DC Inverter U-match Series Duct Type Unit
66
disperse any released refrigerant and preferably expel it externally into the
atmosphere.
5.4.1.8 Checks to the Refrigeration Equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt consult the
manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable
refrigerants:
(1) The charge size is in accordance with the room size within which the
refrigerant containing parts are installed.
(2) The ventilation machinery and outlets are operating adequately and are
not obstructed.
(3) If an indirect refrigerating circuit is being used, the secondary circuit shall
be checked for the presence of refrigerant.
(4) Marking to the equipment continues to be visible and legible. Markings
and signs that are illegible shall be corrected.
(5) Refrigeration pipe or components are installed in a position where they
are unlikely to be exposed to any substance which may corrode
refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded
or are suitably protected against being so corroded.
5.4.1.9 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the circuit until it
is satisfactorily dealt with. If the fault cannot be corrected immediately but it is
necessary to continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
(1) That capacitors are discharged: this shall be done in a safe manner to
avoid possibility of sparking.