Multi Variable Air Conditioners Wall Mounted Type Indoor Unit
6
4.2 The installation of the Rear Panel
Unit: mm(inch)
Fig. 4.2
(1) Find the horizontal position by the seton method; since the drainage pipe is on the left side, it
is necessary to adjust the rear panel to make its left side a little bit lower.
(2) Fix the rear panel on the wall by bolts.
(3) After installing the rear panel, pull it by hands to check if it is secured enough. The hang
panel should support the weight of an adult (60kg), and the weight shared by every bolt
should be fairly even.
(4) The diameter showed in Fig. 4.2 is 55mm(2-3/16inch) or 70mm(2-3/4inch).
4.3 Preparation of the Piping Hole
(1) Make the piping hole (55mm(2-3/16inch) or 70mm(2-3/4inch)) in the wall at a slight
downward slant to the outdoor side. The center of the hole should be determined referring to
Fig. 4.2.
(2) Insert the piping-hole sleeve into the hole to prevent the connected piping and wiring from
being damaged when passing through the hole.
4.4 Installation of the Drainage Pipe
(1) For proper draining, the drain hose should be placed at a downward sloping.
(2) Do not wrench or bend the drain hose or flood its end by water.
(3) Wrap the drain hose with heat resistant material.
(4) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines
which are likely to produce corrosive or peculiar smell to prevent the smell from entering
indoors or corrupt the unit.
(5) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water
from pouring in and cause property loss or personal injury.
(6) Condensate drain pipe should be connected into special drain system for air conditioner.