Super Free Match Series
9
6
Installation of Refrigerant Pipes
6.1 Allowable Length and Drop Height of Connecting Pipe
Fig. 8 (8 indoor units)
Table 3
The sorts
The pipes
Length
˄
m
˅
Total length between outdoor unit and
BU modules
L1+L2+L3+L4+L5
55
MULTI48HP230V1AO
80
Total length
between indoor
units and BU
MULTI56HP230V1AO
1A+1B+1C+2A+2B+2C+
3A+3B
90
Between indoor unit and BU module
1A;1B;1C;2A;2B;2C;3A;3B
15
Maximum
allowable
length
Between indoor unit and the 1st branch
L4+1B;L2+L5+2A;
L2+L3+3B
40
Between outdoor and indoor units
H1
30
Between outdoor units and BU modules
H2
30
Between BU and BU modules
H3
15
Maximum
allowable
length
Between indoor and indoor units
H4
15
Between outdoor and the 1st branch
L1
5
Minimum
allowable
length
Between BU and the branch
L3;L4;L5
as possible
as short
BU module should be placed within the level between the outdoor unit and indoor unit.
Содержание MULTI48HP230V1AO
Страница 2: ......
Страница 4: ......
Страница 35: ......
Страница 36: ... 5 75 33 1 6 1 2 8 GG HVW LQML 5G 4LDQVKDQ KXKDL XDQJGRQJ KLQD 7HO D PDLO JUHH JUHH FRP FQ ZZZ JUHH FRP ...