101
Installation and Maintenance
Service Manual
F:Inspection
Ɣ&KHFNWKHTXDOLW\RIH[SDQGLQJSRUW,IWKHUHLVDQ\EOHPLVKH[SDQGWKH
port again according to the steps above.
The length is equal
Improper expanding
leaning
damaged
surface
crack
uneven
thickness
Smooth surface
Downwards
Pipe
Shaper
Union pipe
Pipe
Expander
Hard
mold
Pipe
Pipe
Pipe cutter
Leaning
Uneven
Burr
Improper pipe expanding is the main cause of refrigerant leakage.Please
expand the pipe according to the following steps:
A:Cut the pip
Ɣ&RQ¿UPWKHSLSHOHQJWKDFFRUGLQJWRWKHGLVWDQFHRILQGRRUXQLWDQGRXWGRRUXQLW
Ɣ&XWWKHUHTXLUHGSLSHZLWKSLSHFXWWHU
B:Remove the burrs
Ɣ5HPRYHWKHEXUUVZLWKVKDSHUDQGSUHYHQWWKHEXUUVIURPJHWWLQJLQWRWKHSLSH
C:Put on suitable insulating pipe
D:Put on the union nut
Ɣ5HPRYHWKHXQLRQQXWRQWKHLQGRRUFRQQHFWLRQSLSHDQGRXWGRRUYDOYHLQVWDOO
the union nut on the pipe.
E:Expand the port
Ɣ([SDQGWKHSRUWZLWKH[SDQGHU
Ɣ$LVGLIIHUHQWDFFRUGLQJWRWKHGLDPHWHUSOHDVHUHIHUWRWKHVKHHWEHORZ
Outer diameter(mm)
A(mm)
Max
Min
Ɏ
1.3
0.7
Ɏ´
1.6
1.0
Ɏ´
1.8
1.0
Ɏ´
2.4
2.2
Appendix 3: Pipe Expanding Method
Note:
Note:
Содержание GWH18RC-K3DNA2C
Страница 66: ...63 Installation and Maintenance Service Manual 2 Models GWH18RC K3DNA8C I GWH18RC K3DNA6C I...
Страница 74: ...71 Installation and Maintenance Service Manual 10 2 Outdoor Unit 1 Model GWH18RC K3DNA3C O...
Страница 76: ...73 Installation and Maintenance Service Manual 2 Model GWH18RC K3DNA8C O...
Страница 78: ...75 Installation and Maintenance Service Manual 3 Model GWH24RD K3DNA3C O...
Страница 80: ...77 Installation and Maintenance Service Manual 4 Model GWH24RD K3DNA8C O...