8
Outdoor Units_Heat Recovery
Ton
12
14
Model
-
GMV-Q144WM/B1-F(U)
GMV-Q168WM/B1-F(U)
Module combination
-
GMV-Q144WM/B1-F(U)
GMV-Q168WM/B1-F(U)
Performance
Nominal Cooling Capacity
①
Btu/h
144000
168000
kW
42.20
49.24
Rated Cooling Capacity
Btu/h
136000
150000
Nominal Heating Capacity
Btu/h
162000
189000
kW
47.48
55.39
Rated Heating Capacity
Btu/h
150000
180000
Cooling Power Input
kW
12.93
14.52
Heating Power Input
kW
12.80
16.43
Sound Pressure Level
dB(A)
64
65
Power Supply
-
208/230V 3~ 60Hz
Compressor
Type
-
Inverter scroll type
Inverter scroll type
Number
N
2
2
Motor Output
②
kW
7.15+7.15
7.15+7.15
Starting Method
-
Inverter
Inverter
Operating Range
-
11%~100%
10%~100%
Refrigeration Oil Brand
-
FVC68D or FV-68H
FVC68D or FV-68H
Oil Charge
③
Compressor
L
1.1+1.1
1.1+1.1
Oil separate tank
L
5
5
Total
L
7.2
7.2
Fan
Type×Quantity
-
Propeller×2
Propeller×2
Motor output
W
750+750
750+750
Starting method
-
Inverter
Inverter
Air flow rate
m
3
/h
14000
16000
cfm
8240
9417
Max. external static pressure
Pa
82
82
in.W.G
0.328
0.328
Ambient
temperature
range
Cooling
°C
-5~52
-5~52
℉
23~125.6
23~125.6
Heating
°C
-20~24
-20~24
℉
-4~75.2
-4~75.2
Refrigerant
Refrigerant Type
-
R410A
R410A
Refrigerant Charge Volume
kg
11.7
11.7
lbs.
25.79
25.79
Control
-
EXV
EXV