DC Inverter U-match Series Duct Type Unit
21
Fig. 4.24
(5) Use a suitable drain hose, and see Table 3.3 for its size.
(6) There is a drain port on both the left and right sides. Select the drain port to
match the local conditions (Fig. 4.23).
(7) When the unit is shipped from the factory, the drain port is defaulted to be
the one on the left side (electric box side); the port on right side has been
plugged.
(8) When using the drain port on the right side of the unit, reinstall the drain cap
to the left side drain port (Fig. 4.25).
Fig. 4.25
Always check that the drain cap is installed to the unused drain port and is fastened with the nylon
fastener. If the drain cap is not installed, or is not sufficiently fastened by the nylon fastener, water
may drip during the cooling operation.
(9) Be sure to insulate where the drain port and the drain hose is connected
(Fig. 4.26).
(10) The unused drain port also should be insulated properly (Fig. 4.27).