40
Maintenance
Service Manual
16.Remove motor
17.Remove damper plate
18.Remove condenser and evaporator
Remove 1 screw fixing the damper plate
and then remove the damper plate.
Note:
1. Before unsoldering the spot weld,
please Confirm the refrigerant is
discharged completely.
2. When unsoldering the spot weld of
capillary,wrap the capillary with wet
cloth to prevent damage to capillary due
to high temperature. Seal the discharge
pipe outlet and suction pipe outlet with
rubber cork or gummed paper to prevent
sundries getting into it.
Unsolder the spot weld between suction
pipe, discharge pipe and evaporator,
condenser,and remove suction pipe and
discharge pipe.Unsolder the spot weld
between capillary sub-assy and condenser,
evaporator, and then remove capillary
sub-assy.
Remove 3 screws fixing the motor
and then remove the motor.
a
b
screw
motor
propeller housing
screw
damper plate
spot weld
condenser and evaporator
process tube
Step
Procedure
Lift it upwards and then remove the evaporator
and the condenser.