28
Technical Information
Service Manual
6. Electric Heating Function of Chassis
(1) When Toutdoor amb.≤32ºF , the electric heating of chassis will operate;
(2) When Toutdoor amb.>35.6ºF , the electric heating of chassis will stop operation;
(3)When 32ºF <Toutdoor amb.≤35.6ºF, the electric heating of chassis will keep original status.
7. Electric Heating Function of Compressor
(1) When Toutdoor amb.≤≤23ºF , compressor stops operation, while the electric heating of compressor starts operation;
(2) When Toutdoor amb.>28.4ºF , the electric heating of compressor stops operation;
(3) When 23ºF <Toutdoor amb.≤28.4ºF , the electric heating of compressor will keep original status.
Содержание GH18QD-D3DNA6E(LCLH)
Страница 1: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Change for Life Service Manual ...
Страница 13: ...10 Technical Information Service Manual 3 2 Outdoor Unit Unit inch 35 13 3 8 27 9 16 15 5 8 38 14 5 16 22 ...
Страница 42: ...39 Installation and Maintenance Service Manual 9 2 Error Code List ...
Страница 87: ...84 Installation and Maintenance Service Manual ...