background image

3

SITE PREPARATION

Before installing, careful consideration should be given to the place of 

operation. Place unit on a smooth, level surface. Use leveling feet to 

correct for minor variations in floor.
Place Tempest near a 115V, 60Hz, 1-ph grounded electrical outlet.
You will also need compressed air, maximum of 100PSI.

the work area should be well ventilated and lit.

Provide adequate lighting in the work area to permit viewing of the 

cleaning process and of the floor area around the machine. Be sure 

to allow adequate room to bring work to and from the machine. Use 

flooring or floor covering that does not become slippery when wet. 

Provide sufficient clearance around the machine for fluid changeovers 

and servicing.

A drain coupling has been provided in the reservoir. It is recommended 

to plumb a drain valve to this coupling to facilitate cleaning.

we recommend our low foaming aquatene

. Contact graymills for 

specific details on the formula best suited for your application.

INSTALLATION

For Tempest 10 Unit:

1. Disconnect Drain Pipe

 

(Fig. 1, p.5) and lower pipe into pail reservoir

2. Remove entire pail assembly from shelf and set on floor.
3. Loosen snap ring securing ring to pail and remove lids (Fig. 2 and 

3, p.5)

4. Graymills recommends use of pail liners as a means of simplifying 

liquid changes and insuring reservoir’s long life

be careful to prevent liner from coming into contact with heater element 

as the plastic will melt on element and cause heater failure

5. Fill pail with low foam detergent and water, following mixing 

directions on recommended detergent package.

  Excessive foaming caused by improper mixing ratios or use of 

improper detergents, can result in loss of pump prime and can 

damage heater and/or pump. Should foaming occur, skim off 

excessive foam and add water to proper level or add defoaming 

agents. If foaming continues, dispose of liquid and review detergent 

ratios and/or formulation

6. Replace lid and secure with snap ring. Put assembly back within 

cabinet.

7. Prime pump by filling intake hose completely with water, then 

connecting filter hose to pump.

8. Plug heater cord into lower socket in outlet box above pump shelf. 

Plug pump cord into upper socket (Fig. 4, p.5).

9. Connect drain hose (Fig. 1, p.5) and close lower cabinet door.
10.Plug unit’s power cord into 115V, 60 Hz, 1-ph grounded outlet.
11.Check GFI Switch on rear of contorl box to make sure it is ON. 

For Tempest 20S Unit:

1. Fill 20-gallon cleaning solution reservoir

 

to at least a 12” depth with 

appropriate cleaning solution. To protect equipment and personnel, 

the fluid level should never fall below 4” from the top of the tank 

and must cover the coiled portion of the heating element and the 

thermostat’s thermal bulb.

2. With door closed and latched, activate main power switch on the 

control panel.

OPERATION 

The spray chamber and reservoir of the Tempest 10S and 20S units 

are stainless steel. The base is carbon steel.
If you have purchased a heated Tempest 10 unit with a carbon steel 

cabinet, some uses of water-based cleaning materials will generate 

steam and water vapor. Surfaces inside the cabinet will be subject 

to rusting. 

this is surface rust and does not appreciably affect the 

service and use of the unit.

 We recommend that the door be left open 

when the unit is not in use. Leaving the door open when not in use 

may lessen condensation and rust inside the unit. If your cleaning 

requirements cannot tolerate any rust or contamination, please contact 

Graymills about stainless steel cabinets. Also, check with your cleaning 

fluid supplier to make sure your cleaning materials contain a rust 

inhibitor.

the graymills warranty does not cover rusting of carbon steel parts.

Check fluid level in cleaning solution reservoir daily. Assure level is at 

or above minimum level at all times. Heavy, constant use may warrant 

daily fluid changes.
Inspect filter bag on end of drain pipe daily. Filter bag is secured to 

drain pipe with a reusable plastic tie – there is a small plastic release 

lever on locking cube.(Fig. 7, p.5) Properly dispose of any solid waste 

accumulation, rinse bag in water, and re-attach to drain pipe.

failure to keep cleaning solution reservoir full can result in heater 

failure, loss of pump prime, or over heating of the fluid.
do Not operate unit without a filter bag.

Inspect heating element daily. Any foreign material should be removed 

by gently scrubbing.

Do NOT neglect cleaning of the heating element. Failure to do so will 

cause premature failure. Do NOT allow oil or sludge to bake onto the 

heater element as premature heater burnout will result.

at this time the pump is fully operational. do Not depress the foot 

pedal switch unless the spray hose is being gripped. under pressure, 

without gripping, it will fly around potentially causing damage.

•  Using the adjustable thermostat, set heat to desired temperature up 

to 120°F maximum. Allow approximately one to two hours for the 

heater to warm the solution to operating temperature.

•  Open spray chamber door and secure with door retaining latch 

(Fig. 5, p.5). Carefully load parts into the cabinet, distributing 

weight as evenly as possible.

tempest is equipped with a pressure relief valve in the spray cabinet 

that is intended as a safety device (figure 6). when pressure is 

relieved, the valve automatically resets. Should pressure inside spray 

delivery system reach an unsafe level, relief valve will vent excess 

pressure back into cabinet. this valve must be kept clean and free of all 

contaminants to insure its proper functioning. activation of the pressure 

relief valve is not expected during normal operation. 

adjustable nozzle should never be adjusted to a no-flow position as it may 

activate the pressure relief valve and cause possible mechanical failure of 

the pump. if no flow is desired, remove foot from foot pedal switch.
always completely lift parts into and out of cabinet. Never allow parts 

to rest on door opening as they will damage gasket material. keep 

gaskets clean and free of contaminants. failure to do so reduces gasket 

life and water sealing effectiveness.

(Continued on next page)

Содержание Tempest T-10

Страница 1: ...795 90914 0812 Operation and Maintenance Instructions Tempest Jet Spray Cabinet T 10 T 10S and T 20S...

Страница 2: ...ay it should be repaired replaced immediately by a qualified electrician Never use an extension cord Since operator safety is at all times a priority this unit is equipped with a Ground Fault Interrup...

Страница 3: ...d a heated Tempest 10 unit with a carbon steel cabinet some uses of water based cleaning materials will generate steam and water vapor Surfaces inside the cabinet will be subject to rusting This is su...

Страница 4: ...lve to this coupling to facilitate cleaning Daily Maintenance 1 Check fluid level in cleaning solution reservoir daily Assure level is at or above minimum level at all times Heavy constant use may war...

Страница 5: ...it is plugged in and the discharge hose is in place start operation by activating the lighted oil skimmer rocker switch located on the main control panel When oil is removed from the main reservoir th...

Страница 6: ...ch Ref Part No Description Door Water Containment Systems continued 21 745 07046 Hinge Seal Gasket 37 required 22 764 02614 11 Hinge Gasket End Support Mylar 2 5 x 1 5 23 603 28730 Door Gasket 24 605...

Страница 7: ...Ref Part No Description Door Water Containment Systems continued 22 745 07046 Hinge Seal Gasket 23 745 91198 Seal P Shaped 36 long 24 603 28730 Door Gasket 25 745 27905 72 36 Filler 26 605 27346 Glove...

Страница 8: ...inal material or product THE FOREGOING WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES WHETHER ORAL WRITTEN EXPRESSED IMPLIED OR STATUTORY GRAYMILLS CORPORATION MAKES NO OTHER WARRANTY OF ANY KIND EXPR...

Отзывы: