MAINTENANCE
1 TROUBLE SHOOTING
1�1 Error Display of Indoor Unit
Error
Code
Error
Source of
error signal
Control description
E1
Compressor
high pressure
protection
High pressure
switch
The high pressure protection value is 4.2MPa. When high pressure of a
compressor is detected for successive three times, the compressor will
stop. Error code E1 will be diaplayed and the running LED will blink.
E2
Indoor
antifreezing
protection
Temperature
sensor of
evaporator
When Tevaporator -2 lasts for 10min, the antifreezing protection will occur.
The indoor electronic expansion valve will be closed and the capacity is 0.
E3
Compressor
low pressure
protection
Low pressure
switch
When the low pressure protection value (0.15Mpa, absolute
pressure) is reached, the low pressure switch will be disconnected.
The low pressure protection will be displayed.
E4
Compressor
discharge
temperature
protection
Discharge
temperature
sensor
When discharge temperature T is 113 or higher, the stop protection will
occur. E4 is displayed upon the irst discharge protection. After discharge
temperature is lower than TR and the unit stops for 3min, the compressor
will resume running. If this occurs for three times in one hour, the compressor
can not resume running. It is a must to cut off the power and restart the unit.
E5
Conversion
overcurrent
protection
Compressor
driver
The driving board of conversion compressor is wrong. Refer to the
error code of outdoor nixie tube for speciic error information.
E6
Communication
Error
Communication
There is communication error between the mainboard of indoor unit or wired
controller and the outdoor unit. The wrong indoor unit will stop and display error code.
E7
Mode conlict
User operation
The running modes of the unit running irst and that of later are variant.
There is mode conlict among cooling, defrosting and heating mode. There
is no mode conlict among fan, cooling, defrosting and heating mode.
When mode conlict occurs, the indoor unit will display E7 and stop.
E9
Water full
protection
Water pump
When the water is full for successive 8s, the water full protection
will occur. The wired controller will display E9 and alarm will occur.
In that case, the water pump will work while the other load of indoor
unit will stop. The outdoor unit needs to adjust capacity output.
F0
Ambient
temperature
sensor error
of indoor unit
Ambient
temperature
sensor of
indoor unit
The indoor unit of temperature sensor error displays the error code and stop.
F1
Indoor coil pipe
inlet temperature
sensor error
Indoor coil pipe
inlet temperature
sensor
The indoor unit of temperature sensor error displays the error code and stop.
F2
Indoor coil
pipe middle
temperature
sensor error
Indoor coil
pipe middle
temperature
sensor
The indoor unit of temperature sensor error displays the error code and stop.
F3
Indoor coil
pipe outlet
temperature
sensor error
Indoor coil
pipe outlet
temperature
sensor
The indoor unit of temperature sensor error displays the error code and stop.
F4
Outdoor ambient
temperature
sensor error
Outdoor ambient
temperature
sensor
If short circuit occurs to the temperature sensor, there will be alarm..
The error information will be transmitted to each indoor unit, The error
LED or wired controller will display the error code. When outdoor
ambient temperature is lower than -5 , the break circuit of outdoor
temperature sensor will be shielded. It is treated according to -30 .
F7
Outdoor
defrosting
temperature
sensor error
Outdoor
defrosting
temperature
sensor
If short circuit occurs to the temperature sensor, there will be alarm..
The error information will be transmitted to each indoor unit, The error
LED or wired controller will display the error code. When outdoor
ambient temperature is lower than -5 , the break circuit of outdoor
temperature sensor will be shielded. It is treated according to -30 .
F9
Discharge
temperature
sensor error
Discharge
temperature
sensor
If short circuit occurs to the temperature sensor, there will be alarm..
The error information will be transmitted to each indoor unit, The error
LED or wired controller will display the error code. When outdoor
ambient temperature is lower than -5 , the break circuit of outdoor
temperature sensor will be shielded. It is treated according to -30 .
Содержание GMV-R series
Страница 1: ...T1 R410A 50Hz GC201110 I...
Страница 4: ...Multi VRF Indoor Unit Service Manual 1 PRODUCT PRODUCT...
Страница 40: ...Multi VRF Indoor Unit Service Manual 37 CONTROL CONTROL...
Страница 42: ...Multi VRF Indoor Unit Service Manual 39 CONTROL 1 1 Cooling Operation...
Страница 43: ...40 Multi VRF Indoor Unit Service Manual CONTROL 1 2 Heating Operation...
Страница 44: ...Multi VRF Indoor Unit Service Manual 41 CONTROL 1 3 Fan Operation 1 4 Dry Operation...
Страница 54: ...Multi VRF Indoor Unit Service Manual 51 INSTALLATION...
Страница 80: ...Multi VRF Indoor Unit Service Manual 77 MAINTENANCE...
Страница 118: ...Multi VRF Indoor Unit Service Manual 115 Exploded View of GMV R56T Na K GMV R63T Na K GMV R71T Na K GMV R80T Na K...
Страница 124: ...Multi VRF Indoor Unit Service Manual 121 Exploded View of GMV R22T NaA K GMV R28T NaA K GMV R36T NaA K GMV R45T NaA K...
Страница 134: ...Multi VRF Indoor Unit Service Manual 131 Exploded View of GMV R56P NaB K GMV R71P NaB K...
Страница 136: ...Multi VRF Indoor Unit Service Manual 133 Exploded View of GMV R90P NaB K GMV R112P NaB K GMV R140P NaB K...
Страница 141: ...138 Multi VRF Indoor Unit Service Manual Exploded View of GMV R56PS NaB K GMV R71PS NaB K...
Страница 143: ...140 Multi VRF Indoor Unit Service Manual Exploded View of GMV R90PS NaB K GMV R112PS NaB K GMV R140PS NaB K...
Страница 145: ...142 Multi VRF Indoor Unit Service Manual Exploded View of GMV R224P NaB M...
Страница 147: ...144 Multi VRF Indoor Unit Service Manual Exploded View of GMV R280P NaB M...
Страница 151: ...148 Multi VRF Indoor Unit Service Manual Exploded View of GMV R45PS NaE K GMV R56PS NaE K GMV R71PS NaE K...
Страница 153: ...150 Multi VRF Indoor Unit Service Manual 5 3 Wall Mounted Type Exploded View of GMV L R22G NaB K GMV L R28G NaB K...
Страница 155: ...152 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R36G NaB K GMV L R45G NaB K...
Страница 157: ...154 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R50G NaB K GMV L R56G NaB K...
Страница 159: ...156 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R22G NaC K GMV L R28G NaC K...
Страница 161: ...158 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R36G NaC K GMV L R45G NaC K...
Страница 163: ...160 Multi VRF Indoor Unit Service Manual Exploded View ofGMV L R71G Na K GMV L R80G Na K...
Страница 165: ...162 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R22G NaG K GMV L R28G NaG K...
Страница 167: ...164 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R36G NaG K GMV L R45G NaG K GMV L R50G NaG K...
Страница 169: ...166 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R56G NaG K GMV L R63G NaG K GMV L R71G NaG K...
Страница 173: ...170 Multi VRF Indoor Unit Service Manual 2 Exploded View of GMV R71Zd NaB K GMV R90Zd NaB K...
Страница 175: ...172 Multi VRF Indoor Unit Service Manual 3 Exploded View of GMV R112Zd NaB K GMV R125Zd NaB K...
Страница 177: ...174 Multi VRF Indoor Unit Service Manual 4 Exploded View of GMV L R28Zd Na K GMV L R36Zd Na K GMV L R50Zd Na K...
Страница 188: ...JF00301272...