38
6
UNIT CAPACITY CORRECTION
6.1 Correction of Capacity Along with Ambient Temperature and Configuration Ratio
GMV-Q***WM/B-F(U) Cooling Capacity Correction Table for GMV5 HR VRF Unit
GMV-Q72WM/B-F(U)
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
Combination
Outdoor
air temp
(℉
DB
)
Indoor air temp
57.2
℉
WB
60.8
℉
WB
64.4
℉
WB
66.2
℉
WB
68
℉
WB
71.6
℉
WB
75.2
℉
WB
68
℉
DB
73.4
℉
DB
78.8
℉
DB
80.6
℉
DB
82.4
℉
DB
86
℉
DB
89.6
℉
DB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
130%
50
63.3
2.51
75.3
3.07
87.4
3.65
90.8
3.73
91.8
3.66
94.1
3.51
96.4
3.34
53.6
63.3
2.56
75.3
3.13
87.4
3.73
89.5
3.71
90.8
3.64
92.8
3.48
95.1
3.43
57.2
63.3
2.61
75.3
3.19
87.2
3.77
88.5
3.70
89.5
3.62
91.8
3.59
94.1
3.62
60.8
63.3
2.65
75.3
3.26
86.1
3.76
87.2
3.73
88.2
3.74
90.5
3.78
92.8
3.81
64.4
63.3
2.70
75.3
3.32
84.9
3.90
85.9
3.92
87.2
3.94
89.5
3.98
91.8
4.01
68
63.3
2.76
75.3
3.54
83.6
4.09
84.9
4.11
85.9
4.13
88.2
4.17
90.5
4.21
69.8
63.3
2.84
75.3
3.66
83.1
4.18
84.3
4.20
85.4
4.23
87.7
4.27
90.0
4.31
73.4
63.3
3.04
75.3
3.92
82.0
4.37
83.1
4.40
84.1
4.42
86.4
4.46
88.7
4.51
77
63.3
3.25
75.3
4.20
80.7
4.56
82.0
4.59
83.1
4.62
85.4
4.66
87.7
4.70
80.6
63.3
3.47
75.3
4.50
79.7
4.02
80.7
4.78
81.8
4.81
84.1
4.86
86.4
4.91
84.2
63.3
3.70
75.3
4.81
78.4
4.95
79.5
4.98
80.7
5.01
83.1
5.06
85.4
5.11
87.8
63.3
3.95
75.1
5.09
77.1
5.15
78.4
0.76
79.5
5.20
81.8
5.26
84.1
5.31
91.4
63.3
4.21
73.8
5.28
76.1
5.33
77.1
5.37
78.4
5.39
80.7
5.45
82.8
5.52
95
63.3
4.49
72.5
5.47
74.8
5.53
76.1
5.56
77.1
5.59
79.5
5.66
81.8
5.72
98.6
63.3
4.78
71.5
5.67
73.8
5.73
74.8
5.76
76.1
5.80
78.2
5.87
80.5
5.93
102.2
63.3
5.09
70.2
5.86
72.5
5.92
73.8
5.96
74.8
6.00
77.1
6.06
79.5
6.14
Combination
Outdoor
air temp
(℉
DB
)
Indoor air temp
57.2
℉
WB
60.8
℉
WB
64.4
℉
WB
66.2
℉
WB
68
℉
WB
71.6
℉
WB
75.2
℉
WB
68
℉
DB
73.4
℉
DB
78.8
℉
DB
80.6
℉
DB
82.4
℉
DB
86
℉
DB
89.6
℉
DB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
120%
50
58.4
2.29
69.4
2.80
80.7
3.33
86.4
3.60
90.5
3.76
92.6
3.61
94.6
3.47
53.6
58.4
2.34
69.4
2.85
80.7
3.40
86.4
3.67
89.2
3.73
91.3
3.59
93.3
3.45
57.2
58.4
2.38
69.4
2.91
80.7
3.46
86.4
3.74
87.9
3.71
90.3
3.57
92.3
3.59
60.8
58.4
2.43
69.4
2.97
80.7
3.53
85.9
3.77
86.9
3.72
89.0
3.76
91.0
3.79
64.4
58.4
2.47
69.4
3.03
80.7
3.65
84.6
3.90
85.6
3.91
87.7
3.95
90.0
3.98
68
58.4
2.52
69.4
3.15
80.7
3.92
83.6
4.09
84.6
4.10
86.7
4.14
88.7
4.17
69.8
58.4
2.54
69.4
3.26
80.7
4.06
82.8
4.18
83.8
4.20
86.1
4.23
88.2
4.28
73.4
58.4
2.72
69.4
3.49
80.7
4.35
81.8
4.37
82.8
4.39
84.9
4.43
86.9
4.47
77
58.4
2.90
69.4
3.73
79.5
4.54
80.5
4.56
81.5
4.58
83.8
4.62
85.9
4.67
80.6
58.4
3.10
69.4
3.99
78.4
4.73
79.5
4.76
80.5
4.78
82.5
4.82
84.6
4.87
84.2
58.4
3.31
69.4
4.26
77.1
4.92
78.2
4.95
79.2
4.97
81.3
5.02
83.6
5.06
87.8
58.4
3.53
69.4
4.55
76.1
5.12
77.1
5.14
78.2
5.17
80.2
5.22
82.3
5.27
91.4
58.4
3.76
69.4
4.86
74.8
5.31
75.9
5.34
76.9
5.36
78.9
5.42
81.0
5.47
95
58.4
4.00
69.4
5.17
73.5
5.50
74.6
5.53
75.9
5.56
77.9
5.62
80.0
5.67
98.6
58.4
4.26
69.4
5.51
72.5
5.70
73.5
5.73
74.6
5.76
76.6
5.81
78.7
5.88
102.2
58.4
4.53
69.2
5.82
71.2
5.89
72.3
5.92
73.3
5.95
75.6
6.02
77.7
6.08