45
Installation and Maintenance
Service Manual
4) Make sure the system has no leakage. When compressor is not working, fill a set amount of R410a refrigerant into the unit
through outdoor unit’s liquid valve. If the inner tube pressure rises and the set amount of refrigerant can’t be filled inside quickly,
you can turn on the unit to make it start cooling, then fill the refrigerant inside through outdoor unit’s gas valve.
a.
Calculation of the Additional Refrigerant Charging
1) Refrigerant Charge in the Outdoor Unit before Shipment
Table 6
Model
GWHD(42NK3AO
Refrigerant Charge (kg)
GWHD(36)NK3BO
4.2
4.8
Notes
˖
ķ
The refrigerant charge mentioned in the table above is not included those charged additionally in the indoor unit and the
refrigerant pipe.
ĸ
The amount of the additional refrigerant charge is dependent on the diameter and length of the liquid refrigerant pipe
which is decided by the actual yield installation requirement.
Ĺ
Record the additional refrigerant charge for future maintenance.
2) Calculation of the Additional Refrigerant Charge
If the total refrigerant pipe length (liquid pipe) is smaller than that listed in the table below, no additional refrigerant will be
charged.
Table 7
Model
Total Liquid Pipe Length (a+b+c+d+e)
GWHD(36)NK3BO
≤40m
GWHD(42)NK3AO
≤50m
Additional Refrigerant Charge2=∑Extra Liquid Pipe Length×22g/m(liquid pipe 1/4").
Note: if the total refrigerant pipe length is larger than that listed in the table above, the additional refrigerant for the extra
length of the pipe needs to be charged as per 22g/m.
3) Example : GWHD (42) NK3AO
Fig.9
Table 8 Indoor Unit
Serial No.
Model
Indoor Unit
Ļ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit
ĺ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit
Ĺ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit
ĸ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit
Ducted Type GFH(18)EA-K3DNA1A/I
Table 9 Liquid Refrigerant Pipe
Serial No.
e
d
c
b
a
Diameter
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Φ9.52
Length
20m
20m
15m
5m
5m
The total length of each liquid refrigerant pipe is: e+d+c+b+a=20+20+15+5+5=65m. Thus, the minimum additional
refrigerant charge=(65-50)×0.022=0.33kg (Note: no additional refrigerant is needed for the liquid pipe within 50m).
a
b
c
d
e
Содержание GWHD(28)NK3FO
Страница 77: ...75 Installation and Maintenance Service Manual 10 Exploded View and Parts List 1 Model GWHD 18 NK3FO...
Страница 79: ...77 Installation and Maintenance Service Manual 2 Model GWHD 24 NK3FO...
Страница 81: ...79 Installation and Maintenance Service Manual 3 Model GWHD 24 NK3GO...
Страница 83: ...81 Installation and Maintenance Service Manual 4 Model GWHD 28 NK3FO...