GREE Duct type split Air conditioner Inverter Series
77
(2) Unit manufactured after Oct 30,2018.
Debugging procedure for test run, display instruction for indicator on main board of outdoor unit and
operation method are as below:
Description of each stage of debugging progress
——
Debugging code
Instruction for Code and Operating Method
Progress
LED
Display code
Display
status
Start
A0
Always
ON
No debugged yeat. Press “SW3” button consecutively in the
master module for over 5s to enter auto debugging.
01_Master unit
setting
01/CC
Display
repeatedly
The system has no master unit.
Debugging can’t be continued, all buttons are invalid, disconnect
the power to reset the correct “SA6” DIP.
01/CF
Display
repeatedly
The system has two or more master units.
Debugging can’t be continued, all buttons are invalid, disconnect
the power to reset the correct “SA6” DIP.
01/oC
Display
repeatedly
The system has only one master unit.
After displaying once circularly, the system will enter the next
step automatically.
02_Address
allocation
02
Bllink
The system is allocating address, which might takes 10s.
02/L7
Display
repeatedly
No master indoor unit.
It will display for 1min continuously. The user can set master
through debugging the software within 1min. If no master unit is
set manually within 1min, the system will set the indoor unit with
the smallest IP address automatically as the master indoor unit.
02/oC
Display
repeatedly
Address allocation of the system is complete with master indoor
unit.
After displaying once circularly, the system will enter the next
step automatically.
03_ Confirm
quantity of outdoor
units
03/ quantity of
modules in the
system
Display
repeatedly
Confirmation of quantity of modules in the system.
To differentiate from the debugging step, the QTY of module will
display only 1-digit on the right.
03/oC
Display
repeatedly
After 10S, all the nixie tubes of modules will display “03” and
“oC”, after displaying once circularly, the system will enter the
next step automatically.
04_Confirm
quantity of indoor
units
04/Cb
Display
repeatedly
The quantity of indoor unit is more than 1.
The system shall not connect more than 1 indoor unit, after
inspection, please redebug for confirmation.
04/oC
Display
repeatedly
The quantity of indoor unit is 1.
After confirming the quantity of indoor unit, it will enter the next
step 2s later.
05_ Internal
communication of
outdoor unit
05/C2
Display
repeatedly
Communication error between master control and compressor
drive.
Please check the connection between the main board of outdoor
unit and communication cord of drive board, after eliminating the
errors, enter the next step. If the ODU should be powered off for
troubleshooting, after re-energizing the unit, please conduct
debugging from the above 01 step.
05/oC
Display
repeatedly
Communication between the master control of outdoor unit and
drive is normal.
After displaying once circularly, the system will enter the next
step automatically.
06_ Component
detection of
outdoor unit
06/
Corresponding
error code
Display
repeatedly
Component error of outdoor unit.
After eliminating all the errors, enter the next step automatically,
if the ODU should be powered off for troubleshooting, after re-
energizing the unit, please conduct debugging from the above 01
step.
06/oC
Display
repeatedly
No component error of outdoor unit.
After displaying for 10s circularly, the system will enter the next
step automatically.
Содержание CF01000730
Страница 27: ...GREE Duct type split Air conditioner Inverter Series 25 4 Click Next 5 Installation is in progress...
Страница 35: ...GREE Duct type split Air conditioner Inverter Series 33 3 Select language 4 Select system of units...
Страница 56: ...GREE Duct type split Air conditioner Inverter Series 54 7 Switchover of Software Languages...
Страница 118: ...GREE Duct type split Air conditioner Inverter Series 116 FGR40Pd D 2 Na X I FGR20Pd DNa X O...
Страница 119: ...GREE Duct type split Air conditioner Inverter Series 117 FGR25Pd DNa X O FGR30Pd DNa X O...
Страница 129: ...JF00303352 JF00304016...