34
DC Inverter Multi
VRF Service Manual
DPOUSPM
Fig.6.5.8 Label of the Smart Zone Controller
6.6 Attachment
Error code list:
Errors code list of Multi VRF Indoor Units
Code
Description
E1
High pressure protection of the compressor
E2
Anti-freezing protection of the indoor unit
E3
Low pressure protection of the compressor
E4
Discharge temperature protection of the compressor
E5
Over-current protection, overload protection of compressor, drive error
E6
Communication error
E7
0RGHFRQÀLFW
E9
:DWHURYHUÀRZSURWHFWLRQ
EH
E-heater protection
F0
Ambient temperature sensor error of the indoor unit
F1
Error of coil pipe inlet sensor of the indoor unit
F2
Error of coil pipe intermediate sensor of the indoor unit
F3
Error of coil pipe outlet sensor of the indoor unit
F4
Ambient temperature sensor error of the outdoor unit
F5
Error of coil pipe inlet sensor of the outdoor unit
F6
Error of coil pipe intermediate sensor of the outdoor unit
F7
Error of coil pipe outlet sensor of the outdoor unit
F8
(UURURIGLVFKDUJHWHPSHUDWXUHVHQVRU¿[HG
F9
Error of discharge temperature sensor 2 (digital)
FA
(UURURIRLOWHPSHUDWXUHVHQVRU¿[HG
Fb
Error of oil temperature sensor 2 (digital)
Fc
High pressure sensor error
Fd
Low pressure sensor error
Содержание GMV-PD100W/NAB-K
Страница 1: ...DCINVERTERMULTIVRF SERVICE MANUAL T1 R410A 50Hz GC201112 CENTRAL AIR CONDITIONERS...
Страница 5: ...1 DC Inverter Multi VRF Service Manual PRODUCT QSPEVDU...
Страница 11: ...7 DC Inverter Multi VRF Service Manual CONTROL DPOUSPM...
Страница 62: ...58 DC Inverter Multi VRF Service Manual INSTALLATION...
Страница 99: ...95 DC Inverter Multi VRF Service Manual MAINTENANCE...
Страница 118: ...114 DC Inverter Multi VRF Service Manual GMV Pd140W NaB M GMV Pd160W NaB M...
Страница 133: ...JF00300208...