Multi Variable Air Conditioners Fresh Air Series Indoor Unit
20
⑨
Do not alter the inner wires of air conditioner. Manufacturer does not assume responsibility for
damage or abnormal operation due to this reason.
⑩
If the unit is installed in places with strong electromagnetic interference, it's recommended to
use twin-twisted shield wire. During wire connection, please pay attention that the metal shield
layer of the twin-twisted wire must be grounded (outer case) in order to prevent the unit from
electromagnetic interference.
⑪
Communication line should be separated from the power cord and the connection wire of IDU
and ODU.
⑫
If the project needs higher static pressure, you can set it through the wired controller.
⑬
The appliance must be fitted with means for disconnection from the supply mains having a
contact separation in all poles that provide full disconnection under overvoltage category III
conditions, and these means must be incorporated in the fixed wiring in accordance with the
wiring rules.
⑭
The appliance shall be installed in accordance with national wiring regulations.
5.1 Connection of Wire and Patch Board Terminal
(1) The connection of wire (as shown in Fig.5.1.1)
1) Strip about 25mm insulation of the wire end by stripping and cutting tool.
2) Remove the wiring screws on the terminal board.
3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in
accordance with screw.
4) Use the screwdriver for tightening the terminal.
(2) The connection of stranded wire (as shown in Fig.5.1.2)
1) Strip about 10mm insulation of the end of stranded wire by stripping and cutting tool.
2) Loosen the wiring screws on terminal board.
3) Insert the wire into the ring tongue terminal and tighten by crimping tool.
4) Use the screwdriver for tightening the terminal.
Unit: mm
Fig.5.1.1 Fig.5.1.2