CASSET TE B SERIES
OWNERS MANUAL - INDOOR UNIT
|
10
2 Buttons
2.1 Buttons on the Wired Controller
2
2
1
3
4
5
6
7
8
Fig. 3 Buttons on the Wired Remote Controller
No.
1
3
7
6
4
5
2
8
3+4
6+7
3+7
4+7
2+5
2+5
5+6
Display
SWING/ENTER
FAN
MODE
FUNCTION
TIMER
ON/OFF
+ MODE
FAN +
+
MODE +
TIMER+FUNCTION
TIMER+FUNCTION
FU FAN
Instruction of Display
1
Function selection and cancellation.
2
Setting of the up and down swing function.
1
Running temperature setting of the indoor unit, range:61~86°F(16~30
0
C).
2
Timer setting, range:0.5-24 hr.
Setting of the auto/low/medium low/medium/medium high/ high fan speed.Heating mode
Setting of the Cooling/Heating/Fan/Dry/Auto mode of the indoor unit.
Switchover among the functions of Turbo/WiFi/X-fan etc..
Timer setting.
Turn on/off the indoor unit.
Press them for 5s under off state of the unit to Enter/Cancel the Memory function(If memory is set, indoor unit after power
failure and then power recovery will resume the original setting state. If not, the indoor unit is defaulted to be off after power
recovery. (Memory off is the factory default setting).
By pressing them at the same time under off state of the unit,
will be displayed on the wired controller for the cooling only
unit, while will be displayed on the wired controller for the cooling and heating unit.
Upon startup of the unit without malfunction or under off state of the unit, press them at the same time for 5s to enter the lock
state, in which case, any other buttons won’t respond.
Repress them for 5s to quit this state. Under OFF state, the Celsius and Fahrenheit scales can be switched by pressing “MODE”
and “ ” for 5s.
Under OFF state, go to the commissioning status by pressing “FUNCTION” and “TIMER” for five seconds, and let “00” displayed
on he temperature display area by pressing “MODE”, then adjust the options which is shown on the timer area by pressing “ ”
and “ ”. There are four options, as follows:
1
Indoor ambient temperature is sensed by the return air temperature sensor (01 displayed on the timer area).
2
Indoor ambient temperature is sensed by the wired controller (02 displayed on the timer area).
3
The return air temperature sensor is selected under the cooling, dry, or fan mode; while the wired controller temperature
sensor is selected under the heating or auto mode. (03 is displayed on the timer area).
4
The wired controller temperature sensor is selected under the cooling, dry, or fan mode; while the return air temperature
sensor is selected under the heating mode. (04 is displayed on the timer display area).
Under OFF state, go to the commissioning status by pressing “FUNCTION” and “TIMER” for five seconds. Press “MODE” button
to until “01” icon is shown at the temperature display area. The setting status will be shown at timer area. Press “ ” and “ ”
button to adjust and two options are available:
1
Three low levels (01) ;
2
Three high levels (02).
Reset the WiFi function: Under off status, press “FUNCTION” + “FAN” combination buttons on its wired controller for 5s. Once
“oC” is displayed, this indicates that reset was successful.
WIRED CONTROLLER (Continued)