10.4 Parameters reference value for the normal operation of unit
No.
Parameters name
Unit
Reference value
1
Outdoor
temperature
℃
―
2
Discharge
temperature
℃
After compressor is started up, normal discharge
temperature for cooling is 60~105
℃
, which is
10
℃
above more than the high pressure
saturation temperature.
The normal temperature for heating is 50
℃
~100
℃
, which is 10
℃
above more than the high
pressure saturation temperature.
3
High pressure
MPa
Under the cooling mode at the ambient temperature
of 25~40
℃
, the high pressure value of the system
is 2.2~3.5MPa;
Under the heating mode when the ambient
temperature is above -5
℃
. The high pressure
value of the system is 2.0~3.5MPa.
4
Low pressure
MPa
Under the cooling mode at the ambient temperature
of 25~40
℃
, the low pressure value of the system
is 0.6~1.5MPa;
Under the heating mode when the ambient
temperature is above -5
℃
. The low pressure value
of the system is 0.4~1.5MPa.
5
Current
A
Current should be no more than 20A during
normal operation for compressor
Ultra Heating GMV5 Multi VRF
Содержание ULTRA heating GMV-36WL/B-T
Страница 1: ...Ultra Heating GMV5 Multi VRF for North America R410A GC201603 1 ...
Страница 3: ...1 Ultra Heating GMV5 Multi VRF for North America PRODUCT PRODUCT ...
Страница 15: ...13 for North America CONTROL CONTROL Ultra Heating GMV5 Multi VRF ...
Страница 38: ...36 Ultra Heating GMV5 Multi VRF for North America INSTALLATION ...
Страница 66: ...64 for North America MAINTENANCE Ultra Heating GMV5 Multi VRF ...
Страница 71: ...69 for North America Ultra Heating GMV5 Multi VRF 3 Discharge temperature protection ...
Страница 95: ...JF00302969 ...