A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
100
MAINTENANCE
1 TROUBLE TABLE
Table 1 Fault Display on Indoor Wired Controller:
Trouble
Code
Trouble
Name
Origin of
Trouble Signal
Control Description
E0
Water Pump
Malfunction
Water pump
If the water-full protection cannot be recovered after 2 hours, it is
believed that the water pump is failed, in which case all the loads will
be switched off and cannot be recovered automatically.
E1
High Pressure
Protection of
Compressor
High-pressure
Switch
When high pressure protection is detected for 3 seconds successively,
all the loads (except the heating 4-way valve) will be switched off, in
which case all the keys and remote control signals except ON/OFF
function will be disabled and cannot be recovered automatically. To
eliminate the fault, it is needed to switch off and on the machine or
recover from power failure.
E2
Indoor
Anti-frozen
Protetion
Indoor
evaporator
sensor
If detecting that the evaporator sensor is lower than protective temp.
value after the unit has been running for a period of time under cooling
or dry mode, the unit will report this fault, in which case the compressor
and outdoor fan will be stopped. The unit will not run until this
temperature exits the pretective temperature value and the compressor
is stopped for 3 minutes.
E3
Low Pressure
Protection of
Compressor
Low-pressure
Switch
If it is detected within 30 seconds successively that the low-pressure
switch is cut off under ON or standby state (If the compressor is started,
the detection will start 3 minutes after the compressor has run), the unit
will report this fault. For the first two faults within 30 minutes, the unit
can be recovered automatically. If over three times, the unit cannot be
recovered automatically.
E4
Air Discharge
High-temperatur
e Protection of
Compressor
Exhaust
Overtemperatur
e Protection
After the compressor is started, if it is detected within 30 seconds
successively that the exhaust temperature is 130 or higher, E4 will be
℃
displayed, in which case all the loads (except the 4-way valve of
heating) will be stopped. The complete unit can only be recovered until
the compressor has stopped for 3 minutes and the exhaust
temperature is lower than 90 . For this protection occurs three times,
℃
the complete unit cannot be recovered automatically.
E5
Overload
Proection of
Compressor
Compressor
After the unit is energized, if it is detected within 3 seconds
successively that the compressor overload switch is cut off, it will be
deemed compressor overload protection. In this case, all the loads will
be stopped (except the 4-way valve of heating) and E5 will be
displayed. If the fault is eliminated, the compressor will be restarted
after 3 minutes. If three compressor overload protections are detected
successively in 30 minutes from the first detection to the occurrence of
fault, the compressor cannot be recovered automatically and the
buzzer will alarm. You shall need to press ON/Off to stop the unit and
clear the sound alarm before pressing ON/OFF again. The unit will be
restarted if the high pressure protection disappears; otherwise the fault
code will be displayed. Besides, “E5” also will also be displayed on the
controller in the event of an error of the compressor drive module.
E6
Communication
s Failure
Communication
between indoor
and outdoor
mainboard
If the outdoor unit does not receive data from indoor unit for 30 seconds
successively once energized, this indicates indoor communication
failure. In this case, the compressor and outdoor fan will be stopped.
Under heating mode, the 4-way valve will be stopped if the compressor
has been stopped for 2 minutes. If the indoor unit does not receive
message from outdoor unit for 1 minute, this indicates communication
failure. In this case, the indoor unit will be stopped and the indicator will
blink. If the display board does not receive message from outdoor unit
in 1 minute, it can be judged that it is communication failure, in which
case the fault will be displayed and the machine will not function. After
the communication is resumed to normal, the system will run as per the
working mode before. This can recover automatically.
E9
Full Water
Protection
Liquid level
switch
If “full water” is detected for 8 seconds successively once energized,
the system will enter into full water protection and the indicator will blink
Содержание U-MATCH GFH09K3CI
Страница 4: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT...
Страница 25: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL...
Страница 26: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 23 CONTROL 1 OPERATION FLOWCHART 1 1Cooling Dry Operation...
Страница 27: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation...
Страница 62: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions...
Страница 63: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION...
Страница 102: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE...
Страница 108: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 105 Malfunction display E1 Compressor High Pressure Protection...
Страница 109: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 106 Malfunction display E3 Compressor Low Pressure Protection...
Страница 121: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection...
Страница 122: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection...
Страница 123: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection...
Страница 124: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor...
Страница 125: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection...
Страница 126: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping...
Страница 130: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 127 Tripping...
Страница 136: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 133 Model GUHD24NK3CO GUHD30NK3CO Model GUHD36NK3CO GUHD42NK3CO...
Страница 137: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 134 Model GUHD48NK3CO Model GUHD36NM3CO GUHD42NM3CO...
Страница 138: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 135 Model GUHD48NM3CO Model GUHD60NM3CO...
Страница 182: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 179 3 A B 0 5 0 1kgf c C 4 5 6 A B 0 5 0 1kgf c C...
Страница 183: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 180 7 8 A B C 9 A B 0 5 0 1kgf c C 10 A B...
Страница 195: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 192 4 5 6...
Страница 197: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 194 5 6 A B 0 5 0 1kgf c C 7 8 A B C...
Страница 198: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 195 9 A B 0 5 0 1kgf c C 10 A B 11 A B 0 5 0 1kgf c C 12 A B...
Страница 227: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 224 Model GUHD24NK3CO Exploded View...
Страница 233: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 230 Model GUHD36NM3CO GUHD42NM3CO Exploded View...
Страница 235: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 232 Model GUHD48NM3CO GUHD60NM3CO Exploded View...
Страница 247: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model GKH18K3CI Exploded View...
Страница 252: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 249 Model GKH36K3CI GKH42K3CI Exploded View...
Страница 264: ...261 JF00300705...