66
Installation and Maintenance
Service Manual
NO.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of
display status and during
blinking, ON 0.5s and OFF
0.5s
Operation
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
43
Malfunction of
phase current
detection
circuit for
compressor
U1
During cooling and drying
operation, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Replace outdoor control panel AP1
44
Malfunction of
voltage
dropping for
DC bus-bar
U3
During cooling and drying
operation, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Supply voltage is unstable
45
Malfunction
of complete
units current
detection
U5
During cooling and drying
operation, the compressor will
stop while indoor fan will
operate;
During heating operating,
the complete unit will stop
operation.
Theres circuit malfunction on
outdoor units control panel AP1,
please replace the outdoor units
control panel AP1.
46
The four-way
valve is
abnormal
U7
If this malfunction occurs
during heating operation,
the complete unit will stop
operation.
1.Supply voltage is lower than
AC175V;
2.Wiring terminal 4V is loosened or
broken;
3.4V is damaged, please replace
4V.
47
Frequency
limiting
(power)
OFF 3S
and blink
13 times
48
Compressor
is open-
circuited
OFF 3S
and blink
once
49
The
temperature
for turning
on the unit is
reached
OFF 3S
and blink
8 times
50
Frequency
limiting
(module
temperature)
OFF 3S
and blink
11 times
51
Malfunction
of detecting
plate(WIFI)
JF