GREE Duct type split Air conditioner Inverter Series
78
Description of each stage of debugging progress
——
Debugging code
Instruction for Code and Operating Method
Progress
LED
Display code
Display
status
07_ Component
inspection of
indoor unit
07/
Corresponding
error code
Display
repeatedly
Component error of indoor unit.
After eliminating all the errors, enter the next step automatically,
if the ODU should be powered off for troubleshooting, after re-
energizing the unit, please conduct debugging from the above 01
step.
07/oC
Display
repeatedly
No component error of indoor unit.
After displaying for 5s circularly, the system will enter the next
step automatically.
08_ Preheat
confirmation of
compressor
08/oC
Display
repeatedly
After displaying for 2s circularly, the system will enter the next
step automatically.
09_ Confirmation
of valve of outdoor
unit
09/oF
Display
repeatedly Standby status, ready to start.
09/on
Display
repeatedly The system has started.
09/U6
Display
repeatedly
Malfunction shutdown.
The nixie tube of faulted module will display “09” and “U6”
repeatedly and the nixie tube of other modules will display “09”
and “J0”. In canse malfunction occurd, please check if the valve
is opened and if the connection pipes among different modules
are correctly connected.
09/oC
Display
repeatedly
Confirmation of valve status.
All modules are halted normally, nixie tubes of all modules will
display once circularly.
10_ Debugging
completed
OFF
ON
Debugging is completed, the system is in standby status.
1.5 Function setting
1.5.1 Function setting of outdoor unit
After debugging, long press “SW1” button in master control for 5s, the system will enter function
standby status, main board indicator of outdoor unit is displayed acquiescently as follows:
LED
Function code
Display method
A7
Blink
Select corresponding function to switch LED function code through “SW1” and “SW2” button in
master control, function setting includes: outdoor quiet mode setting (A7), unit cooling and heating
function setting (A6), mandatory defrosting operation (n3) and energy conservation mode setting (n0).
After selecting corresponding function, short press “SW3” button for confirmation, main board
indicator of outdoor unit is displayed as follows:
LED
Function code
Display method
A7
Blink
A6
Blink
n3
Blink
n0
Blink
Содержание CF01000730
Страница 27: ...GREE Duct type split Air conditioner Inverter Series 25 4 Click Next 5 Installation is in progress...
Страница 35: ...GREE Duct type split Air conditioner Inverter Series 33 3 Select language 4 Select system of units...
Страница 56: ...GREE Duct type split Air conditioner Inverter Series 54 7 Switchover of Software Languages...
Страница 118: ...GREE Duct type split Air conditioner Inverter Series 116 FGR40Pd D 2 Na X I FGR20Pd DNa X O...
Страница 119: ...GREE Duct type split Air conditioner Inverter Series 117 FGR25Pd DNa X O FGR30Pd DNa X O...
Страница 129: ...JF00303352 JF00304016...