BACnet Gateway Kit for Central Air Conditioners
29
24
Water tank mode(setting)
WaterTankModeCommand_XX_
YYY_ZZ
MV(19)+YYY*8192+ZZ*64+2
MV
25
Double-Tube supply Water
Temp
DoubleTubeSupplyWaterTemp_XX_
YYY_ZZ
AI(0)+YYY*8192+ZZ*64+2
AI
26
Floor Heating supply
Water Setting Temp.
F l o o r H e a t i n g S u p p l y W a t e r
SettingTemp_XX_YYY_ZZ
AV(2)+YYY*8192+ZZ*64+2
AV
27
Disinfecting
Disinfecting_XX_YYY_ZZ
BI(3)+YYY*8192+ZZ*64+2
BI
28
Floor heat power
FloorHeatPower_XX_YYY_ZZ
BI(3)+YYY*8192+ZZ*64+3
BI
29
W a t e r t a n k c o n t r o l
shielding code(setting)
WaterTankControlShieldingCodeCom
mand_XX_YYY_ZZ
MV(19)+YYY*8192+ZZ*64+3
MV
Parameters of GMV Outdoor Units
30
Outdoor unit general error
mark
OutdoorUnitErrorMark_XX_YYY_ZZ
BI(3)+YYY*8192+ZZ*64+4
BI
31
Outdoor unit error code
OutdoorUnitErrorCode_XX_YYY_ZZ
MI(13)+YYY*8192+ZZ*64+4
MI
32
O u t d o o r e n v i r o n m e n t
temp
OutdoorEnvironmentTemp_XX_YYY_
ZZ
AI(0)+YYY*8192+ZZ*64+3
AI
33
C o m p l e t e m a c h i n e
compressor state
CompleteMachineCompressorState_
XX_YYY_ZZ
BI(3)+YYY*8192+ZZ*64+5
BI
Table 3.2.2
Parameter
number
Instance Number
Present_Value
Units
Min_
Pres_
Value
Max_
Pres_
Value
Resolution
Parameters of GMV Indoor Units
1
YYY*8192+ZZ*64+1
0:without, 1:with
2
YYY*8192+ZZ*64+1
see Alarm codes
3
YYY*8192+ZZ*64+1
-20~100
-20
100
1
4
YYY*8192+ZZ*64+1
16~30
5
YYY*8192+ZZ*64+2
1- Cool, 2- Dehumidify,3- Fan,4-
Heat; Others-0 means nothing, used
insignificance symbol to express, like
"--";
6
YYY*8192+ZZ*64+1
1- Cool,2- Dehumidify,3- Fan,4-
Heat;Others:0 means nothing, used
insignificance symbol to express, like
"--";
7
YYY*8192+ZZ*64+2
0:Off,1:On
8
YYY*8192+ZZ*64+1
0:Off,1:On
9
YYY*8192+ZZ*64+3
0- Auto fan speed,1- Low fan
speed,2- Middle fan speed,3- High
fan speed;
10
YYY*8192+ZZ*64+2
1- Low fan speed,2- Middle fan
speed,3- High fan speed;
11
YYY*8192+ZZ*64+1
0:Off,1:On