Multi Variable Air Conditioners One-way Cassette Type Indoor Unit
10
(6) Make sure to perform insulation work for all drainage piping in order to prevent any
possible water drop due to dew condensation.
(7) Apply the suitable diameter for converging drainage pipe according to the operating
capacity of the unit.
Unit: mm(inch)
Fig.4.3.2
(8) The installation height of raising pipe for drainage should be lower than B. The gradient
from raising pipe towards drainage direction should be at least 1%~2%. If the raising pipe
is vetical with the unit, the raising height should be less than C.
Unit: mm(inch)
Fig.4.3.3
Model
A (mm/inch)
B(mm/inch)
C(mm/inch)
GMV-ND07TD/A-T(U)
GMV-ND09TD/A-T(U)
GMV-ND12TD/A-T(U)
100(3-15/16)
1100(43-5/16)
1050(41-5/16)
(9) Drain pipes should have a downward slope of at least 1%~2%, in order to prevent pipes
from sagging, install hanger bracket at intervals of 1000~1500mm (39-3/8~59 inch).