![Gree MG30-24/D1(B) Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/gree/mg30-24-d1-b/mg30-24-d1-b_installation-and-operation-manual_2260747049.webp)
BACnet Gateway Kit for Central Air Conditioners
33
Object type: Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the mode setting of the indoor unit.
Present_Value:
1- Cool,
2- Dehumidify,
3- Fan,
4- Heat;
Note :
1) The indoor unit running mode takes effective only when the unit is turned on.
2) For the cooling only unit, the “HEAT” parameter takes ineffective.
3) It is required to judge if the setting parameter sent by the BMS is within the effective range.
(7) On/Off(status)
Member number:6
Object name:OnOffStatus_XX_YYY_ZZ (XX means Air condition type,like GMV is 01;YYY
means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor Units's
number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: It is used to monitor the on/off status of the indoor unit.
Present_Value:
ACTIVE:On
INACTIVE:Off
Note :
1) When the unit runs normally, Present_Value wil reflect the real-time on/off status of the unit.
(8) On/Off(setting)
Member number:7
Object name:OnOffCommand_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Binary Output
Object ID: BO(4)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the on/off setting of the unit.
Present_Value:
ACTIVE:On
INACTIVE:Off
Notes:
1) Relinquish default is INACTIVE.
2) In the event that the Present-Value of “Indoor unit mode (status)” is “0”, it will be defaulted to
Содержание MG30-24/D1(B)
Страница 5: ...中央空调 BACnet 网关套件安装使用说明书 3 ...
Страница 33: ...BACnet Gateway Kit for Central Air Conditioners 17 4 5 6 ...