GREE                                                     U-Match 5 SERIES UNIT SERVICE MANUAL 

19 

displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:

 

(1)   Centralized controller (LCD displays 00). 

(2)   Long-distance monitoring (LCD displays 01). 

2.3.9.9 Selecting fan mode of indoor fan motor 

Under  debugging  state,  press  Mode  button  to  adjust  to  “11” in  temperature displaying  zone. Timer  zone 

displays setting state and p

ress ▲ or ▼ button to adjust. 

 

a.There are 5 selections for low static pressure duct: 

(1)   P3 (LCD displays 03). 

(2)   P4 (LCD displays 04). 

(3)   P5 (LCD displays 05). 

(4)   P6 (LCD displays 06). 

(5)   P7 (LCD displays 07). 

Note:

 You can select P03, P04, P05, P06, P07 in fan mode of indoor fan motor, which means different fan mode 

combinations are corresponding to different static pressure. Ex-factory defaulted mode is P05. You can set the 

mode through wired controller. S01, S02, S03……S12, S13 means the rotation speed of indoor unit is from low to 

high. 

Combination relationship of P03, P04, P05, P06, P07. 

Static 

pressure 

selection 

Super 

high 

speed 

High 

speed 

Medium 

high 

speed 

Medium 

speed 

Medium 

low speed 

Low 

speed 

Quiet 

R1 speed 

Quiet 

R2 speed 

Quiet 

R3 speed 

P03 

S09 

S08 

S07 

S06 

S05 

S04 

S03 

S02 

S01 

P04 

S10 

S09 

S08 

S07 

S06 

S05 

S04 

S03 

S02 

P05 

S11 

S10 

S09 

S08 

S07 

S06 

S05 

S04 

S03 

P06 

S12 

S11 

S10 

S09 

S08 

S07 

S06 

S05 

S04 

P07 

S13 

S12 

S11 

S10 

S09 

S08 

S07 

S06 

S05 

b.There are 9 selections for high static pressure duct: 

(1)   P1 (LCD displays 01). 

(2)   P2 (LCD displays 02). 

(3)   P3 (LCD displays 03). 

(4)   P4 (LCD displays 04). 

(5)   P5 (LCD displays 05). 

(6)   P6 (LCD displays 06). 

(7)   P7 (LCD displays 07). 

(8)   P8 (LCD displays 08). 

Содержание U-Match 5 Series

Страница 1: ...1 U Match 5 SERIES UNIT SERVICE MANUAL GC202011 VII Capacity 3 5kW 16 0kW Rate Frequency 50 60Hz Operation Range 20 48...

Страница 2: ...ning system may fail or be damaged and personnel safety accident may also occur Safety Notice The air conditioner is charged with inflammable refrigerant R32 Before using the air conditioner please fi...

Страница 3: ...3 Error Code 53 3 4 Troubleshooting 55 3 5 Failures Not Caused by Errors 89 4 Maintenance 91 4 1 System Diagram 91 4 2 Connection Pipe Vacuum Pumping 91 4 3 Refrigerant Charging 92 4 4 Maintenance of...

Страница 4: ...cations WARNING 1 If the working place is more than 2m s high please wear a safety helmet gloves and a safety belt 2 Never mix any other substances except the specified refrigerant into the refrigeran...

Страница 5: ...should all be done according to applicable local rules and regulations Safety Notice on Operation PROHIBITED 1 Never try to modify the unit otherwise it may cause electric shock overheat or fire haza...

Страница 6: ...its 1 1 1 List of ODUs Model Power Supply Finished Product Code Appearance V Ph Hz GUD35W NhA T 220 240V 50Hz 208 230V 60Hz CF090W1310 GUD50W NhA T CF090W1210 GUD71W NhA T CF090W1220 GUD85W NhA T CF09...

Страница 7: ...h Hz GUD100W NhA X 380 415V 3N 50Hz 60Hz CF090W1250 GUD125W NhA X CF090W1270 GUD140W NhA X CF090W1290 GUD160W NhA X CF090W1300 Note 1 Ton 12000Btu h 3 517kW If one outdoor unit is to be connected with...

Страница 8: ...roduct Code Appearance V Ph Hz Cassette Type GUD35T A T 3 5 4 0 220 240V 50Hz 208 230V 60Hz ET010N1640 GUD50T A T 5 0 5 5 ET010N1540 GUD71T A T 7 0 8 0 ET010N1420 GUD85T A T 8 5 8 8 ET010N1430 GUD100T...

Страница 9: ...GUD35P A T 3 5 4 0 220 240V 50Hz 208 230V 60Hz CF022N1650 GUD50P A T 5 0 5 5 CF022N1630 GUD71P A T 7 0 8 0 CF022N1670 GUD85P A T 8 5 8 8 CF022N1610 GUD71PH A T 7 0 8 0 CF022N2890 GUD85PH A T 8 5 8 8...

Страница 10: ...5PS A T 3 5 4 0 220 240V 50Hz 208 230V 60Hz CF022N1640 GUD50PS A T 5 0 5 5 CF022N1620 GUD71PS A T 7 0 8 0 CF022N1660 GUD85PS A T 8 5 8 8 CF022N1600 GUD71PHS A T 7 0 8 0 CF022N2900 GUD85PHS A T 8 5 8 8...

Страница 11: ...T 7 0 8 0 ED020N1740 GUD85ZD A T 8 5 8 8 ED020N1750 GUD100ZD A T 10 0 12 0 ED020N1680 GUD125ZD A T 12 1 13 5 ED020N1690 GUD140ZD A T 13 4 15 5 ED020N1700 GUD160ZD A T 16 0 17 0 ED020N1710 Wall Mounted...

Страница 12: ...ambient temperature is 40 and multi core copper cable e g YJV copper cable with insulated PE and PVC sheath is protected by a conduit and is resistant to 90 in maximum See IEC 60364 5 52 If working c...

Страница 13: ...ower on Cooling start control Indoor fan run Satisfying open Comp condition Comp and outdoor fan run Oil return IN conditi on are met Defrost IN condition are met Oil return operation Defrosting opera...

Страница 14: ...r 1 min Comp and outdoor fan stop 2 2 Control Mode 2 2 1 Based Control 2 2 1 1 Compressor Control When cooling or heating mode is turned on indoor fan will run for a while before the compressor starts...

Страница 15: ...mporarily and lose power after a while There must be adequate differential pressure for the 4 way valve to change directions 2 2 2 Special Control 2 2 2 1 Defrosting Control ODU defrosting control in...

Страница 16: ...s to be used to enable this control For cassette type unit you can enable the control through the light board Enabling method through the light board of cassette type unit After the unit is installed...

Страница 17: ...lue When high temperature prevention control is enabled outdoor fan will slow down 2 3 Functions 2 3 1 Setting of Filter Cleaning Reminder When setting washing remind function the timer area will disp...

Страница 18: ...of unit press and buttons simultaneously for 5 seconds can enter into child lock function the liquid crystal screen will display Press and buttons simultaneously again for 5 seconds can quit the child...

Страница 19: ...ING ENTER button for 5 seconds to enter into ambient temperature inquiry interface then timer area displays the ambient temperature type 01 or 02 and ambient temperature area displays the correspondin...

Страница 20: ...nit 2 3 9 3 Setting refrigerant lacking protection function Under debugging state press Mode button to adjust to 04 in temperature displaying zone Timer zone displays setting state and press or button...

Страница 21: ...perature is within 35 37 the belt will keep its previous operation state Mode 2 Compressor electric heating belt starts when outdoor ambient temperature is below 2 and stops when outdoor ambient tempe...

Страница 22: ...fan mode combinations are corresponding to different static pressure Ex factory defaulted mode is P05 You can set the mode through wired controller S01 S02 S03 S12 S13 means the rotation speed of indo...

Страница 23: ...3 S02 S02 S02 S02 S02 P3 S07 S05 S04 S04 S03 S03 S03 S03 S03 P4 S08 S06 S05 S05 S04 S04 S04 S04 S04 P5 S09 S07 S06 S06 S05 S05 S05 S05 S05 P6 S10 S08 S07 S07 S06 S06 S06 S06 S06 P7 S11 S09 S08 S08 S07...

Страница 24: ...mer zone displays setting state and press or button to adjust There are 2 selections 1 Auto mode 1 the set temperature under auto mode can t be adjusted LCD displays 01 2 Auto mode 2 the set temperatu...

Страница 25: ...er and Mode buttons at the same time for 5s to set master and slave wired controller Then press or button to adjust the value 01 stands for the master wired controller and 02 stands for the slave wire...

Страница 26: ...of centralized controller The unit will memorize this setting status The setting value will be memorized after power failure Address setting of each unit when the address mode is set to be Long dista...

Страница 27: ...d receive logical control information to realize control and monitor of the unit 2 Function instructions In order to achieve this function set the address mode and address through wired controller Ple...

Страница 28: ...unit press Function and Mode buttons at the same time for 5s to enter setting interface of wired controller address LCD displays address sequence Press or button to adjust the address sequence and th...

Страница 29: ...T SERVICE MANUAL 26 3 Troubleshooting 3 1 Wiring Diagrams The following electric diagram is for reference only Please refer to diagram sticked on the unit as the latest version 3 1 1 Wiring Diagrams o...

Страница 30: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 27 Model GUD50W NhA T Model GUD71W NhA T GUD85W NhA T...

Страница 31: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 28 Model GUD100W NhA T...

Страница 32: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 29 Model GUD125W NhA T GUD140W NhA T...

Страница 33: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 30 Model GUD100W NhA X...

Страница 34: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 31 Model GUD125W NhA X GUD140W NhA X...

Страница 35: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 32 Model GUD160W NhA X...

Страница 36: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 33 3 1 2 Wiring Diagrams of IDUs Model GUD35T A T GUD50T A T...

Страница 37: ...SERIES UNIT SERVICE MANUAL 34 Model GUD71T A T GUD85T A T GUD100T A T GUD125T A T GUD140T A T GUD160T A T Duct Type Model GUD35P A T GUD50P A T GUD71P A T GUD85P A T GUD35PS A T GUD50PS A T GUD71PS A...

Страница 38: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 35 Model GUD71PH A T GUD85PH A T GUD71PHS A T GUD85PHS A T Model GUD100PH A T GUD125PH A T GUD140PH A T GUD100PHS A T GUD125PHS A T GUD140PHS A T...

Страница 39: ...REE U Match 5 SERIES UNIT SERVICE MANUAL 36 Model GUD160PH A T GUD160PHS A T Floor Ceiling Type Model GUD35ZD A T GUD50ZD A T GUD71ZD A T GUD85ZD A T GUD100ZD A T GUD125ZD A T GUD140ZD A T GUD160ZD A...

Страница 40: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 37 Wall Mounted Type Model GUD71G A T Model GUD100G A T...

Страница 41: ...pump 4 WATER_DTCT Water level switch 5 UD_SWING2 Vertical swing output 2 6 UD_SWING1 Vertical swing output 1 7 DOOR_C Access control interface 8 COM_BMS MODBUS gateway interface 9 COM1 COM2 Accessorie...

Страница 42: ...ntrol interface 8 COM_BMS MODBUS gateway interface 9 COM1 COM2 Accessories communication interface 10 COM_MANUAL Wired controller communication interface 11 COM_OUT ODU communication interface 12 TUBE...

Страница 43: ...input 2 AC N Neutral wire input 3 PE Ground wire 4 DC MOTOR DC motor output 5 CN6 Motor type selection interface 6 COM OUT ODU communication interface 7 COM MANUAL Wired controller communication inter...

Страница 44: ...ut 7 SWING UD Vertical swing output 8 WIFI WIFI wire terminal 9 DISP1 Light board interface 1 10 DISP2 Light board interface 2 11 TUBE Evaporator temperature sensor 12 ROOM Ambient temperature sensor...

Страница 45: ...porator temperature sensor 8 ROOM Ambient temperature sensor interface 9 SWING LR1 SWING LR2 Horizontal swing output 10 SWING UD Vertical swing output 11 DISP1 Light board interface 1 12 SW1 AUTO KEY...

Страница 46: ...g 6 2WAY 2 way valve 7 4WAY 4 way valve 8 OFAN External drive DC fan 9 LPP System low pressure protection interface 10 FA Solenoid expansion valve 11 T_SENSOR Temperature sensor group 12 OVC_COMP Comp...

Страница 47: ...interface 11 HEAT B Chassis electric heating 3 FA Electronic expansion valve 12 JUMP1 Jumper cap 4 T SENSOR Temperature sensor 13 DRED DRED 5 OVC COMP Compressor overload detection 14 COM7 IDU and ODU...

Страница 48: ...valve 1 interface Refrigerant heat dissipation 9 DRED DRED communication interface 10 COMM1 Drive communication interface 11 OVC_COMP Compressor overload protection interface 12 LPP System low pressur...

Страница 49: ...2 L2 1 PFC induction wire yellow 4 N Neutral wire 13 G OUT Reserved 5 COMM1 Communication terminal same with COMM 14 U Compressor U phase terminal 6 COMM Communication terminal same with COMM1 15 V Co...

Страница 50: ...UT Power output neutral wire terminal 3 E1 Filtering board ground wire terminal 7 L OUT Power output live wire terminal 4 E2 Filtering board grounding hole reserved Power Board No Printing Interface N...

Страница 51: ...1 PWR Power supply busbar input terminal 2 X1 X2 X3 Mainboard power supply 3 phase input terminal 3 X4 X5 X6 Electric reactor 3 phase connection terminal input terminal 4 X7 X8 X9 Electric reactor 3...

Страница 52: ...L3 2 X5 Power output wire L1 F connect to drive board L1 F 8 X2 Unit power input wire AC L2 3 X6 Power output wire L2 F connect to drive board L2 F 9 X1 Unit power input wire AC L1 4 X7 Power output w...

Страница 53: ...N Neutral wire 9 COMM Communication interface 3 PWR Drive power supply busbar terminal 10 W Compressor W phase 4 L2 2 PFC induction wire white 11 V Compressor V phase 5 L2 1 PFC induction wire white 1...

Страница 54: ...S DC busbar terminal 5 E Filtering board grounding hole 3 2 2 IPM PFC Testing Method 3 2 2 1Method of Testing IPM Module 1 Preparation before test prepare a universal meter and turn to its diode optio...

Страница 55: ...ter it is powered off for one minute 2 Testing Steps Step 1 Put the black probe on the place P and the red one on the wiring terminal L1 2 L2 1respectively as shown in the following figure to measure...

Страница 56: ...ure protection 5 E6 Communication error 6 E8 Indoor fan error 7 E9 Water full protection 8 F0 Indoor ambient temperature sensor error 9 F1 Evaporator temperature sensor error 10 F2 Condenser temperatu...

Страница 57: ...Pd Sensor connection protection 36 PL Bus low voltage protection 37 PH Bus high voltage protection 38 PU Charge loop error 39 PP Input voltage error 40 ee Drive memory chip error 41 C4 ODU jumper cap...

Страница 58: ...through the action of high pressure switch If the high pressure switch is cut off it is judged that high pressure is too high and the system stops operation for protection Possible reason Cut off valv...

Страница 59: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 56 Troubleshooting...

Страница 60: ...display E2 Error judgment condition and method Check IDU pipe temperature When pipe temperature is too low freeze protection will be activated to prevent freezing damage of evaporator Possible reason...

Страница 61: ...ethod It is judged through the action of low pressure switch If the low pressure switch is cut off it is judged that low pressure is too low and the system stops operation for protection Possible reas...

Страница 62: ...cuum pumping and pressure retaining are passed Check if there is leakage in the pipeline Reconnect wire according to the circuit diagram or replace the pressure switch Yes 35 85 outdoor units are with...

Страница 63: ...t fully opened Electronic expansion valve is abnormal Outdoor or indoor fan is not working properly IDU filter or air duct is blocked cooling mode Ambient temperature exceeds allowable operation range...

Страница 64: ...ition and method If no communication between ODU and IDU or between IDU and wired controller in continuously 120s this error will be reported Possible reason Communication wire is connected improperly...

Страница 65: ...will display E8 Error judgment condition and method Check if the rotation speed of IDU is too slow or it stops rotation or protection signal of outdoor fan is transferred If yes it is judged that ind...

Страница 66: ...light board will display E9 Error judgment condition and method Check the status of IDU float switch When water level is too high float switch is activated so water full protection happens Possible re...

Страница 67: ...temperature sensor and terminal in mainboard interface Ambient temperature sensor is abnormal Detecting circuit is abnormal Troubleshooting 3 4 9 F1 Evaporator Temperature Sensor Error Error display...

Страница 68: ...ppendix 1 for the relation between temperature and resistance of temperature sensor 3 4 10 F2 Condenser Temperature Sensor Error Error display ODU mainboard IDU wired controller and IDU receiver light...

Страница 69: ...r the relation between temperature and resistance of temperature sensor 3 4 11 F3 Outdoor Ambient Temperature Sensor Error Error display ODU mainboard IDU wired controller and IDU receiver light board...

Страница 70: ...r and IDU receiver light board will display F4 Error judgment condition and method Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD valu...

Страница 71: ...e and resistance of temperature sensor 3 4 13 F5 Wired Controller Temperature Sensor Error Error display IDU wired controller and IDU receiver light board will display F5 Error judgment condition and...

Страница 72: ...led Jumper cap model is wrong Detecting circuit is abnormal Troubleshooting 3 4 15 EE ODU Memory Chip Error Error display IDU wired controller IDU and ODU receiver light board will display EE Error ju...

Страница 73: ...nsor detecting circuit and judge the range of AD value If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously report the error Possible reason Poor contact between temp...

Страница 74: ...protection compressor overload protection Check if the over comp interface on the mainboard is connection Replace the mainboard Connection the over comp interface YES NO 3 4 18 H4 Overload Error disp...

Страница 75: ...ntroller and IDU receiver light board will display H5 Error judgment condition and method When power is connected and drive chip received IPM lead F0 that is of low level than it is IPM module malfunc...

Страница 76: ...judgment condition and method Mainboard doesn t receive the signal of outdoor fan within 30s after the outdoor fan starts up Possible reason Outdoor fan wiring terminal is not correctly connected to t...

Страница 77: ...or display ODU mainboard IDU wired controller and IDU receiver light board will display H7 Error judgment condition and method During operation it can t detect the rotor position and stops output Or t...

Страница 78: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 75 Troubleshooting...

Страница 79: ...m will shut down for protection Possible reason Power grid voltage is abnormal Drive board PFC module is damaged Drive board IPM module s 15V power supply is lower than 13 5V Drive board PWM signal fo...

Страница 80: ...receive light board will display Lc Error judgment condition and method Check the error code on nixie tube of ODU main controller board If PJ is displayed it indicates inverter compressor startup fai...

Страница 81: ...or judgment condition and method Possible reason Voltage is abnormal For example low voltage will cause abnormal direction change of the 4 way valve Pilot valve holder hole or the capillary tube is bl...

Страница 82: ...Replace the drive board Re arrange the wires Heavy current wires s hould avoid the drive board chip NO YES 3 4 27 P5 Over Current Protection Error display ODU mainboard IDU wired control and IDU recei...

Страница 83: ...communication between master control and driver is cut off for 30s then it can be judged that the communication between master control and driver is faulted System will shut down for protection Possi...

Страница 84: ...PM or PFC module temperature is lower than the set protection value then it can be judged that driver module sensor error occurs and system will shut down for protection Possible reason Module tempera...

Страница 85: ...module The module securing screws are not tightened up Drive board temperature sampling circuit element is damaged or drive chip temperature sampling AD terminal is abnormal Troubleshooting 3 4 31 PA...

Страница 86: ...set voltage average is detected to exceed 12 5 of 1 65V in 1s then it can be judged that current detection or current sensor circuit is faulted System will shut down for protection Possible reason Cur...

Страница 87: ...AD value exceeds upper limit and lower limit in 5 seconds continuously report the error Possible reason Poor contact between sensor and terminal in mainboard interface sensor is abnormal Detecting ci...

Страница 88: ...maged or drive board busbar voltage sampling AD terminal is abnormal Troubleshooting PL Bus low voltage protection Grid voltage is normal or not Normal protection Replace the dr ive board YES NO 3 4 3...

Страница 89: ...not reach the set value in a certain period of time then it can be judged that charge loop error exists System will shut down for protection Possible reason Voltage of power grid is abnormal Voltage i...

Страница 90: ...ive board that needs memory chip is not installed with the memory chip The lead or connector of memory chip is badly welded or short circuited Troubleshooting ee Drive memory chip error Drive board is...

Страница 91: ...tch 5 SERIES UNIT SERVICE MANUAL 88 Troubleshooting 3 4 39 EL Emergency Stop Fire Alarm If fire alarm terminal is enabled after the IDU mainboard connects to function expansion panel error EL will be...

Страница 92: ...plug is loose Re insert the power plug Remote controller has low battery Replace the batteries Bad cooling or heating effect Air inlet and outlet of indoor or outdoor units have been blocked Clear the...

Страница 93: ...ection The sound will disappear after the valve changes its direction There is hissing sound when the unit is started or stopped and a slight hissing sound during and after operation It s the sound of...

Страница 94: ...essure side of the manifold valve assembly and start the vacuum pump Meanwhile the switch at the high pressure side of the manifold valve assembly should be kept closed otherwise evacuation would fail...

Страница 95: ...nect the two hoses of the branch valve assembly to the maintenance ports to speed up the evacuation Refrigerant should be reclaimed into the appropriate storage tank System should use oxygen free nitr...

Страница 96: ...rged refrigerant m m1 m2 m M m The remaining charging quantity is m M m Step 8 After charging remove the pressure gauge Refrigerant charging when unit is turned on Step 1 Close the valve of refrigeran...

Страница 97: ...or not yet completed stick a label on the system 5 Before re charging refrigerant into the system use oxygen free nitrogen to perform pressure test When charging is completed perform leak test before...

Страница 98: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 95 1 Inverter compressor QXF A102zE170B 2 Inverter compressor QXF B141zF030F 3 Inverter compressor QXFS D25zX090H 4 Inverter compressor QXFS D32zX090D...

Страница 99: ...CE MANUAL 96 5 Inverter compressor QXFS D32zX090C 6 Inverter compressor QXFS F428zX450E 7 Inverter compressor QXFS F428zX450I Step 2 Judge whether the operating noise of the compressor is normal and w...

Страница 100: ...of the valve spool In the last stage of the reset process you will hear the click of the valve and feel its vibration Touch the electronic expansion valve a Touch the top of the electronic expansion...

Страница 101: ...ed to the exhaust side it is with high pressure and high temperature regardless of the operating mode When the unit is powered on in defrosting or oil return mode the 4 way valve will produce some noi...

Страница 102: ...t the unit cannot be started up we also need to check the solenoid valve assembly of the system including the electronic expansion valve The checking method is the same as instructed above Step 4 Chec...

Страница 103: ...and models of the compressors are identical Make sure the rubber seal of the liquid separator is complete If it is lost during transport use adhesive tape to seal the opening at once The container mu...

Страница 104: ...otice board on the power switch to remind people to be cautious of electric shock Step 3 Neaten the electric components When you detach the compressor wires temperature sensors and electric heaters ma...

Страница 105: ...ction 2 Prevent the compressor from falling 3 Put a transparent container over 150ml in volume under the exhaust pipe to collect the compressor oil thus we can see the oil quality 3 Put the container...

Страница 106: ...essor please refer to the section Removal of Major Components Step 9 Check Replace the gas liquid separator Note If a compressor is damaged and needs to be replaced its gas liquid separator should als...

Страница 107: ...ng belt according to the signs marked before and the wiring diagram on the cover of the electric box 4 4 3 How to replace the drive module of compressor Step 1 First make sure that power is cut off Se...

Страница 108: ...ODU Major Components Picture Name Function Compressor Through compression the low pressure refrigerant occupies a less space As its pressure and temperature both rise it becomes high pressure and high...

Страница 109: ...of the hot flow to the cold flow so that the flow temperature can reach the specified index It is an energy exchanging device Electronic expansion valve It is used to lower the pressure and temperatur...

Страница 110: ...panel to the middle insulating board and screws around the front panel 5 Remove the right side plate Unscrew the screws that connect the right side plate to the electric box and the screws around the...

Страница 111: ...de plate 10 Install the upper cover plate Tighten up the screws around the upper cover plate Model GUD35W NhA T GUD50W NhA T GUD71W NhA T GUD85W NhA T Removal of compressor Note Before removing the co...

Страница 112: ...of compressor 3 Break off the pipes that connecting to the compressor Weld the pipes that are connected to the compressor Then remove the pipes Note When welding the pipes do not let the flame burn th...

Страница 113: ...ng the nearby pipeline and components 7 Connect the compressor wires Connect the compressor wires to the wire terminals on the top of compressor Note When connecting the wires be sure to match the col...

Страница 114: ...he flame burn the other components 3 Replace the 4 way valve and connect it to the connection pipes Replace the 4 way valve and then use a soldering gun to weld the 4 joints of the 4 way valve Tighten...

Страница 115: ...otor Use a screwdriver to unscrew the bolt of motor Note Motor wire should be first removed from the electric box 4 Install the motor Replace with a new motor Then tighten up the screw bolt 5 Install...

Страница 116: ...n the wire clamp at the bottom of the electric box Unscrew the screws of electric box The connection wires inside and outside the electric box should be removed 3 Remove motor support When removing th...

Страница 117: ...the chassis Install the condenser by referring to the positions of entering and leaving pipes Weld the connection pipes Nitrogen welding the pressure of nitrogen is 0 5 0 1kgf c relative pressure Note...

Страница 118: ...nt panels Loosen the wire clamp at the bottom of the electric box Unscrew the screws of electric box 2 Remove the electric box The connection wires inside and outside the electric box should be remove...

Страница 119: ...alve the valve should be wrapped with wet cloth Nitrogen welding the pressure of nitrogen is 0 5 0 1kgf c relative pressure Note When welding the pipes do not let the flame burn the other components I...

Страница 120: ...e Work instruction 1 Remove the upper cover plate Unscrew the screws of the upper cover plate with a screwdriver 2 Remove the front side plate Unscrew the screws of the upper and front side plate with...

Страница 121: ...to the electric box and the screws around the right side plate 6 Install the right side plate Screw up the screws around the right side plate Be careful to handle well the clasps at the bottom of the...

Страница 122: ...ound the upper cover plate Model GUD100W NhA T GUD125W NhA T GUD140W NhA T GUD100W NhA X GUD125W NhA X GUD140W NhA X Removal of compressor gas liquid separator Note Before removing the compressor gas...

Страница 123: ...s Note When welding the pipes do not let the flame burn the other components 3 Loosen the compressor s base connectors gas liquid separator s base nuts Use a wrench to twist off the compressor gas liq...

Страница 124: ...compressor avoid touching the nearby pipeline and components 7 Connect the compressor wires Connect the compressor wires to the wire terminals on the top of compressor Note When connecting the wires...

Страница 125: ...e connection pipes Note When welding the pipes the 4 way valve should be wrapped with wet cloth for cooling Do not let the flame burn the other components 3 Replace the 4 way valve and connect it to t...

Страница 126: ...e the grill Use a screwdriver to unscrew the two screws on the upper left and lower right corners 2 Remove the fan Use a wrench to remove the specialized nut and gasket of the fan Note Please keep the...

Страница 127: ...use a screwdriver to tighten up the screw bolt that secures the motor Arrange the wires according to the wiring diagram Model GUD100W NhA T GUD125W NhA T GUD140W NhA T GUD100W NhA X GUD125W NhA X GUD...

Страница 128: ...the flame burn the other components The welding points of condenser are steel and copper welding points Be sure to maintain the welding quality 5 Take out the condenser Loosen the securing screws of c...

Страница 129: ...ion wire is well connected If everything is OK place back the upper left and right side panels Model GUD100W NhA T GUD125W NhA T GUD140W NhA T GUD100W NhA X GUD125W NhA X GUD140W NhA X Removal of elec...

Страница 130: ...emove the fixed block Remove the fixed block between the electronic expansion valve and the pipe 3 Remove the electronic expansion valve Take off the coil of electronic expansion valve Loosen the conn...

Страница 131: ...e valve should be wrapped with wet cloth Nitrogen welding the pressure of nitrogen is 0 5 0 1kgf c relative pressure Note When welding the pipes do not let the flame burn the other components Install...

Страница 132: ...the screws of the upper cover plate with a screwdriver 2 Remove the front grill Unscrew the screws of the front grill with a screwdriver 3 Remove the front panel Unscrew the screws that connect the f...

Страница 133: ...around the right side plate Be careful to handle well the clasps at the bottom of the right side plate 6 Install the front panel Install the front panel by mounting on 6 clasps on its both sides Pleas...

Страница 134: ...ires with a screwdriver Remove the wires Note When removing the wires mark the wire terminals corresponding to their color so as to avoid misconnection 2 Loosen the securing screws at the foot of comp...

Страница 135: ...compressor and replace it Note When replacing the compressor avoid touching the nearby pipeline and components 5 Fix the new compressor back onto the chassis After replacing the compressor tighten up...

Страница 136: ...re terminals Model GUD160W NhA X Removal of 4 way valve Note Before removing the 4 way valve make sure refrigerant is fully discharged from the unit and power is cut off Step Picture Work instruction...

Страница 137: ...the 4 way valve should be wrapped with wet cloth for cooling Do not let the flame burn the other components 4 Install the coil of 4 way valve Tighten the screws of the coil of 4 way valve with a screw...

Страница 138: ...first removed from the electric box 4 Install the motor Replace with a new motor Then tighten up the screw bolt 5 Install the fan Install the fan in place Put on the gasket and use a wrench to secure...

Страница 139: ...ove the upper lower and front panels Loosen the wire clamp at the bottom of the electric box Unscrew the screws of electric box 2 Remove the electric box The connection wires inside and outside the el...

Страница 140: ...the 2 welding interfaces Nitrogen welding the pressure of nitrogen is 0 5 0 1kgf cm relative pressure Note When welding the pipes do not let the flame burn the other components Tighten the screws of g...

Страница 141: ...he upper lower and front panels Loosen the wire clamp at the bottom of the electric box Unscrew the screws of electric box 2 Remove the electric box The connection wires inside and outside the electri...

Страница 142: ...welding the electronic expansion valve the valve should be wrapped with wet cloth Nitrogen welding the pressure of nitrogen is 0 5 0 1kgf c relative pressure Note When welding the pipes do not let th...

Страница 143: ...Work instruction 1 Remove the front panel Turn off the power supply of indoor unit Push the 4 corner plates in the directions shown by the arrows Loosen the screws and remove the front panel 2 Remove...

Страница 144: ...g band of motor Then remove the fan 5 Remove motor Use a screwdriver to unscrew the 4 screws of motor Then remove the motor 6 Replace and install the motor Remove the motor from motor support and then...

Страница 145: ...p of power cord Then tighten the screws with a screwdriver Removal and installation of drain pump Step Picture Work instruction 1 After removing the front panel as instructed above loosen the screws o...

Страница 146: ...and tighten the screws of water pump Connect the drain pipe and tighten the screws of water pump 8 Install the water tray and tighten the screws Direct the 4 corners of the water tray to the 4 corner...

Страница 147: ...n frame Use a hex wrench to loosen the screws of fan Order of removal air return plate air return frame longitudinal component cross beam 3 Remove the upper volute Loosen the screws of upper volute an...

Страница 148: ...Do not place the filter near any heat source Step Picture Work instruction Remove air return filter Press the air return filters on the guide way sponge There are 2 or 3 air return filters Removal of...

Страница 149: ...vaporator Note Make sure power is cut off Take good care of the copper pipe and aluminum fins If the removal takes a long time please put the copper pipe under pressure Step Picture Work instruction 1...

Страница 150: ...te Before removal make sure power is cut off During the removal procedure take good care of all the components Do not scratch the appearance components Step Picture Work instruction Remove the left an...

Страница 151: ...e of all the components Step Picture Work instruction Remove the water tray Remove the water tray Removal of evaporator Note Make sure power is cut off Take good care of the copper pipe and aluminum f...

Страница 152: ...e Then loosen the screws of the rear volute Lift up the retaining ring of the rear volute and take it off As shown in the picture the lines indicate the screws on both sides of the volutes 2 Remove th...

Страница 153: ...Open the front panel Hold the indents on both sides of the panel and pull it out in the direction shown by the arrow 3 Remove the electrical box cover 2 Unscrew the screws fixing the electrical box c...

Страница 154: ...ng the press plate of connection pipe on the back of the unit and take off the press plate Unscrew the screws of evaporator with a screwdriver and then remove the evaporator 9 Remove motor s pressing...

Страница 155: ...3 Axial Flow Fan 10333011 1 4 Fan Motor 1501308511 1 5 Base Plate Sub Assy 17000060107 1 6 Compressor and Fittings 9001060093 1 7 Electric Expand Valve Fitting 4300034401 1 8 Cut off Valve 71302395 1...

Страница 156: ...nser Assy 11002060290 1 25 Condenser Support Plate 1795028 1 26 Terminal Board 42200000000701 1 27 Terminal Board 42200000002402 1 28 Main Board 300027060151 1 29 Radiator 49013060 1 30 Coping 0120490...

Страница 157: ...15 Silencer 07245013 1 16 Silencer 1 07243050 1 17 4 way Valve 430004032 1 18 Rear Grill 01473060 1 19 Strainer 07225088 1 20 Electronic Expansion Valve 07133821 1 21 Strainer 0721302608 1 22 Clapboar...

Страница 158: ...Motor 1501506402 1 5 Drainage Joint 06123401 1 6 Drainage hole Cap 76713033 1 7 Drainage hole Cap 76713068 1 8 Drainage hole Cap 06813401 1 9 Base Plate Sub Assy 01205816 1 10 Compressor and Fittings...

Страница 159: ...ic Expand Valve Fitting 43000344 1 28 4 way Valve Assy 030152060086 1 29 Condenser Support Plate 01795031 1 30 Terminal Board 422000000007 1 31 Terminal Board 42200000002402 1 32 Main Board 3000270601...

Страница 160: ...305086 1 4 Axial Flow Fan 10335014 1 5 Fan Motor 15010400000102 1 6 Base Plate Sub Assy 0280319601 1 7 Drainage Joint 06123401 1 8 Drainage hole Cap 06813401 3 9 Compressor and Fittings 00900100019501...

Страница 161: ...cer1 07243050 1 27 Silencer 07245101 1 28 Condenser Support Plate 01175092 1 29 4 way Valve Assy 030152000329 1 30 Terminal Board 422000000007 1 31 Terminal Board 42200000002402 1 32 Main Board 300027...

Страница 162: ...007 1 5 Axial Flow Fan 1043410000801 1 6 Electric Heater Compressor 7651873215 1 7 Drainage hole Cap 76715005 3 8 Drainage Joint 26113009 1 9 Base Plate Sub Assy 017000060073 1 10 Filter Board 3000200...

Страница 163: ...ff Valve 071302391 1 29 Radiator 430034000048 1 30 Inductance 43128000014 1 31 Main Board 30221000024 1 32 Power Switch 300012060010 1 33 PFC Inductance 43120011 1 34 Coping 01264100052 1 35 Main Boar...

Страница 164: ...e Plate 012050000007 1 6 Handle 26904100016 2 7 Base Plate Sub Assy 01700006008901 1 8 Compressor and Fittings 009001060077 1 9 Electric Expand Valve Fitting 43000344 1 10 Gas liquid Separator 0742390...

Страница 165: ...0040045 1 28 Cut off Valve 071302391 1 29 Coping 01264100052 1 30 Electric Box Assy 100002061303 1 31 Radiator 49018000013 1 32 Main Board 300027060292 1 33 Inductance 4312800001401 1 34 Terminal Boar...

Страница 166: ...007 1 6 Connection Board 01344100070P 1 7 Axial Flow Fan 1043410000801 1 8 Fan Motor 150104060013 1 9 Motor Support Sub Assy 017012060039 1 10 Drainage hole Cap 76715005 1 11 Electrical Heater Compres...

Страница 167: ...agnet Coil 4300040045 1 30 Strainer 0721212101 1 31 Rear Grill 01574100014 1 32 Clapboard Sub Assy 017021060074 1 33 Condenser Assy 01100200031501 1 34 Electric Box Assy 100002061303 1 35 Filter Board...

Страница 168: ...6 1 6 Axial Flow Fan 1043410000801 1 7 Fan Motor 150104060013 1 8 Motor Support Sub Assy 01701206003901 1 9 Left Side Plate 012055000007 1 10 Base Plate Sub Assy 017000060073 1 11 Drainage Joint 26113...

Страница 169: ...enser Assy 011002060190 1 30 Drainage hole Cap 76715005 1 31 Electric Expand Valve Fitting 43000344 1 32 Electrical Heater Compressor 7651873215 1 33 4 way Valve Coil 4300040087 1 34 Temperature Senso...

Страница 170: ...late 012050000007 1 6 Handle 26904100016 1 7 Base Plate Sub Assy 01700006008901 1 8 Compressor and Fittings 009001060059 1 9 Electric Expand Valve Fitting 43000344 1 10 Gas liquid Separator 07423902 1...

Страница 171: ...alve Fitting 43000344 1 28 Cut off Valve 71302391 1 29 Coping 01264100052 1 30 Radiator 49018000087 1 31 Main Board 300027000644 1 32 Terminal board 42011147 1 33 Inductance 43128000014 1 34 Filter Bo...

Страница 172: ...007 1 6 Connection Board 01344100070 1 7 Axial Flow Fan 1043410000801 1 8 Fan Motor 150104060013 1 9 Motor Support Sub Assy 017012060039 1 10 Drainage Hole Cap 76715005 3 11 Electrical Heater Compress...

Страница 173: ...29 Magnet Coil 4300040045 1 30 Strainer 0721212101 1 31 Rear Grill 01574100014 1 32 Clapboard Sub Assy 017021060074 1 33 Condenser Assy 01100200031501 1 34 Electric Box Assy 100002061295 1 35 Filter...

Страница 174: ...Fan 1043410000301 1 5 Handle 26235253 1 6 Front Side Plate 01314100012 1 7 Brushless DC Motor 1570410001305 1 8 Brushless DC Motor 1570410001306 1 9 Electric Expand Valve Fitting 43000344 1 10 Electr...

Страница 175: ...501603 1 28 Electric Box Assy 100002062084 1 29 Inductance 43128000014 1 30 Filter Board 30223000044 1 31 Terminal Board 42011147 1 32 Terminal Board 422000000007 1 33 Main Board 300027060156 1 34 Ter...

Страница 176: ...rd 300002060465 1 4 Water Tray Assy 000069060065 1 5 Centifugal Fan 103003060008 1 6 Connection Sheet Sub Assy 017025060047 1 7 Water Level Switch 43002400000502 1 8 Water Pump 43138000058 1 9 Drain P...

Страница 177: ...e Loop 200150060003 1 23 Terminal Board 42018000551 1 GUD71T A T Product Code ET010N1420 GUD85T A T Product Code ET010N1430 No Material Name Finished Product Code Quantity 1 Electric Box Assy 10000206...

Страница 178: ...er 07213050 1 16 Support 01809400052 1 17 Brushless DC Motor 1570410000701 1 18 Water Pump 43138000058 1 19 Drainage Pipe Sub Assy 26909400055 1 20 Remote Controller 305001060024 1 21 Temperature Sens...

Страница 179: ...012078060022 3 10 Evaporator Assy 011001060201 1 11 Side Plate 1 01319400049 1 12 Side Plate 3 01319400051 2 13 Side Plate 2 01319400050 1 14 Seat Board Sub Assy 02229400011 1 15 Support 012060060787...

Страница 180: ...1001000225 1 7 Liquid Level Switch 4502021601 1 8 Side Plate 1 01319400025 1 9 Body Installing Plate 01332701 4 10 Side Plate 3 01319400036 2 11 Seat Board Sub Assy 02229400011 1 12 Seal Plate Assy 01...

Страница 181: ...ial Name Finished Product Code Quantity 1 Electric Box Assy 100002061280 1 2 Terminal Board 42018000551 1 3 Diversion Circle 10479400002 1 4 Water Tray Assy 000069060008 1 5 Centrifugal 10429400003 1...

Страница 182: ...9400001 1 23 Terminal board 42000100000202 1 24 Filter Board 30221000021 1 25 Main Board 300002060224 1 GUD160T A T Product Code ET010N1470 No Material Name Finished Product Code Quantity 1 Electric B...

Страница 183: ...0055 1 19 Evaporator Assy 011001060200 1 20 Remote Controller 305001060024 1 21 Temperature Sensor 39000286 1 22 Temperature Sensor 390000453 1 23 Filter Board 30221000021 1 24 Main Board 300002060224...

Страница 184: ...4 Bottom Cover Plate Assy 01264100102 1 15 Evaporator Assy 011001000473 1 16 Right Side Plate Assy 01315200053 1 17 Propeller Housing Lower 26905200019 18 Centrifugal Fan 10425200003 2 19 Propeller Ho...

Страница 185: ...te Assy 01264100103 1 13 Water Tray Assy 01285200022 1 14 Right Side Plate Assy 01315200053 1 15 Centrifugal Fan Assy 15404100032 1 16 Blower Mounting Plate Sub Assy 01325200035 1 17 Bearing Holder Su...

Страница 186: ...0223 1 4 Terminal Board 42018000551 1 5 Terminal Board 42011106 1 6 Electric Box Assy 100002002911 1 7 Left Side Plate Assy 01315200170 1 8 Strainer 0721200102 1 9 Air Outlet Frame Assy 000141000021 1...

Страница 187: ...Joint Slack 73018731 2 24 Rotary Axis Sub Assy 73018761 2 25 Centrifugal Fan Assy 000052060004 1 26 Filter Sub Assy 111253039 1 27 Temperature Sensor 390000597 1 28 Ambient Temperature Sensor 39000191...

Страница 188: ...1 14 Right Side Plate 012056060251 1 15 Volute Casing 200230060004 2 16 Centrifugal Fan 103003060003 2 17 Filter Sub Assy 111001060139 1 18 Brushless DC Motor 15704100001 1 19 Volute Casing 2002300600...

Страница 189: ...69 1 11 Brushless DC Motor 15705200016 1 12 Propeller Housing Upper 26905200078 2 13 Air Outlet Frame Assy 01375200026 1 14 Temperature Sensor 390001921 1 15 Ambient Temperature Sensor 3900012123 1 16...

Страница 190: ...455200003 3 5 Joint Slack 73018731 1 6 Propeller Housing Lower 26905200079 3 7 Propeller Housing Upper 26905200078 3 8 Bearing Holder Sub Assy 26151139 1 9 Support Of Motor Bearing 02285200001 1 10 Co...

Страница 191: ...lay Board 300001000204 1 26 Temperature Sensor 390001921 1 27 Temperature Sensor 3900012123 1 GUD160PH A T Product Code CF022N1530 No Material Name Finished Product Code Quantity 1 Main Board 30000206...

Страница 192: ...ropeller Housing Lower 26905200079 3 22 Brushless DC Motor 1570940000801 1 23 Joint Slack 73018731 1 24 Rotary Axis Sub Assy 73018000117 1 25 Centrifugal Fan 10455200003 3 26 Support Of Motor Bearing...

Страница 193: ...1 14 Air Outlet Frame Assy 01374100057 1 15 Cover Plate Air return 01265200057 1 16 Bottom Cover Plate Assy 01264100102 1 17 Evaporator Assy 011001000473 1 18 Right Side Plate Assy 01315200053 1 19 B...

Страница 194: ...001060229 1 14 Air Outlet Frame Assy 01374100058 1 15 Cover Of Air in 01265200073 1 16 Bottom Cover Plate Assy 01264100103 1 17 Water Tray Assy 01285200022 1 18 Right Side Plate Assy 01315200053 1 19...

Страница 195: ...02002911 1 7 Liquid Level Switch 430024000005 1 8 Left Side Plate Assy 000080000025 1 9 Strainer 0721200102 1 10 Water Pump 812007060016 1 11 Drainage Pipe Rubber 760022000001 1 12 Water Pump Assy 000...

Страница 196: ...9 Centrifugal Fan Assy 000052060004 1 30 Filter Sub Assy 111253039 1 31 Temperature Sensor 390000597 1 32 Ambient Temperature Sensor 39000191 1 33 Display Board 300001000204 1 GUD71PHS A T Product Cod...

Страница 197: ...849 1 15 Choke Plug of Drain Pipe 76815214 2 16 Water Tray 012122060338 1 17 Bottom Cover Plate 012147060060 1 18 Cover Of Air In 012104060001 1 19 Right Side Plate Sub Assy 012056060251 1 20 Volute C...

Страница 198: ...0016 1 11 Propeller Housing Upper 26905200078 2 12 Return Air Frame Sub Assy 017026000002 1 13 Filter Sub Assy 111001000045 2 14 Ambient Temperature Sensor 390001921 1 15 Temperature Sensor 3900012123...

Страница 199: ...porator Assy 011001060191 1 6 Right Side Plate Assy 01315200124 1 7 Centrifugal Fan Assy 000052060096 1 8 Blower Mounting Plate Sub Assy 01325200076 1 9 Propeller Housing Lower 26905200079 3 10 Centri...

Страница 200: ...00002060227 1 26 Filter Board 300020000017 1 27 Terminal Board 42000100000101 1 28 Terminal Board 42018000551 1 29 Left Side Plate Assy 01315200125 1 30 Water Pump Assy 000104060007 1 31 Pump Drainpip...

Страница 201: ...390001921 1 16 Ambient Temperature Sensor 3900012123 1 17 Display Board 300001000204 1 18 Rotary Axis Sub Assy 73018000117 1 19 Support Of Motor Bearing 02285200001 1 20 Bearing Holder Sub Assy 261511...

Страница 202: ...1809402 1 7 Axial Bush 10542704 2 8 Evaporator Assy 011001060235 1 9 Rotating Shaft 3 26909430 2 10 Guide Louver 200004000046 2 11 Crankshaft 200023000001 2 12 Stepping Motor 1521240215 2 13 Display B...

Страница 203: ...10582009 2 29 Air Louver 200007000001 10 30 Drainage Pipe Sub Assy 05235434 1 31 Supporter Guide Louver 26909400076 1 32 Water Tray 200063000024 1 33 Top Cover 012148000046 1 34 Front Grill Sub Assy...

Страница 204: ...30294000009 1 18 Base Plate Assy 011007000032 1 19 Crankshaft 200023000001 2 20 Stepping Motor 1521240215 2 21 Electric Box Assy 100002003030 1 22 Main Board 300002060226 1 23 Terminal Board 420180005...

Страница 205: ...1 1 5 Right Side Plate 26909400074 1 6 Installation Supporting Frame right 01809402 1 7 Axial Bush 10542704 2 8 Evaporator Assy 011001000202 1 9 Rotating Shaft 3 26909430 4 10 Guide Louver 20000450042...

Страница 206: ...0001 3 25 Centrifugal Fan 103003000001 3 26 Joint Slack 73018731 1 27 Brushless DC Motor 1570520000501 1 28 Roller Wheel 700004500433 1 29 Propeller Housing Upper 200230000002 3 30 Filter Sub Assy 111...

Страница 207: ...0063000003 1 6 Swing Lever 10582009 3 7 Air Louver 200007000001 15 8 Supporter 26909400076 2 9 Rotating Shaft 3 26909430 4 10 Right Side Plate 26909400071 1 11 Installation Supporting Frame Right 0180...

Страница 208: ...1 26 Support Of Motor Bearing 01792408 1 27 O Gasket of Bearing 76512404 1 28 Clapboard Assy 000075000040 1 29 Propeller Housing Lower 200230000001 3 30 Rotary Axis 700004500433 1 31 Filter Sub Assy...

Страница 209: ...1809402 1 7 Axial Bush 10542704 2 8 Evaporator Assy 011001060178 1 9 Rotating Shaft 3 26909430 6 10 Guide Louver 200004500426 2 11 Crankshaft 200023000001 2 12 Stepping Motor 1521240206 2 13 Display B...

Страница 210: ...2 4 30 Rear Side Plate Sub Assy 017051000006 1 31 Filter Sub Assy 111001000001 3 32 Drainage Pipe Sub Assy 05235434 1 33 Swing Lever 10582009 4 34 Air Louver 200007000001 20 35 Supporter Guide Louver...

Страница 211: ...g Frame Left 01809401 1 18 Main Board 300002060226 1 19 Terminal Board 42018000551 1 20 Terminal Board 42000100000202 1 21 Electric Box Assy 100002003030 1 22 Support Of Motor Bearing 01792408 2 23 O...

Страница 212: ...0703 2 4 Front Case Assy 00000200043 1 5 Evaporator Assy 011001061587 1 6 Cross Flow Fan 10352057 1 7 Axile Bush 10542036 2 8 Helicoid Tongue 26112513 1 9 Air Louver 1 10512741 2 10 Drainage Hose 0523...

Страница 213: ...Temperature Sensor 390000592 1 25 Temperature Sensor 390000456 1 26 Fan Bearing 7651221001 1 27 O Gasket of Cross Fan Bearing 76512203 1 28 Ring of Bearing 26152025 1 29 Left Axile Bush 10512037 1 30...

Страница 214: ...Holder 76712017 1 15 Brushless DC Motor 1501213401 1 16 Electric Box Assy 100002070914 1 17 Display Board 30565277 1 18 Terminal Board 42010268 1 19 Main Board 300002061478 1 20 Rear Case 2220215102 1...

Страница 215: ...11 87 35 0 484 80 1 871 2 934 10 82 75 0 506 81 1 811 2 945 9 78 43 0 53 82 1 754 2 955 8 74 35 0 554 83 1 699 2 964 7 70 5 0 579 84 1 645 2 974 6 66 88 0 605 85 1 594 2 983 5 63 46 0 631 86 1 544 2 9...

Страница 216: ...863 122 0 547 3 184 32 11 09 1 897 123 0 532 3 187 33 10 63 1 931 124 0 519 3 19 34 10 2 1 964 125 0 505 3 192 35 9 779 1 998 126 0 492 3 195 36 9 382 2 03 127 0 48 3 198 37 9 003 2 062 128 0 467 3 2...

Страница 217: ...k Voltage V 30 361 8 0 173 66 3 998 2 75 29 339 8 0 183 67 3 861 2 766 28 319 2 0 195 68 3 729 2 781 27 300 0 206 69 3 603 2 796 26 282 2 0 218 70 3 481 2 811 25 265 5 0 231 71 3 364 2 825 24 249 9 0...

Страница 218: ...3 145 16 30 04 1 319 112 0 9556 3 15 17 28 68 1 356 113 0 9295 3 153 18 27 39 1 393 114 0 9043 3 157 19 26 17 1 429 115 0 8799 3 161 20 25 01 1 466 116 0 8562 3 165 21 23 9 1 503 117 0 8333 3 168 22 2...

Страница 219: ...47 60 4 948 2 646 156 0 3164 3 249 61 4 773 2 664 157 0 3093 3 25 62 4 605 2 682 158 0 3024 3 251 63 4 443 2 7 159 0 2956 3 252 64 4 289 2 717 160 0 2891 3 253 65 4 14 2 734 1 3 Voltage List of 50 K D...

Страница 220: ...64 4 131 5 0 233 95 3 841 2 384 5 126 17 0 242 96 3 7283 2 404 6 119 08 0 256 97 3 6194 2 423 7 113 37 0 267 98 3 5143 2 442 8 107 96 0 28 99 3 4128 2 46 9 102 85 0 292 100 3 3147 2 478 10 98 006 0 30...

Страница 221: ...2 882 41 25 114 0 94 132 1 4141 2 891 42 24 128 0 967 133 1 3803 2 9 43 23 186 0 994 134 1 3474 2 908 44 22 286 1 022 135 1 3155 2 916 45 21 425 1 05 136 1 2846 2 924 46 20 601 1 078 137 1 2545 2 932...

Страница 222: ...95 3200 50 806 950 4 9506 2100 33 341 3250 51 482 1000 6 624 2150 34 271 3300 52 15 1050 8 2352 2200 35 184 3350 52 811 1100 9 7896 2250 36 082 3400 53 464 1150 11 291 2300 36 965 3450 54 11 1200 12 7...

Страница 223: ...10 2 4 0 15 3 4 0 137 4 2 11 3 4 2 16 8 4 2 151 4 4 12 4 4 4 18 5 4 4 166 4 6 13 5 4 6 20 2 4 6 182 4 8 14 7 4 8 22 0 4 8 198 5 0 16 0 5 0 23 8 5 0 215 5 2 17 3 5 2 25 8 5 2 232 5 4 18 6 5 4 27 8 5 4...

Страница 224: ...JF00303775...

Отзывы: