background image

Clean and maintenance

Deep clean (parts clean) 

Claps of

swing blade

swing motor

T-ON

Guide louver clean 

Under standby status, press

button for 3s, and the display flashes
to display          . Meanwhile, the guide 

louver will open automatically.

When the guide louver automatically

rotates to the maximum position,

             will disappear. Cut off the 

    power.

Press the left side connection rod

with left hand, hold the guide louver

with the right hand, and then pull

the guide louver outwards.

Immerse the cloth into the warm

water (45

), wring it out and then

wipe the dirty part slightly. After

that, dry it.

Press the clasp at the left side of

the swing blade and pull it to the

right side, and then it can separate

with the swing motor.

Press the cross clasp at the right

side of guide louver with right hand,

hold the guide louver with left hand

and then draw out the guide louver

to the left side.

When the installation is finished,

energize the air conditioner again

until the guide louver is  reset

automatically and then the unit can

be operated.

11

Содержание GIST09BXA

Страница 1: ...ual carefully before operation and retain it for reference If you lost the User s Manual please contact the Tool Box or visit www gilman group com or send an email to Tool Box for the electronic versi...

Страница 2: ...GIST09BXAE GIST09BXAC GIST12BXAE GIST12BXAC...

Страница 3: ...This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision o...

Страница 4: ...components that produced by other manufacturers 6 After verification the problem or dispute is caused by the quality specification or 7 The damage is caused by natural calamities harsh environment or...

Страница 5: ...dren without supervision Do not connect air conditioner to multi purpose socket Otherwise it may cause fire hazard Disconnect power supply when cleaning air conditioner Otherwise it may cause electric...

Страница 6: ...recautions WARNING conditioner and disconnect power immediately and then If the air conditioner operates under abnormal conditions it may cause malfunction electric shock or fire hazard Do not spill w...

Страница 7: ...ve wire properly neutral wire and any work related to electricity and safety Be sure to cut off the power supply before proceeding Including an circuit break with suitable capacity please Air Conditio...

Страница 8: ...ified personnel local wiring regulations requirement of NEC and CEC by authorized personnel only Precautions WARNING wire which can t be used for other purposes The grounding resistance should comply...

Страница 9: ...anufacturer Precautions WARNING place please can perform the work by qualified personnel Otherwise it may cause personal injury or If you need to relocate the air conditioner to another must be instal...

Страница 10: ...ake sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection pipe If compressor starts running when stop valve is open and connection pipe is not...

Страница 11: ...e controller is lost or damaged please use aux button to turn on or turn off the air conditioner The operation in details is as below As shown in the fig Below 1 Open panel 2 Press aux button to turn...

Страница 12: ...diagram of parts Filter Evaporator Swing motor Base Blade Drainage pipe Screw cover Clasp of swing blade Panel Storage groove of screw Silver screw Cross buckle Bottom case Guard network Air outlet f...

Страница 13: ...turning on the unit If you don t want to clean the air conditioner at the moment press the combination buttons of MODE TEMP to cancel this remind Please select the clean procedure according to the act...

Страница 14: ...as grease use warm water 45 dissolved with neutral detergent to clean it and then put it at the shady place to dry it Caution Reminder Do not use hot water more than 45 to clean the filter to prevent...

Страница 15: ...the right hand and then pull the guide louver outwards Immerse the cloth into the warm water 45 wring it out and then wipe the dirty part slightly After that dry it Press the clasp at the left side o...

Страница 16: ...ened to the maximum angle when a sound has been heard the panel can be fixed Open the screw cover at the lower side of the air outlet frame and then use screwdriver to remove 2 black screws Immerse th...

Страница 17: ...oth sides with both hands simultaneously and pull it upwards and then remove the guard net 3 Remove blade Rotate the blade slightly and the find the silver screw at the right side of the blade Use the...

Страница 18: ...ing the bottom case Press the appointed positions at both sides with both thumbs as shown in below figure hold the bottom case with other four fingers and then lift it upwards and then remove the bott...

Страница 19: ...m case push it upwards parallel along the guide rail of base and then check whether the both ends of bottom case is set into the tail of the guide rail of base for ensuring the installation Fix the bo...

Страница 20: ...e node to pull it to the right side until to the locking status Tighten silver screw 4Please make sure the blade is locked and then the silver screws of blade can be tightened clockwise Install guard...

Страница 21: ...to the direction of drainage outlet until you have head a sound White drainage pipe Install air outlet frame 7Insert the clasp at the back side of the air outlet frame into the groove of the base as s...

Страница 22: ...r will open to the first position and then display Please make sure all disassembled screws are fixed well If the indoor unit cannot work normally after power connected please check the unit Whether t...

Страница 23: ...ainage pipe Distance to the obstruction At least 50cm At least 250cm Distance to the ceiling At least 15cm At least 50cm Distance to the obstruction 3 uc At least 0cm At least 200cm At least 30cm Dist...

Страница 24: ...medical equipment 3 The place near coast area 4 The place with oil or fumes in the air 5 The place with sulfureted gas 6 Other places with special circums tances 7 The appliance shall not be install e...

Страница 25: ...e keep the interconnec 9 The appliance shall be installed in accordance with national wiring regulations 2 for other purposes The yellow green wire in air conditioner is grounding wire which can t be...

Страница 26: ...Step one choosing installation location Step two install wall mounting frame 300 300 55 55 Step three open piping hole 55 22 Installation of indoor unit...

Страница 27: ...tion for selection of drainage outlet there are no mandatory requirements for the direction of the drainage pipe However it s suggested to be same with the direction of liquid pipe and gas pipe Theref...

Страница 28: ...til you have head a sound Rubber cork of left drainage outlet Rubber cork of right drainage outlet 24 1 Aim the pipe joint at the corresponding bellmouth 3 Adjust the torque force by referring to the...

Страница 29: ...60 65 70 75 15 20 insulating pipe 1 Connect the drain hose to the outlet pipe of indoor unit 2 Bind the joint with tape outlet pipe drain hose drain hose tape outlet pipe drain hose insulating pipe N...

Страница 30: ...an circuit break must be installed in the line The circuit break should be all pole parting and the contact parting distance should be more than 3mm 3 Remove the wire clip connect the power connectio...

Страница 31: ...QWURO ZLUH FDQ W EH FURVVHG RU ZLQGLQJ 7KH GUDLQ KRVH VKRXOG EH ERXQG DW WKH ERWWRP GUDLQ KRVH EDQG FRQQHFWLRQ SLSH LQGRRU SRZHU FRUG 6WHS QLQH KDQJ WKH LQGRRU XQLW 3XW WKH ERXQG SLSHV LQ WKH ZDOO SLS...

Страница 32: ...it select it according to the actual installation situation 1 Select installation location according to the house structure 2 Fix the support of outdoor unit on the selected location with expansion sc...

Страница 33: ...pe liquid pipe liquid valve gas valve union nut pipe joint Hex nut diameter Tightening torque N m 6 9 52 12 16 19 30 40 45 55 60 65 70 75 15 20 1 Remove the wire clip or front plate connect the power...

Страница 34: ...outlet pipe hole of indoor unit Slant the drain hose slightly dow nwards The drain hose can t be The water outlet can t be placed in water in order to drain smoothly Installation of outdoor unit U sh...

Страница 35: ...UL JHUDQW FKDUJLQJ YHQW RQQHFW WKH FKDUJLQJ KRVH RI SLH RPHWHU WR WKH UHIUL JHUDQW FKDUJLQJ YHQW RI JDV YDOYH DQG WKHQ FRQQHFW WKH RWKHU FKDUJLQJ KRVH WR WKH YDFXXP SXPS 2SHQ WKH SLH RPHWHU FRP SOHWHO...

Страница 36: ...RQ RU GDPDJLQJ WKH SDUWV V WKHUH DQ REVWUXFWLRQ LQ WKH DLU LQOHW V WKH LQOHW DQG RXWOHW RI SLSLQJ KROH EHHQ FRYHUHG DQG RXWOHW KHDWLQJ FDSDFLW 7KH GXVW DQG VXQGULHV FDXVHG GXULQJ LQVWDOODWLRQ DUH UHPR...

Страница 37: ...ctual products power indicator display temp indicator receiver window WARNING Do not insert your fingers it will cause personal injury WARNING Do not touch the fins it will cause personal injury WARNI...

Страница 38: ...34 Buttons on remote controller Note i button signal varied for defferent HOLD 3S WiFi...

Страница 39: ...QWURGXFWLRQ IRU EXWWRQV RQ UHPRWH FRQWUROOHU Note Only for models with heating function...

Страница 40: ...right and then loosen the button the unit will stop swinging and present position of guide louver will be kept immediately Under swing left and right mode when the status is switched from off to if p...

Страница 41: ...temperature or low temperature in order to avoid detecting inaccurate ambient temperature When I FEEL function is turned on the remote controller should be put within the area where indoor unit can r...

Страница 42: ...troller blinks Press or button to adjust TIMER ON setting After each pressing or button TIMER ON setting will increase or decrease 1min Hold or button 2s later the time will change quickly until reach...

Страница 43: ...te at the same time If energy saving function has been set under cooling mode press sleep button will cancel energy saving function If sleep function has been set under cooling mode start up the energ...

Страница 44: ...RQWURO VLJQDO VHQGHU DW WKH UHFHLYLQJ ZLQGRZ RQ LQGRRU XQLW 7KH GLVWDQFH EHWZHHQ VLJQDO VHQGHU DQG UHFHLYLQJ ZLQGRZ VKRXOG EH QR PRUH WKDQ P DQG WKHUH VKRXOG EH QR REVWDFOHV EHWZHHQ WKHP 6LJQDO PD EH...

Страница 45: ...m Pull out the plug Reinsert the plug after about 3min and then turn on the unit again Signal receiving range is 8m Remove obstacles Select proper angle and point the remote controller at the re ceivi...

Страница 46: ...42 Malfunction analysis 16 8 Odours are emitted Whether there s odour source such as furniture and cigarette etc Eliminate the odour source Set temperature range Set temperature range in HEAT mode...

Страница 47: ...V WXUQHG RQ XULQJ GHIURVWLQJ XQGHU KH DWLQJ PRGH LW PD JHQHUDWH YDSRU ZKLFK LV D QRUPDO SKHQRPHQRQ DWHU QRLVH LU FRQGLWLRQHU LV WXUQHG RQ RU WXUQHG RII MXVW QRZ 7KH QRLVH LV WKH VRXQG RI WKH XQLW ZKLF...

Страница 48: ...5 E8 It can be eliminated after restarting the unit If not please contact qualified professionals for service H3 H6 C5 E6 F3 F4 Please contact qualified professionals for service F0 F1 F2 WARNING Malf...

Страница 49: ...according to the requirement as shown in the table The additional refrigerant charging amount per meter is different according to the diameter of liquid pipe See the following sheet Additional refrige...

Страница 50: ...unt for R22 R407C R410A and R134a Diameter of connection pipe Liquid pipe mm Gas pipe mm 6 6 or 9 52 12 16 19 22 2 9 52 or 12 16 or 19 19 or 22 2 25 4 or 31 8 _ _ Cooling only g m Cooling and heating...

Страница 51: ...ZDUGV SLSH VKDSHU 3XW RQ VXLWDEOH LQVXODWLQJ SLSH 3XW RQ WKH XQLRQ QXW 5HPRYH WKH XQLRQ QXW RQ WKH LQGRRU FRQQHFWLRQ SLSH DQG RXWGRRU YDOYH LQVWDOO WKH XQLRQ QXW RQ WKH SLSH XQLRQ SLSH SLSH SDQG WKH S...

Страница 52: ...veness ToolBox Customer Service Centre 4 F DCH Building 20 Kai Cheung Road Kowloon Bay Hong Kong Service E mail 8210service gilman group com Please register now at www toolbox hk Website www gilman gr...

Отзывы: