Combi V3, Combi Max and Vortex Combi models
52
13 - FAULT FINDING
Combi V3, Combi Max and Vortex Combi - Boiler faults on central heating and hot water
13.1
Boiler will not start
Low pressure cut-out activated (amber neon on panel lit).
No electrical supply to burner
.
No electrical supply to boiler
.
Check controls are switched on and calling for heat.
Overheat thermostat has operated (red neon on panel lit).
Boiler thermostat and/or overheat thermostat faulty
.
Fault with burner
.
No fuel supply
Oil tank empty
.
Isolating valve(s) in fuel supply line closed.
Fire valve closed.
Fuel line filter is blocked.
Oil supply line is air locked.
Excessive combustion air
.
Fault with burner
.
Insuf
ficient combustion air supply to burner
.
Incorrect or faulty nozzle fitted.
Fuel pressure too high.
Insuf
ficient combustion air supply to burner
.
Contaminated combustion air (balanced flue).
Insuf
ficient oil flow to burner due to restriction in supply line.
Excessive combustion air
.
Refill system to 0.5 - 1.0 bar
.
Check for 230 V at boiler terminal block.
Check boiler On/Of
f switch is set to 'ON'.
Set boiler thermostat to maximum.
Set 3-position Heating switch to 'Constant'.
Check and reset thermostat as necessary
.
Check for 230 V output from BURNER LIVE terminal of PCB.
Check continuity of overheat thermostat - replace as necessary
.
Press reset button - no more than twice.
If burner does not operate refer to burner fault finding chart.
Check tank and refill as necessary
.
Check and open valves as necessary
.
Check and reset as necessary
.
Check and clean as necessary
.
V
ent oil supply line at pump.
Reset burner air damper and check combustion.
Refer to burner fault finding chart.
Check flue terminal is clear (balanced flue).
Check room ventilation is adequate (conventional flue).
Check condition of burner fan.
Check air damper setting on burner
.
Check nozzle size and type and replace if necessary
.
Check fuel pressure and adjust as necessary
.
Check as for high smoke number (above).
Check the flue terminal is unobstructed
Connect vacuum gauge to pump and check pump vacuum.
Check for blockage in filter
, fire valve, valves or pipe and rectify
.
Reset burner air damper and check combustion.
F
AUL
T
POSSIBLE CAUSE
ACTION
Burner lights but goes to lock-out
Burner not lighting
Oil & electricity present at burner
Burner fir
es but smoke visible
fr
om flue or high smoke number
Burner pulsates
Burner cycles On and Off
Содержание Combi 70 V3
Страница 26: ...Combi V3 Combi Max and Vortex Combi models 26 5 GENERAL BOILER INFORMATION Fig 14 External flue Green system...
Страница 58: ...Combi V3 Combi Max and Vortex Combi models 58 13 FAULT FINDING Riello RDB burner fault finding 13 7...
Страница 60: ...Combi V3 Combi Max and Vortex Combi models 60 14 BURNER SPARE PARTS Burner Heads...
Страница 63: ...63 Combi V3 Combi Max and Vortex Combi models...