Multi Variable Air Conditioners Console Type Indoor Unit
6
(Unit: mm)
Boring a wall hole and installing wall embedded pipe.
For walls containing metal frame or metal board, be sure to use a wall embedded pipe and wall
cover in the feed-through hole to.
Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage.
(1) Bore a feed-through hole of 65mm in the wall so it has a down slope toward the outside.
(2) Insert a wall pipe into the hole.
(3) Insert a wall cover into wall pipe.
(4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole gap with putty.
(Unit: mm)
2.3 Drain Piping
(1) Use commercial rigid polyvinyl chloride pipe general VP 20 pipe, outer diameter 26mm,
inner diameter 20mm for the drain pipe.
(2) The drain hose (outer diameter 18mm at connecting end, 220mm long) is supplied with the
indoor unit. Prepare the drain pipe picture below position.
(3) The drain pipe should be inclined downward so that water will flow smoothly without any
(Should not be trap).
(4) Insert the drain hose to this depth so it won’t be pulled out of the drain pipe.
(5) Insulate the indoor drain pipe with 10mm or more of insulation material to prevent
condensation.
(6) Remove the air filters and pour some water into the drain pan to check the water flows
smoothly.
(7) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines
which are likely to produce corrosive or peculiar smell to prevent the smell from entering
indoors or corrupt the unit.