10 - OPERATING INSTRUCTIONS
10.3.5 Parameter Setting Menu
To set PCB parameters proceed as follows:
1.
Press
and
together for about 6 seconds, the
display shows "PO1" alternating with its value (01);
2.
The parameter setting menu is divided in pages, each with
10 parameters (ie Px0-Px9).
3.
: short push to go to the next page (e.g. from
P10-P19 page to P20-P19 page). See Note.
4.
: short push to go to the previous page (e.g. from
P20-P19 page to P10-P19 page). See Note.
5.
Address/Page Knob:
turning Left Knob permits scrolling
between the parameter within the current selected page.
See Note.
6.
If
Data Knob
(Right Knob) is moved, "NOP" is seen on
the display to inform the user that moving the Data Knob
has no consequences
NOP= N
o
OP
eration.
7.
short push: parameter visualized in display is selected
and the board goes in the Value setting menu.
8.
: short push to go to next page (e.g. from values 10-
19 page to 20-29 page)
9.
: short push to go to previous page (e.g. from values
20-29 page to 10-19 page)
10.
Data Knob: turning Right Knob permits scrolling the
values in the current selected page.
11.
: short push to save the value visualized on the
display and return to parameter setting menu.
12.
Address/Page Knob: returns to Parameter setting menu
without saving the current value (escape function).
This function always ends after 3 minutes, or sooner by
pressing
and
simultaneously with a long push.
Note
Knob design does not change scrolling
position when moving back and forth
between pages. If display was on
P07, a short push of
will result in
P17 display. Rotate knob to reach P11
through P16.
P70
Ignition fan speed setting: Fan Speed =
P70
* 100 rpm
P71
Maximum fan speed: Fan speed = 3500 +
P71
* 25 rpm
P72
Minimum fan speed: Fan speed = 750 +
P72
* 10rpm
Example
To set ignition speed at 3000 rpm
P70
= 30
To set max fan speed at 5800 rpm
P71
= 92
To set min fan speed at 1100 rpm
P72
= 35
Note:
Parameters in Grey are not visible unless
P22
is set at 22.
10.3.6 Description Of Parameters
Parameter
Parameter Description
GMHB
227
NG
GMHB
227
LPG
GMHB
380
NG
GMHB
380
LPG
P01
DHW Modulation
0
0
0
0
P02
gas type selection
0
1
0
1
P03
Boiler setting
00= instantaneous combi boiler
02= instantaneous combi boiler with DHW micro tank
03= instantaneous combi boiler with pre heat
04= only heating boiler with DHW thermostat (system boiler 1)
05= only heating boiler for external DHW tank
06= boiler with DHW storage tank
07 = Heating only
08 = only heating boiler
09 = storage tank 3 (simple solar)
10 = instantaneous boiler for solar application
11 = instantaneous boiler for solar application with DHW micro-tank
13 = instantaneous boiler with pre-heat for solar application
15= only heating boiler with DHW pump for external tank
16= boiler with DHW storage tank and DHW pump with plate to plate
DHW heat exchanger
17 = System boiler 2 (04 without pump)
18 = only heating boiler with DHW pump for external tank
19= System boiler 3
8
8
8
8
P04
Manufacturer information. Shall be set to 02. Ignore all other options.
2
2
2
2
P05
Manufacturer information. Shall be set to 04. Ignore all other options.
4
4
4
4
P06
Outdoor reset input configuration
00= with an outdoor sensor connected, the outdoor temperature
value helps to calculate the supply temperature setpoint
01= with an outdoor sensor connected, the display shows the outdoor
temperature value (no influence on supply temperature)
02= no function is associated
03= heating request input (e.g. telephonic trigger)
04 = Low temperature safety thermostat
05 = DHW pump activation
0
0
0
0
P07
Aux input configuration
00..02 = No function is associated
03 = This is an input contact for CH request (e.g. trigger phone).
When contact CN2 is closed and Room Thermostat (RT) requiring
heat switches burner on.
Note: verify heating mode is enabled (winter or heat only mode)
04 = This is an input contact for Low Temperature Thermostat (e.g.
floor heating system).
When Low Temperature Thermostat connected on CN2 cuts out,
burner
switches off and display shows E178 anomaly.
Note: verify heating mode is enabled (winter or heat only mode)
05 = This is an input contact for external DHW recirculation pump.
When contact CN2 is closed the pump runs for a specific period.
To enable input it is necessary to set parameter P04 or P05 = 08 and
P69 = 05.
Pump will run at P19 minutes (Summer/Winter mode or Only Winter
mode) or P19/2 minutes (only Summer mode).
0
0
0
0
P08
Manufacturer information. Set to 0. Ignore other options.
0
0
0
0
P09
Manufacturer information. Set to 1. Ignore other options.
0
0
0
0
P10
Manufacturer information. Set to 0. Ignore other options.
0
0
0
0
P11
Manufacturer information. Shall be set to 02. Ignore all other options.
2
2
2
2
P12
Manufacturer information. Shall be set to 0. Ignore all other options.
0
0
0
0
P13
Max CH power setting
100
100
100
100
PN 240012369, REV A [08/31/2018]