GREE U-Match 5 SERIES UNIT SERVICE MANUAL
55
3.4 Troubleshooting
3.4.1 “E1” Compressor High Pressure Protection
Error display:
ODU mainboard, IDU wired controller and IDU receiver light board will display E1
Error judgment condition and method:
It is judged through the action of high pressure switch. If the high pressure switch is cut off, it is judged that
high pressure is too high and the system stops operation for protection.
Possible reason
:
■Cut
-off valve of ODU is not fully opened;
■High pressure switch is abnormal;
■Outdoor or indoor fan is not working properly;
■IDU filter or air duct is blocked (heating mode);
■Ambient temperature is too high
;
■Refrigerant charging amount is too much;
■System pipeline is blocked
Содержание U-Match 5 Series
Страница 30: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 27 Model GUD50W NhA T Model GUD71W NhA T GUD85W NhA T...
Страница 31: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 28 Model GUD100W NhA T...
Страница 32: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 29 Model GUD125W NhA T GUD140W NhA T...
Страница 33: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 30 Model GUD100W NhA X...
Страница 34: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 31 Model GUD125W NhA X GUD140W NhA X...
Страница 35: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 32 Model GUD160W NhA X...
Страница 36: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 33 3 1 2 Wiring Diagrams of IDUs Model GUD35T A T GUD50T A T...
Страница 40: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 37 Wall Mounted Type Model GUD71G A T Model GUD100G A T...
Страница 59: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 56 Troubleshooting...
Страница 78: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 75 Troubleshooting...
Страница 224: ...JF00303775...