotherflammable vapours and liquids in the vicinity of this or any other appliance In...

Страница 2: ...Efficiency 74 5 LHV 70 HHV FIRE EXTINGUISHER AND SMOKE DETECTION All home with a pellet burning stove should have at least one fire extinguisher in a central location known to all the household Smoke...

Страница 3: ...ough Concrete Wall with Vertical Rise 13 Inside Vertical Installations 13 Outside Vertical Installations 14 Hearth Mount Installations 14 GFI55 Pellet Insert 15 Clearances to Combustibles 15 Fireplace...

Страница 4: ...e ALIMENTATION LECTRIQUE 120 Volts 60 Hz 4 3 A Maintenir le c ble lectrique l cart de l appareil de chauffage For Use With Only Pelletized Wood fuels Keep viewing and ash removal doors tightly closed...

Страница 5: ...ING PELLET STOVE 341 8 866mm 231 16 586mm 19 16 40mm 197 16 494mm 131 16 332mm 247 16 620mm 24 610mm 1 25mm 191 8 866mm 24 610mm 129 16 319mm 15 8 41mm 145 8 371mm 231 16 586mm 3 76mm 205 16 516mm 511...

Страница 6: ...16 582mm 203 8 517mm 241 16 610mm 11 16 26mm 13 329mm 10 253mm 225 16 567mm 13 8 35mm 303 16 766mm 71 4 183mm 2215 16 582mm 203 8 517mm 241 16 610mm 11 16 26mm 13 329mm 10 253mm FACEPLATE DIMENSIONS R...

Страница 7: ...ent of the fuel used and the operation of the stove It is advisable to inspect and clean the exhaust vent semi annually or every two tons of pellets ELECTRICAL The use of a surge protected power bar i...

Страница 8: ...nd roof REMOVING PELLET STOVE FROM PALLET To remove your new stove from its pallet remove the two 2 screws securing the bottom to the pallet Freestanding One screw can be easily seen from behind but t...

Страница 9: ...m Clearances to Combustibles ALCOVE CLEARANCES Minimum Width 36 914mm Minimum Height 48 1219mm Maximum Depth 30 762mm Figure 5 Alcove Clearances CLEARANCES TO COMBUSTIBLES MOBILE HOME INSTALLATION Sec...

Страница 10: ...ixture is out of balance a slight discoloration of the exterior of the house might occur Since these factors are beyond the control of FPI we grant no guarantee against such incidents NOTE Venting ter...

Страница 11: ...n airtight homes and mobile homes A Fresh air intake is strongly recommended for all installations Failure to install intake air may result in improper combustion as well as the unit smoking during po...

Страница 12: ...um of 3 8 cm clear ance from the back of the stove to the wall Seal the vent pipe to the thimble with high temperature silicone 10 The pipe must extend at least 12 30 cm away from the building If nece...

Страница 13: ...manner so when the pellet vent is installed vertically it will be 3 76 mm away from a combustible wall 3 Locate the center of the fresh air intake pipe on the unit Match that center with the same poi...

Страница 14: ...Rain cap Flashing 24 61 cm 3 7 5cm Tee with cleanout Fresh air intake 3 7 5 cm Clearance Support bracket Type L PL or all fuel vent Figure 16 Outside Vertical Installation HEARTH MOUNT INSTALLATION 1...

Страница 15: ...so that the clip will be facing up Thread hex nut onto the bolt till it is approximately 1 25 mm from the bolt head slide washer onto bolt Thread the bolt into the square nut so length of the bolt sh...

Страница 16: ...s unit ensure that the pedestal is removed from the inside of the hopper and installed on the bottom of the unit Refer to Installation of Pedestal and Leveling Legs Adjust hopper height refer to Insta...

Страница 17: ...rom the chimney from coming back into the fireplace and prevent air from the fireplace from entering the chimney which will affect proper drafting of appliance A qualified installer should evaluate th...

Страница 18: ...d on top of the unit while the control panel is removed or disconnected If electrical connection is required for the maintenance remove the circuit board control panel from the surround If electrical...

Страница 19: ...lass retainer Ensure the four screws are also hand tight and close door Do not overtighten or you may break screws Cleanallplatedsurfacesbeforestartingthestove Referto Cleaning PlatedSurfacesinRoutine...

Страница 20: ...is requires more primary air the slider damper must be pulled out to compensate Pulling the slider damper out gives the fire more air Slider Damper Exhaust Channel Exhaust Blower Note Some parts have...

Страница 21: ...ing completely unburned fuel in the burn pot liner Insufficient air will cause build up further restricting the air flow through the Burn Pot Liner This in turn will cause the fuel to burn cold and ve...

Страница 22: ...sensor and determine cause was it Convection Blower failure or 160 F 71 C Temperature Sensor failure Bypass the 160 F 71 C sensor does the Convection blower come on high If not replace the blower If y...

Страница 23: ...Black White Grey Grey Vacuum Switch Black White Thermostat 120 V Grounded Connector Ground Green White Red Ignitor Auger Motor White Yellow 5 Amp Fuse Convection Blower Connect Thermostat Here High Li...

Страница 24: ...Roll Nut GF55 GFI55 2 Set 11 GF55 028 Glass Side GF55 GFI55 12 GF55 029 Glass Front GF55 GFI55 GF55 033 Exhaust Starter Tube 3x2 5 GF55 GFI55 GF55 036 Cleaning Rod Heat Tube GF55 GFI55 13 GF55 037 Bu...

Страница 25: ...Greenfire Pellet Stove and Insert Technical Manual 25 7 6 2 9 1 14 8 3 5 PELLET STOVE COMPONENTS PARTS LIST...

Страница 26: ...Greenfire Pellet Stove and Insert Technical Manual 26 17 25 26 28 19 16 20 21 4 10 13 18 27 29 34 15 12 11 GF55 FREESTANDING PELLET STOVE PARTS LIST...

Страница 27: ...Greenfire Pellet Stove and Insert Technical Manual 27 24 32 33 31 22 23 30 GFI55 PELLET INSERT PARTS LIST...

Страница 28: ...t in manufacture or FPI factory assembled components only unless herein specified otherwise Any part s found to be defective during the warranty period as outlined above will be repaired or replaced a...

Страница 29: ...cardboard coal or coal products oil based products waxed cartons compressed pre manufactured logs lack of regular maintenance and upkeep acts of God weather related problems from hurricanes tornados...

Страница 30: ...ide the U S should consult their local provincial or national legal codes for additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the auth...

Страница 31: ...in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product De...

Страница 32: ......

Страница 33: ...___________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ _____...

Страница 34: ...___________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ _____...

Страница 35: ......

Страница 36: ...e following information Dealer Name Address ________________________________________ ___________________________________________________________ Installer _____________________________________________...

Отзывы: