53
Installation and Maintenance
Service Manual
(4) Start-up failure (following AP1 for outdoor unit control board)
Mainly detect:
Ɣ:KHWKHUWKHFRPSUHVVRUZLULQJLVFRQQHFWHGFRUUHFW"
Ɣ,VFRPSUHVVRUEURNHQ"
Ɣ,VWLPHIRUFRPSUHVVRUVWRSSLQJHQRXJK"
)DXOWGLDJQRVLVSURFHVV
Y
N
Y
N
N
Y
Y
N
Power on the unit
Is stop time of the compressor
longer than 3 minutes?
Restart it up after
3 minutes
Does startup fail?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Connect the wires as
per the connection
diagram
Replace the control panel AP1
If the fault is eliminated?
Replace the
compressor
End
Содержание GWH09QB-K3DNA1D
Страница 47: ...44 Installation and Maintenance Service Manual...