greenfan® bipolar ionizer Model 1600-01
© 2022 greenfan® inc.
9
installation. Do not connect electrical power until installation is completed.
b) For ventilation fan, install greenfan® bipolar ionizer behind protective grill of fan on a
22-gauge sheet metal support (supplied by installer) attached to a vertical bracket
holding fan motor with two self-tapping screws (1/4" drive x ¾" long) attached
through holes in flanges on either side of unit with at least one inch clearance
between carbon fiber electrodes and metal surfaces to ensure airflow over both
electrodes as shown in
Figure 12
. Make sure any wires secured with zip ties and
located more than one inch away from greenfan® bipolar ionizer carbon fiber
electrode brushes. Make sure screws do not interfere with wires or fan blade
movement. Manually rotate fan blade after installation to verify screws do not
interfere with fan rotation.
c) After completing all steps of mechanical installation proceed to electrical installation.
Figure 12. Bipolar ionizer installed at inlet of ventilation fan behind protective grill
6.2 Ventilation Fan Electrical Operation
a) Ventilation fan electrical installation requires UL-listed 120/24VAC transformer
(Model 1602-01). Use multimeter to locate 120VAC wire to fan motor and use in-line
splices to connect 120/24VAC transformer wire to 120VAC fan motor wire and
120/24VAC transformer common to 120VAC neutral wire shown in
Figure 11
.
b) Connect greenfan® bipolar ionizer blue wire to one wire of 24VAC transformer and
connect greenfan® bipolar ionizer black wire to other wire of 24VAC transformer.
c) Install wire nut to insulate unused white wire of greenfan® bipolar ionizer.
d) The greenfan® bipolar ionizer will draw less than 130mA and 1.6W or greater at
24VAC and 50/60 Hz when energized when ventilation fan is turned on.
e) After completing all steps of mechanical and electrical installation proceed to
ventilation fan verification of proper operation.