Multi Variable Air Conditioners Compact Cassette Type Indoor Unit
5
Material Type
Total Length L
(m/ft.) of
Communication
Cable between
Indoor Unit and
Indoor (Outdoor)
Wire size
(mm
2
/AWG)
Material
standard
Remarks
Light/Ordinary
polyvinyl
chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤1000
(L≤3280-13/16)
≥2×0.75
(≥2×AWG18)
IEC
60227-5
1. If the wire diameter is enlarged
to 2×1 mm² (2×AWG16), the
total communication line length
can reach 1500m (4920ft).
2. The cord shall be Circular cord
(The cores shall be twisted
together).
3. If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to
use shielded wire.
3.4 Wiring Requirement
Power Cord Size and Air Switch Capacity
Model
Power Supply
MCA(A)
MOP(A)
GMV-ND07T/B-T(U)
208/230V-1ph-60Hz
2
15
GMV-ND09T/B-T(U)
2
15
GMV-ND12T/B-T(U)
2
15
GMV-ND15T/B-T(U)
2
15
GMV-ND18T/B-T(U)
2
15
(1) An all-pole disconnection switch having a contact separation of at least 3mm (1/8 inch) in all
poles should be connected in fixed wiring.
(2) The circuit breaker and power cord specification in above sheet are based on max power (max
current) of the unit.
(3) The power cord specification in above sheet is based on ambient temperature of 40°C (104°F).
(4) The circuit breaker specification in above sheet is based on ambient temperature of 40°C
(104°F). If the working condition is different, please adjust it according to the specification sheet
of circuit breaker.