Multi Variable Air Conditioners Fresh Air Series Indoor Unit
8
(6) The air switch should include magnetic trip function and thermal trip function so that system can be
protected from short circuit and overload.
(7) An all-pole disconnection switch having a contact separation of at least 3mm (1/8in.) in all poles should
be connected in fixed wiring.
NOTICE!
①
.
Use copper wire only as unit’s power cord. Operating temperature should be
within its rated value.
②
. If the power cord is more than 15 m (49-1/4 ft.) long, please increase properly
the sectional area of power cord to avoid overload, which may cause accident.
③
. Above selection requirements: Power cord size is based on BV single-core wire
(2~4pc) at 40° (104°F) Cambient temperature when laying across plastic pipe.
Air switch is D type and used at 40°C (104°F). If actual installation condition
varies, please lower the capacity appropriately according to the specifications of
power cord and air switch provided by manufacturer.
④
. Install cut-off device near the unit. The minimum distance between each stage
of cut-off device should be 3 mm (1/8 in.) (The same for both indoor unit and
outdoor unit).
4 Installation Instructions
4.1 Installation of Indoor Unit
4.1.1 Outline Dimension and Installation Spots
Equip with a service port after hanging the unit. For the convenience of maintenance,
the service port should be on one side of the electric box and below unit’s lower level.
Fig 4.1.1