6.3 Ventilation Fan Verification of Proper Operation
a) Verify all wires are correctly connected and wire nuts are tight and secure.
b)
Install protective grill before turning on power to the ventilation fan.
c) Plug in ventilation fan, turn on fan, and verify green LED lamp is illuminated on
greenfan® bipolar ionizer indicating ions are being generated.
d) Turn off power and verify LED lamp is not illuminated.
7.0 OPERATING NOTES
Follow all local, state, and national electrical and building codes.
a) The greenfan® bipolar ionizer is designed to operate at temperatures at or below
140F or 60C.
b) The greenfan® bipolar ionizer is designed for 24VAC operation only.
c) When power is supplied, the greenfan® bipolar ionizer will be energized and the
LED will be illuminated.
d) The greenfan® bipolar ionizer is self-balancing and does not require any adjustment.
e) The greenfan® bipolar ionizer must be installed inside the HVAC equipment, air
purifier, or fan. L'ioniseur bipolaire greenfan® doit être installé à l'intérieur de
l'équipement CVC, du purificateur d'air ou du ventilateur.
f) This air cleaner shall not be installed on the hot-air side of duct-type systems. Ce
filtre à air ne doit pas être installé du côté air chaud des systèmes de type conduit.
8.0 TROUBLESHOOTING
a) If LED lamp is continuously illuminated when thermostat fan switch, air purifier, or
fan is turned to the ON position, then bipolar ionizer is operating properly. The
greenfan® bipolar ionizer continuously monitors high-voltage signals on the positive-
ion electrode and the negative-ion electrode to maintain consistent high-voltage and
balanced bipolar ion concentrations over a range of voltage inputs from 20 to
30VAC. For HVAC systems without easily accessible 24VAC wires nearby install a
120/208/240V to 24VAC UL-listed transformer shown in
Figure 8
and
Figure 9
.
b) If LED lamp does not illuminate when thermostat fan switch, air purifier, or fan is
turned to the ON position, then check: 1) power supply or transformer is plugged in
and operating properly; 2) bipolar ionizer is properly connected to power supply or
transformer (check all wire nut connections); 3) verify all wire and wire nut
connections are correct and tight; and 4) reconnect any loose wires as necessary
and verify operation as described above.
c) If LED lamp is flashing when thermostat fan switch, air purifier, or fan is turned to the
ON position, then check: 1) power supply voltage input is within 20 to 30VAC; and 2)
electrical shorts on the positive-ion electrode or the negative-ion electrode.
d) If above steps do not correct flashing or non-illuminated LED lamps, then please
contact technical support.
e) Technical support:
GreenFan® Inc., 6125 Bearclaw Ln, Bozeman, MT 59715.
9.0 MAINTENANCE
The following maintenance procedure is recommended.