11. Removal Procedure
Warning: Be sure to wait for a minimum of 20 minutes after turning off all
power supplies and discharge the refrigerant completely before removal.
(1)Model:GWHD(18)NK3FO
Steps
Procedure
1. Before disassembly
Complete axonometric drawing.
2. Remove valve cover
Remove the connection screw fixing the valve
cover and then remove the valve cover.
3. Remove Coping
Remove the connection screws connecting the
top panel with the right side plate and the left
side plate, and then remove the Coping
.
Coping
valve cover