Multi Variable Air Conditioners Console Type Indoor Unit
10
When using commercial copper pipes and fittings, observe the following:
(1) Insulation material: Polyethylene foam.
Heat transfer rate:0.041 to 0.052W/m K (0.035 to 0.045kca/(m h °C)).
Refrigerant gas pipe’s surface temperature reaches 110 max.
Choose heat insulation materials that will withstand this temperature.
(2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as
below.
Gas side
Liquid side
Gas pipe thermal insulation
Liquid pipe thermal insulation
22/28 class
36/45/50 class
—
22/28 class
36/45/50 class
—
O.D.9.52mm
O.D.12.7mm
O.D.6.35mm
I.D.12-15mm
I.D.14-16mm
I.D.8-10mm
Thickness 0.8mm
Thickness 10mm Min.
(3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Checking for gas leakage.
(4) Check for leakage of gas after air purging.
(5) See the sections on air purges and gas leak checks in the installation manual for the outdoor
unit.
Attaching the connection pipe.
Attach the pipe after checking for gas leakage, described above.
(1) Cut the insulated portion of the on-site piping, matching it up with the connecting portion.
(2) Secure the slit on the refrigerant piping side with the butt joint on the auxiliary piping using
the tape, making sure there are no gaps.
(3) Wrap the slit and butt joint with the included insulation sheet, making sure there are no gaps.