Multi Variable Air Conditioners Fresh Air Series Indoor Unit
14
(5) Install the trap as shown in following Fig.4.3.5.
Fig.4.3.5
(6) Install one trap for each unit.
(7) Convenience for cleaning trap in the future should be considered when installing it.
(8) The horizontal pipe can be connected to vertical pipe in the same level; please select the
connection way as shown in following fig.
No.1: Connection of drainage pipe joints (Fig.4.3.6).
No.2: Connection of downspout elbow (Fig.4.3.7).
No.3: Inserting pipe connection (Fig.4.3.8).
Fig.4.3.6 Fig.4.3.7 Fig.4.3.8
(9) Drain pipes should have a downward slope of at least 1% ~ 2%, in order to prevent pipes from
sagging, install hanger bracket at intervals of 1000 ~ 1500mm.
Unit: mm
Fig.4.3.9
4.3.3 Test of Drainage System
Models without water pump
(1) Fill some water to the water tray of indoor unit as following:
1) Connect the drain hose to the other drain connection pipe of water tray and fill about 1L
water (as shown in Fig.4.3.10). (Remove the drain hose after finishing testing and then put
on the plug of water tray).
2) Spray 1L water on evaporator with sprayer, as shown in Fig.4.3.11.