Multi Variable Air Conditioners Fresh Air Series Indoor Unit
17
Unit: mm (in.)
Model
Size of Air Outlet
Size of Air
–returen Opening
A
B
C
D
GMV-NDX42P/A-T(U)
197 (7-3/4)
1151 (45-5/16)
1362 (53-5/8)
264 (10-3/8)
GMV-NDX48P/A-T(U)
197 (7-3/4)
1151 (45-5/16)
1362 (53-5/8)
264 (10-3/8)
GMV-NDX54P/A-T(U)
192(7-1/2)
992(39)
1150(45-1/4)
327(12-7/8)
GMV-NDX72P/A-T(U)
192(7-1/2)
992(39)
1150(45-1/4)
327(12-7/8)
GMV-NDX96P/A-T(U)
192(7-1/2)
992(39)
1150(45-1/4)
327(12-7/8)
4.5 Installation of Wired Controller
Please refer to User Manual of Wired Controller for the installation details.
NOTICE!
When installation is finished, the unit must be tested and debugged before operation.
Please refer to Instruction Manual of ODU for auto addressing and debugging details
.
5 Wiring Work
(1) Wiring should conform to national rules. All the parts, materials, electric work should be in accordance with
local codes.
(2) Rated voltage and exclusive power supply should be used.
(3) Power cord should be fixed soundly and reliable. Never forcibly pull the power cord.
(4) Wire size of power cord should be large enough. The damaged power cord and connecting wire should be
replaced by exclusive cable.
(5) All the electrical work should be performed by professional personnel as per local law, regulation and this
manual.
(6) Connect the unit to the special earthing device and make sure the unit is earthed soundly.
(7) Air switch and circuit breaker is required to be set. Air switch should have both magnetic trip and thermal trip
functions so as to protect the unit when short-circuit and overload happens. D-type breaker is adviced to be
used.
(8) Wiring diagram attached on the unit is prevailed.
(9) Before obtaining access to terminals, all supply circuits must be disconnected.
(10) If units are type I electrical appliances, they must be reliably grounded.
(11) Ground resistance must be in accord with requirements of local standard.
(12) The green-yellow wire within units are ground wire. Do not use it for other purposes. Nor should it be cut off
or secured by tapping screws. Otherwise, it may cause electric shock.
(13) Power supply at user side must have reliable ground terminal. Do not connect ground wire to the following
places:
①
. Water pipe.
②
. Gas pipe.
③
. Drainage pipe.
④
. Other places that are considered by professionals as unreliable.
(14) Power cord and communication wire should be separated, with a distance of more than 200mm (7-7/8in.).
Otherwise, system’s communication may not work well.