46
9.3 Fill Condensate Trap with Water
WARNING
Asphyxiation hazard! Fill condensate trap before
starting boiler to avoid combustion products escaping
boiler. Failure to follow these instructions could result in
death or serious injury.
!
• To fill the condensate trap pour water into exhaust vent
until water begins to flow through the siphon.
• Visually inspect the siphon to ensure it is full with clean
water.
• During operation check condensate trap to ensure it drains
properly.
Note
Condensate trap must be manually filled with water
at initial start up.
• (227) Open Aerator valve located on heat exchanger. See
Figure 9-1.
• (227) Boiler is fitted with automatic air vent positioned on
pump Vent and is fitted with adjustable sealing cap. See
Figure 9-1.
• (380) has vent at the top of the boiler. See Illustration
Page 9 of this manual.
• Open central heating flow and return valves. Spindle is flat
in-line with valve.
• Open fill point valve on filling system until water begins to
flow. To aid venting boiler drain may be open until water
flows out. Close drain as soon as water appears.
• Systems using radiators to remove air - Vent each radiator
in turn, starting with lowest in the system.
• It is important the pump is properly vented to avoid
running it dry and damaging its bearings. Unscrew and
remove cap from center of pump. Use screwdriver. Rotate
exposed spindle about half turn, replace cap.
• Check operation of heating pressure relief valve. Pull lever
on top of valve upwards lifting the seat. This will allow
water to escape from system. Check water is escaping
from the system.
• Open cold water supply inlet valve. Turn on all hot water
taps. Allow water to flow until no air is present. Turn
off taps. See page 4- Physical Data and section 2.7
Operational Features.
• Recommended system pressure
21.7 psig.
9.2 System Start Up
Follow all codes and regulations when filling the boiler.
Use drain taps to allow system to completely drain.
Thoroughly flush the heating system before boiler is connected
and again after first heating.
FIGURE 9-1 Condensate Drain Assembly
Model 227 shown (380 at top of boiler)
Pour
approximately
1 cup of water
into flue way of
boiler.
Condensate Drain
Air Vent
Aerator
PN 240012369, REV A [08/31/2018]
9 - START UP PROCEDURE