background image

19

6 - COMBUSTION AIR AND VENT PIPING

WARNING

Fire, explosion, and asphyxiation hazard.  Improper 

installation could result in death or serious injury.  Read 

these instructions and understand all requirements 

before beginning installation.

!

  

WARNING

ABS/PVC venting shall not to be used this product. 
Use of DWV plumbing pipes to vent this boiler shall be 

prohibited.
Use of cellular core PVC (ASTM F891), cellular core 

CPVC, or Radel® (polyphenolsulfone) in venting 

systems shall be prohibited.
Covering non-metallic vent pipe and fittings with 

thermal insulation shall be prohibited.
Failure to follow these instructions could result in death 

or serious injury.

!

  

Note

Follow venting manufacturer's equivalent lengths 

for specialty fittings. 

6.1 General

•  Installations shall comply with Authority having jurisdiction 

and in absence of such with: 

 

»

U.S. ANSI Z223.1 /NFPA 54 in the United States

 

»

CSA B149.1 in Canada.

•  This boiler requires a dedicated direct vent system. (For 

380 Only, optional category IV indoor air.)

•  Vent connections serving appliances vented by natural draft 

shall not be connected into any portion of mechanical draft 

systems operating under positive pressure.

•  Use only manufacturer approved venting materials or 

venting materials primer and glue approved to: ULC S636 

in Canada, or UL 1738 in the U.S. 

•  Materials used in the U.S. shall comply with Authority 

having jurisdiction and in absence of such with: ANSI/ASTM 

D1785, ANSI/ASTM F441, ANSI/ASTM F493. 

•  Vent system must have unrestricted movement through 

walls, ceilings and roof penetrations.

•  Check for proper joint construction when joining pipe to 

fittings.

•  If vent is penetrating ceilings and floors, openings must 

have means of fire stopping in joist areas and proper 

firestop spacer assemblies installed.

•  Standard roof flashing methods must be used to install roof 

flashing.

•  Frame wall and roof openings to provide support for 

attachment of termination assemblies.

•  Support piping in accordance with pipe manufacturer's 

instruction and authority having jurisdiction. In absence 

of manufacturer's instruction use pipe hooks, pipe straps, 

brackets, or hangers of adequate and strength located 

at intervals of 3 ft (1.m) or less. Allow for expansion/ 

contraction of pipe.

•  Support horizontal sections of vent pipe to prevent sags 

capable of accumulating condensate.

•  Assemble vent materials in accordance with venting 

manufacturer’s instructions.

•  Slope exhaust pipe minimum of 1/4” per foot, or vent 

manufacturer’s recommendation, whichever is greater; 

back toward the boiler.

•  Any "in line" elbows in flue system must be taken into 

consideration.  First elbow on the top of the boiler is 

included in equivalent length calculations.

•  Use U.V. Stabilized polypropylene when it will be exposed 

to sunlight, wind, or prone to freeze ups.

6.2 Removal of Existing Boiler From Common Vent 

System

When existing boiler is removed from common venting 

system, common venting system is likely to be too large for 

proper venting of appliances remaining connected to it. 
After removal of existing boiler, following steps shall be  

followed with each appliance remaining connected to common 

venting system placed in operation, while other appliances 

remaining connected to common venting system are not in 

operation:

•  Seal any unused openings in common venting system.

•  Visually inspect venting system for proper size and      

horizontal pitch. Determine there is no blockage or 

restrictions, leakage, corrosion and other deficiencies which 

could cause an unsafe condition.

•  When practical, close all building doors, windows, and 

all doors between space in which appliances remaining 

connected to common venting system are located and 

other spaces of building. Turn on clothes dryer and any 

appliance not connected to common venting system. 

Turn on exhaust fans, such as range hoods and bathroom 

exhaust so they will operate at maximum speed. Do not 

operate summer exhaust fan. Close fireplace dampers.

•  Turn on appliance being inspected. Follow lighting         

instructions. Adjust thermostat so appliances will operate 

continuously.

•  Test for spillage at draft hood relief opening after 5    

minutes of main burner operation.  Use flame of match or 

candle, smoke from cigarette, cigar or pipe.

•  Determine each appliance remaining connected to  common 

venting system properly vents when tested as outlined 

above. Then return doors, windows, exhaust fans and any 

other gas-burning appliance to their previous condition of 

use.

•  Any improper operation of common venting system 

should be corrected so installation conforms with National 

Fuel Code, ANSI Z223.1/NFPA 54 and/or Natural Gas 

and Propane Installation Code, CAN/CSA B149.1. When 

re-sizing any portion of common venting system, common 

venting system should be re-sized to approach  minimum 

size as determined using appropriate tables in Chapter 13 

of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/

or Natural Gas and Propane Installation Code, CAN/CSA 

B149.1.

•  Venting shall be supported adjacent to each joint using 

steel strapping or equivalent. See Figure 6-1.

 PN 240012369,  REV A  [08/31/2018] 

Содержание GMHB227

Страница 1: ...ed Gas Fired INSTALLATION OPERATION MAINTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 253 7900 www ecrinternational com PN 240012369 REV A 08 31 2018 Mo...

Страница 2: ...perature Gauge Includes essential documents Used for measuring outside temperature Used for connecting condensate piping to boiler Gas Shutoff Valve Document Package Outdoor Sensor Optional Condensate...

Страница 3: ...6 9 4 Commission Setup Electric 47 9 5 Control Panel 47 9 6 Commissioning Setup Overview 48 9 7 De aerationFunction 48 9 8 Commissioning 48 9 9 Before Gas Conversion 50 9 10 Gas Conversion Propane 50...

Страница 4: ...r 50 00 psig 3 44 bar Recommended System Pressure cold 21 7 psig 1 5 bar 21 7 psig 1 5 bar SYSTEM Pressure relief valve connection 3 4 NPT Onboard pressure switch display limit PN 240012369 REV A 08 3...

Страница 5: ...Front View All Models Top View All Models GMHB227 0NLY Bottom View Dimensions 101 2 4 GMHB380 0NLY Bottom View Dimensions 33 4 73 4 83 4 PN 240012369 REV A 08 31 2018 PHYSICAL DATA D E G F B A D E G C...

Страница 6: ...BEFORE OPERATING Hot Water Can Scald Water heated to temperature for clothes washing dish washing and other sanitizing needs can scald and cause permanent injury Children elderly and infirm or physic...

Страница 7: ...eatures Modulating GMHB227 20 100 Input Rate GMHB380 16 100 Input Rate Integral Dual Limit Integral Low Water Pressure Cutoff Outdoor Temperature Reset Optional Heat exchanger over heat protection Rec...

Страница 8: ...10 Ignition Electrode 11 Flue Sensor 12 Coaxial Connector 13 Heat Exchanger Temperature Sensor 14 Heat Exchanger 15 Burner not shown 16 Flame Detection Electrode 17 Air Gas Blend Manifold 18 Air Purg...

Страница 9: ...13 Flue Sensor 14 De Aerator 15 Heat Exchanger 16 Heat Exchanger Temperature Sensor 17 Water Safety Thermostat 18 NTC Heating sensor Supply Return QTY 2 1 Shown for clarity 19 Spark Generator 20 Ventu...

Страница 10: ...any room or internal space special attention shall be given to the requirements of the current electrical provisions with respect to the installation of the boiler in a room or internal space contain...

Страница 11: ...rvice Clearances Boiler Front FIGURE 4 1b Clearance to Combustible Materials FIGURE 4 2b Service Clearances Boiler Left side Boiler Front View FIGURE 4 2c Service Clearances Closet Installation CLOSET...

Страница 12: ...the position of the center of the hole for the flue Cut 5 5 16 135 00 mm diameter hole in the wall for concentric flue Lift boiler and hang it on wall Adjust position of the boiler verify it is level...

Страница 13: ...piping in parallel with boiler with appropriate valves to prevent chilled medium from entering boiler System piping connected to heating coils located in air handling unit exposed to refrigerated air...

Страница 14: ...threaded 5 4 Low Water Cutoff These guidelines are supplied when necessary to install an additional Low Water Cut Off LWCO for sensing a low water level condition in a boiler as required by the Autho...

Страница 15: ...apped in the water pump impeller and reduce water flow rate Non flushed systems have low energy efficiency and potential boiling noise due to ineffective heat transfer and reduced water flow rate Flus...

Страница 16: ...tions are meant to show system piping concept only Installer responsible for all equipment and detailing required by authority having jurisdiction Piping Legend Boiler PN 240012369 REV A 08 31 2018 5...

Страница 17: ...N 240012369 REV A 08 31 2018 5 HYDRONIC PIPING 1 12 305mm Maximum Separation Note Note Manufacturer requires all domestic hot water DHW installations use an anti scald valve Local codes may require ad...

Страница 18: ...l equipment expansion tank relief valves etc Select and size equipment to suit installation and meet code requirements Note Use external pump relay or Zone Control to interface system pump to boiler N...

Страница 19: ...of 1 4 per foot or vent manufacturer s recommendation whichever is greater back toward the boiler Any in line elbows in flue system must be taken into consideration First elbow on the top of the boile...

Страница 20: ...ystem For other venting system suppliers see their instructions 1 Place clamp so etched UP is facing up 2 Open clamp slightly by separating circular areas from each other 3 Slide male end of first pip...

Страница 21: ...uirements of authority having jurisdiction or in absence of such requirements USA National Fuel Gas Code ANSI Z223 1 NFPA 54 WARNING Manufacturer recommends this condensing boiler be vented with appro...

Страница 22: ...d Anticipated Snow Line Maintain 12 305mm US 18 457mm Canada clearance above highest anticipated snow level 24 610mm above roof or ground Anticipated Snow Line 18 Vertical Clearance to ventilated soff...

Страница 23: ...ents between connected indoor spaces vi All Outdoor Air Provide permanent opening s communicating directly or by ducts with outdoors 01 Two Permanent Opening Method Provide opening commencing within 1...

Страница 24: ...ake To transition from Coaxial at the top of the boiler to Twin Pipe CPVC PVC a kit is available B Twin Pipe Polypropylene System Single wall polypropylene is used for both exhaust and air intake pipi...

Страница 25: ...ructions for applying the securing mechanism on twin pipe polypropylene venting Example for Natalini venting system For other venting system suppliers see their instructions 1 Place clamp so etched UP...

Страница 26: ...e Air Single Pipe 380 Figure 6 16 Table 5A Combustion Air Venting Locations Type Location Terminal Type Corresponding Figures Venting Flue Gas Side Wall S Terminal with 90 elbow Figure 6 10 6 11 T Ter...

Страница 27: ...doned unused masonry chimney may be used as chaseway for combustion air and vent Both combustion air and vent pipe must exit above top of chimney with clearances as shown in figure 6 9 FIGURE 6 9 Two...

Страница 28: ...2 does not have a max separation requirement between flue gas and fresh air Fig 6 13 Flue on Roof Air Intake on Side Wall Maintain 12 305mm US 18 457mm Canada clearance above highest anticipated snow...

Страница 29: ...air and Vent Piping Length Page 23 PN 240012369 REV A 08 31 2018 Vent Combustion Air Outer Ring Ground Level Snow line Maintain 12 305mm US 18 457mm Canada clearance above highest anticipated snow lin...

Страница 30: ...be min 12 305mm from or below doors windows or gravity inlet If boiler uses inside air min 4 1219 mm 12 305mm Min Termination Forced Air Inlet 3 0 9m If located within 10 3m of forced air inlet Termin...

Страница 31: ...or recirculated vent gases Give consideration to excessive wind and locate away from windward side of building Vapors Position termination where vent vapors are not objectionable Walkways Locate vent...

Страница 32: ...ance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 305mm 3 ft 0 9m K Clearance to mechanical air supply inlet 3 ft 0 9m 6 ft 1 8m L Clearance abo...

Страница 33: ...re supports along the joint of each pipe Do not mix boiler sizes on the same piping manifold 6 13 Multiple Boiler Venting Mounting Procedure See Figures 6 23 thru 6 25 1 Vent pipes correctly mounted S...

Страница 34: ...e adapters using approved clamps to wall Ensure clamps are connected minimum of 10 in from top of boiler See Figure 6 26 12 Secure approved clamp around flue adapter Ensure clamp is locked in to prope...

Страница 35: ...bow Type 6 in 8 in Equivalent Length Equivalent Length 45 5 ft 7 in 1 7m 12 ft 3 8 m 90 13 ft 1 in 4 0m 19 ft 5 8 m 6 in Cascade Vent System Example Elbow Equivalent Length 45 90 Number of Elbows 3 Eq...

Страница 36: ...n line each connected to common exhaust manifold 3 2 in per 3 ft 4 in 50 0 mm per 1 0 m B Back to Back System This system consists of boilers installed back to back connected to a common exhaust manif...

Страница 37: ...3 ft 4 in 50 0 mm per 1 0 m 3 6 15 Multiple Boiler Venting Parameter Settings To set parameter P19 see section 9 PARAMETER P19 Revs min rpm at minimum Power Natural Gas LPG 30 30 Flue header size sha...

Страница 38: ...boiler Support condensate pipe to eliminate any sagging Use field source condensate pump if boiler located below disposal point Condensate pump should have overflow switch Condensate from Boiler is s...

Страница 39: ...d pipe dope suitable for liquefied petroleum gas Install external field sourced manual main gas shutoff valve ground joint union and sediment trap upstream of gas valve See figures 7 2 and 7 3 Leak te...

Страница 40: ...tem by closing manual gas shutoff valve See figure 7 3 Locate leakage using gas detector noncorrosive detection fluid or other leak detection method acceptable to authority having jurisdiction Do not...

Страница 41: ...on all sizes Note Wiring diagrams can be found in Appendix A of this Manual 8 2 Electrical Connections Boiler requires 120V 60Hz power supply Verify electrical supply is polarized Boiler shall be grou...

Страница 42: ...al block M1 which is high voltage 120V 60Hz Fuses 3 15 A are incorporated in the power supply terminal block To check or replace fuse pull out black fuse carrier TERMINAL BLOCK M1 L Live brown N Neutr...

Страница 43: ...s per thermostat manufacturer instructions NOTE maximum load allowed is 10 mA FIGURE 8 4 Thermostat Connections 8 5 Install Room Thermostat Install room thermostat on inside wall Do not install where...

Страница 44: ...calculated according to set Kt coefficient Select required curve by rotating right knob as indicated in chart below for selecting the appropriate curve 00 to 90 Flow temp Outside temp NOTE Temperatur...

Страница 45: ...ting supply connection 1 NPT 1 1 4 NPT C Gas connection 3 4 NPT 1 NPT D Drain connection for condensate 3 4 NPT 3 4 Hose 9 1 Central Heating System Connections GMHB227 HEATING ONLY WITH OPTIONAL INDIR...

Страница 46: ...il water flows out Close drain as soon as water appears Systems using radiators to remove air Vent each radiator in turn starting with lowest in the system It is important the pump is properly vented...

Страница 47: ...djustment CW to increase the temperature and CCW to decrease it Heating water temperature adjustment CW to increase the temperature and CCW to decrease it Boiler operating information Operating mode D...

Страница 48: ...ll valves at unused outlets are closed and plugged capped Ensure gas connections are tight 4 Purge air from piping Confirm there is a steady gas supply to the boiler 5 Pressure test the gas line A Tes...

Страница 49: ...ion About 10 min Open Heat Exchanger Aeration purge Valve Boiler Decides If Deaeration OK Boiler ready for CH DHW request Boiler Displays Temperature Display shows Short push Unstable Power supply Che...

Страница 50: ...upted if the central heating supply temperature reaches its MAX SETPOINT To measure combustion efficiency and emissions of products of combustion boiler has two dedicated built in test ports One conne...

Страница 51: ...port with boiler operating at maximum heat capacity matches that indicted in Combustion Table below If it does not turn adjustment screw V Throttle on gas valve Turn the screw clockwise to decrease l...

Страница 52: ...valve must be adjusted before turning boiler on Failure to follow these instructions could result in death or serious injury 9 13 Check Firing Rate 1 Measure input if a gas meter is installed in the s...

Страница 53: ...display to inform the user that moving the Data Knob has no consequences NOP No OPeration 7 short push parameter visualized in display is selected and the board goes in the Value setting menu 8 short...

Страница 54: ...ely call a qualified service technician to inspect appliance and to replace any part of control system and any gas control which has been under water FOR YOUR SAFETY READ BEFORE OPERATING CAUTION WHAT...

Страница 55: ...enu Fault in progress Set unit of measurement SYMBOL Key 10 OPERATING INSTRUCTIONS 10 3 Boiler Controls For correct boiler ignition proceed as follows Check system pressure is correct Power boiler Ope...

Страница 56: ...CSF moving Right Knob CH 10 3 1 Boiler Operating Mode To change the boiler MODE press with a very short push The mode changes are as follows Boiler Start Mode Boiler Mode After Pressing OFF DHW only C...

Страница 57: ...is divided in pages each with 10 parameters i e Ax0 Ax9 While in the INFO menu short push to go to the next page e g from A10 A19 page to A20 A29 page short push to go to the previous page e g from A2...

Страница 58: ...20 29 page 9 short push to go to previous page e g from values 20 29 page to 10 19 page 10 Data Knob turning Right Knob permits scrolling the values in the current selected page 11 short push to save...

Страница 59: ...hows the outdoor temperature value no influence on supply temperature 02 no function is associated 03 heating request input e g telephonic trigger 04 Low temperature safety thermostat 05 DHW pump acti...

Страница 60: ...ptions 7 7 7 7 P30 Manufacturer information Set to 10 Ignore other options 10 10 10 10 P31 Manufacturer information Set to 20 Ignore other options 20 20 20 20 C00 Fault History C00 C01 Fault History C...

Страница 61: ...acturer information Set to 0 Ignore other options 0 0 0 0 P69 Manufacturer information Set to 0 Ignore other options 0 0 0 0 P70 Ignition fan speed Fan speed F70 100rpm Consult factory before adjustin...

Страница 62: ...s that set by adjustable temperature selector burner output is reduced 4 When set temperature is reached burner is turned off and fan stops Pump continues to run for three minutes to remove residual h...

Страница 63: ...quire no further lubrication Lubricate field sourced pumps and or motors according to pump and or motor manufacturer s instruction CAUTION Label all wires prior to disconnection when servicing control...

Страница 64: ...Check condition of electrodes 7 Check spark gap positioning and height of electrodes 8 Check fan impeller is clean and free to rotate 9 Replace used gaskets with new gaskets see parts literature for c...

Страница 65: ...e the system 11 7 Final Assembly Place front jacket in position over boiler Ensure bottom is located behind the control panel Secure in position at top using screws previously removed If boiler is to...

Страница 66: ...om thermostat if fitted are set to User s requirements E Tell User about sealed system pressure F Tell User if display is active and boiler has not operated for 24 hours for heating or hot water the p...

Страница 67: ...ns above 4500 ft 1350m above sea level TABLE 14 SEA LEVEL RATINGS NATURAL AND PROPANE GASES Model Number Input MBH 1 Heating Capacity MBH 1 2 Net AHRI Rating Water MBH 1 3 AFUE 2 Thermal Efficiency Ma...

Страница 68: ...n the flue duct E 83 87 shows possible error of communication with Room units Go to section P E 110 shows overheat of the primary E 117 is displayed when the primary water pressure is more than 2 7 ba...

Страница 69: ...s elapsed from the error event System Status Phase Status CH flow temperature value during the error event See the following table for error codes The system status is the operating mode before the er...

Страница 70: ...SYSTEM STATUS PHASE STATUS CH FLOW TEMPERATURE VALUE DURING ERROR EVENT NO RESET ERROR P32 C00 P33 C01 P34 C02 P35 C03 P36 C04 P37 C05 P38 C06 RESET ERROR P39 C07 P40 C08 P41 C09 Table 13 3 Error Tab...

Страница 71: ...the Calibration Function Enable the Calibration function E71 Fan parameter Out of range in auto calibration Check the fan speed E72 Combustion test Out of range in auto calibration Check the correct p...

Страница 72: ...f the water and the pump Check the status of the primary exchanger E131 Flue thermostat sensor tripped lockout Check the sensor correct circulation of the water and the pump Check the status of the pr...

Страница 73: ...l Check flue recirculation and the combustion levels E66 Obstruction of the flue duct at minimum power Check obstruction on the flue duct E67 Antiwind activation at maximum power Check the position of...

Страница 74: ...284 98 6 640 42 8 2 186 100 4 617 44 6 2 093 102 2 595 46 4 2 004 100 4 617 48 2 1 920 102 2 595 50 0 1 840 104 0 575 51 8 1 763 106 0 556 CHART 2 10 K Ohm INDIRECT TANK SENSOR DATA T R T R F Ohm F Oh...

Страница 75: ...40 40 309396 30 22 171840 20 4 98932 10 14 58879 0 32 36129 10 50 22804 20 68 14773 25 77 12000 30 86 9804 40 104 6652 50 122 4607 60 140 3252 70 158 2337 80 176 1707 90 194 1266 100 212 952 110 230 7...

Страница 76: ...STION AIR Air that is drawn into an appliance to mix with fuel and support combustion CONDENSATE Liquid separated from flue gas due to reduction in temperature DIRECT VENT BOILER Boiler constructed an...

Страница 77: ...exceeds pressure capability of equipment SAFETY SHUTOFF DEVICE Device that will shut off gas supply to controlled burner in event source of ignition fails SEDIMENT TRAP Gas piping arrangement designe...

Страница 78: ...78 PN 240012369 REV A 08 31 2018 A 1 MODEL GMHB227 APPENDIX A WIRING DIAGRAMS...

Страница 79: ...2 3 X22 4 RETURN SENSOR WATER PRESSURE SENSOR X22 7 X22 6 X22 8 P X22 9 X22 10 EXCHANGER SENSOR OUTDOOR SENSOR X20 1 X20 2 DHW TEMP SENSOR X20 3 X20 4 X20 7 X20 8 FLUE SAFETY THERMOSTAT X31 2 X31 1 RE...

Страница 80: ...80 PN 240012369 REV A 08 31 2018 A 2 MODEL GMHB380 APPENDIX A WIRING DIAGRAMS...

Страница 81: ...10 3 FAN X11 1 X23 1 X11 2 X23 2 X23 3 X23 4 X13 1 X13 2 PUMP X1 FLAME SENSOR X5 1 X5 3 GAS VALVE X3 1 X3 2 X37 3 X37 4 JUMPER X22 1 X22 2 FLOW SENSOR X22 3 X22 4 RETURN SENSOR WATER PRESSURE SENSOR X...

Страница 82: ...82 PN 240012369 REV A 08 31 2018 NOTES...

Страница 83: ...83 PN 240012369 REV A 08 31 2018 NOTES...

Страница 84: ...OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decre...

Отзывы: