![Gree GMV ND50PHS/B-T Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/gree/gmv-nd50phs-b-t/gmv-nd50phs-b-t_owners-manual_2260287012.webp)
Multi Variable Air Conditioners Ducted Type Indoor Unit
9
Fig 4.1.6
(7) Remove the washer locating plate and then tighten the nut on it
(8) Remove the paper pattern
Fig 4.1.7
4.2 Refrigerant Pipe Connection
(1) Aim the flaring port of copper pipe at the center of screwed joint and then tighten the
flaring nut with hand as shown in fig 4.2.
(2) Tighten the flaring nut with torque wrench.
Fig 4.2
(3) Use pipe bend when bending the pipe and the bending angle should not be too small.
(4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape.
4.3 Drainage Pipe Installation and Drainage System Testing
4.3.1 Notice for Installation of Drain Pipe
(1) The drainage pipe should be short and the gradient downwards should be at least 1%~2%
Torque for tightening nut
Pipe diameter (mm)
Torque (N·m)
Φ6.35
15~30
Φ9.52
35~40
Φ12.7
45~50
Φ15.9
60~65
Φ19.05
70~75