DC Inverter U-match Series Duct Type Unit
7
Notes:
①
The
refrigerant
pipe should be insulated with proper water-proof insulating
material.
②
The pipe wall thickness shall be 0.5~1.0mm (1/50~1/25inch) and the pipe
wall shall be able to withstand the pressure of 6.0MPa (870psig). The
longer the connecting pipe, the
less efficient the
cooling and heating
performance
.
3.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 3.4
Notes:
①
The fuse is located on the main board.
②
Install the disconnect device with a contact gap of at least 3mm (1/8inch) in
all poles nearby the units (Both indoor unit and outdoor unit).
The appliance
Indoor Units
Power Supply
Fuse Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
V/Ph/Hz
A
A
A
UMAT18HP230V1BD
208V/230V~60Hz
5
2
15
UMAT24HP230V1BD
208V/230V~60Hz
5
2
15
UMAT30HP230V1BD
208V/230V~60Hz
5
2
15
UMAT36HP230V1BD
208V/230V~60Hz
5
5
15
UMAT42HP230V1BD
208V/230V~60Hz
5
5
15
UMAT48HP230V1BD
208V/230V~60Hz
5
5
15
Table 3.5
Outdoor Units
Power Supply
Fuse Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
V/Ph/Hz
A
A
A
UMAT18HP230V1BO
208V/230V~60Hz
5
16
25
UMAT24HP230V1BO
208V/230V~60Hz
5
24
40
UMAT30HP230V1BO
208V/230V~60Hz
5
24
40
UMAT36HP230V1BO
208V/230V~60Hz
5
45
70
UMAT42HP230V1BO
208V/230V~60Hz
5
45
70
UMAT48HP230V1BO
208V/230V~60Hz
5
45
70