Ducted Type Split Air-Conditioner Units(Inverter Series)
18
Fig.20
2) Connection of power cord and communication wire for IDU and ODU.
Selection of circuit breaker and power cord.
Model
Power supply
Circuit
breaker
capacity
(A)
Number of
ground wire ×
Min sectional
area (mm
2
)
Number of
power cord ×
Min sectional
area (mm
2
)
FGR20Pd/DNa-X
(O)
380-415V 3N~
50/60Hz
20
1×2.5
4×2.5
FGR20Pd/DNa-X
(I)
220-240V ~
50/60Hz
10
1×1.5
2×1.5
FGR25Pd/DNa-X
(O)
380-415V 3N~
50/60Hz
25
1×2.5
4×2.5
FGR25Pd/DNa-X
(I)
220-240V ~
50/60Hz
10
1×1.5
2×1.5
FGR30Pd/DNa-X
(O)
380-415V 3N~
50/60Hz
32
1×4.0
4×4.0
FGR30Pd/DNa-X
(I)
220-240V ~
50/60Hz
10
1×1.5
2×1.5
FGR40Pd/D(2)N
a-X(I)
380-415V 3N~
50/60Hz
10
1×1.5
4×1.5