5
D Series Modular Air-cooled Scroll Chillers
Service Manual
QSPEVDU
1RPLQDOFDSDFLWLHVDUHEDVHGRQWKHIROORZFRQGLWLRQV
Item
Water side
Air side
:DWHUÀRZYROXPH
Leaving Water Temperature
Dry-bull temp.
Wet-bull temp.
m
3
/(h·kw)
(
ć
/
̧
)
(
ć
/
̧
)
(
ć
/
̧
)
Cooling
0.172
7/45
35/95
—
Heating
45/113
7/45
6/43
4.3 Operation Range
Water side
Air side
Leaving Water Temperature
Temperature Difference of Water
Air on Condenser
(
ć
/
̧
)
(
ć
/
̧
)
(
ć
/
̧
)
Cooling
5~15/41~59
2.5~6/37~43
15~45/59~113
Heating
40~50/104~122
2.5~6/37~43
-15~24/5~75
Note: when the unit is going to operate beyond the working conditions, please contact Gree for consultation.
4.4 Electric Data
Model
Rated Power Supply
Compressor
Fan Motor
Air Switch
Qty
MRC Each
(A)
NRC Each
(A)
Qty.
NRC Each
(A)
MRC
(A)
LSQWRF65M/NaD-M
380-415V
,
3Ph,50Hz
2
29.1
17.6
2
1.71
63
LSQWRF80M/NaD-M
2
29.3
25.7
2
2.50
80
LSQWRF130M/NaD-M
4
29.1
17.6
4
1.71
125
LSQWRF160M/NaD-M
4
35
25.7
4
2.50
160
Notes:
05&0D[LPXPUXQQLQJFXUUHQW$
NRC: Nominal running current (A).