9.4 How to
simply c
heck the main part
(1) Malfunction of power supply from indoor unit to outdoor unit
Main inspection point:
Inspect the power supply plug seat with AC voltage gauge to check if the voltage between L and N is within 200VAC~240VAC;
Check with AC voltage gauge if the voltage between N 1and 3 of indoor wiring block is within 200VAC~240VAC;
Flow chart of Malfunction diagnosis
Y
Y
N
N
Y
N
Energize the unit
and wait for 3min
Measure voltage between
N 1and 3 of indoor
wiring block
Voltage > 200V?
Measure voltage
between L and N
of outdoor wiring
block
Normal wiring?
Voltage > 200V?
Indoor main board error
Adjust wiring
Outdoor electric
box error
indoor and outdoor
wiring error
Replace main board
of indoor unit
Replace outdoor
electric box
Replace indoor
and outdoor wiring
Remove malfunction
(2) Indoor fan does not rotate
and there is no
feedback
Main detection point:
z
z
Malfunction diagnosis process:
Is the control panel reliably connected with the motor? Is it loose? Is the connecting sequence correct?
Is the input voltage within the normal range (measure the voltage between L and N of the wiring block XT with AC voltage
gauge.)?
Содержание GWC09KF-K3DNA5A
Страница 22: ...19 Schematic Diagram null line live wire communication wire ground wire dispaly board infrared receiver...
Страница 24: ...21 FRONT VIEW BOTTOM VIEW Schematic Diagram...
Страница 25: ...22 TOP VIEW Schematic Diagram BOTTOM VIEW...
Страница 48: ...45 Exploded Views and Parts list 8 2 Outdoor Unit 1 Cooling Only Models Round grill...
Страница 50: ...47 Exploded Views and Parts list Square grill...
Страница 52: ...49 2 Cooling Heating Models Exploded Views and Parts list Exploded Views and Parts list Round grill...
Страница 54: ...51 Square grill...
Страница 82: ...79 Removal Procedure 13 Remove Motor Sub Assy 14 Remove Fan Motor Remove Motor Sub Assy 1...